The Phoenix Contact UK 16 BU feed-through terminal block secures electrical conductors onto standard mounting rails to ensure safe and reliable circuit continuity inside electrical panels. Feed-through terminals are fundamental components for managing wire terminations, organizing complex wiring layouts, and maintaining system integrity across various industrial machinery. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Connectable conductor cross section solid-core (EF007337): 0.5 mm²
- Connectable conductor cross section multi-wired (EF007343): 0.5 mm²
- Rated current In (EF008250): 76 A
- Rated voltage (EF000228): 800 V
- Type of electrical connection 1 (EF002526): Screw connection
- Type of electrical connection 2 (EF002527): Screw connection
- Number of clamp positions per level (EF002660): 2
- Suitable for conductor material (EF012572): Aluminium/copper
- Mounting method (EF000003): DIN rail (top hat rail) 35 mm
- Operating temperature (EF002393): -60 °C
- Width (EF000008): 10.2 mm
- Height (EF000040): 42.5 mm
- Depth (EF000049): 54 mm
- Closing plate required (EF002525): Yes
- Colour (EF000007): Blue
- Internally connected stages (EF002661): Yes
More info
▲Key Commercial Data
| Orderkey | 3006098 |
|---|---|
| Packing unit | 50 pc |
| GTIN | 4017918091347 |
| Weight per Piece (excluding packing) | 20.150 g |
| Custom tariff number | 85369010 |
| Country of origin | DE (Germany) |
General
| Number of levels | 1 |
|---|---|
| Number of connections | 2 |
| Potentials | 1 |
| Color | blue |
| Insulating material | PA |
| Flammability rating according to UL 94 | V2 |
| Rated surge voltage | 8 kV |
| Degree of pollution | 3 |
| Overvoltage category | III |
| Insulating material group | I |
| Nominal current IN | 76 A |
| Nominal voltage UN | 800 V |
| Open side panel | Yes |
| Shock protection test specification | IEC 60529:2001-02 |
| Back of the hand protection | guaranteed |
| Result of surge voltage test | Test passed |
| Surge voltage test setpoint | 9.8 kV |
| Result of power-frequency withstand voltage test | Test passed |
| Power frequency withstand voltage setpoint | 2 kV |
| Result of the test for mechanical stability of terminal points (5 x conductor connection) | Test passed |
| Result of bending test | Test passed |
| Bending test rotation speed | 10 rpm |
| Bending test turns | 135 |
| Bending test conductor cross section/weight | 0.5 mm² / 0.3 kg |
| 10 mm² / 2 kg | |
| 16 mm² / 2.9 kg | |
| Tensile test result | Test passed |
| Conductor cross section tensile test | 0.5 mm² |
| Tractive force setpoint | 20 N |
| Conductor cross section tensile test | 10 mm² |
| Tractive force setpoint | 90 N |
| Conductor cross section tensile test | 16 mm² |
| Tractive force setpoint | 100 N |
| Result of tight fit on support | Test passed |
| Tight fit on carrier | NS 32/NS 35 |
| Setpoint | 5 N |
| Result of voltage-drop test | Test passed |
| Requirements, voltage drop | ≤ 3.2 mV |
| Result of temperature-rise test | Test passed |
| Short circuit stability result | Test passed |
| Conductor cross section short circuit testing | 10 mm² |
| Short-time current | 1.2 kA |
| Conductor cross section short circuit testing | 16 mm² |
| Short-time current | 1.92 kA |
| Result of thermal test | Test passed |
| Proof of thermal characteristics (needle flame) effective duration | 30 s |
| Relative insulation material temperature index (Elec., UL 746 B) | 125 °C |
| Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21)) | 125 °C |
Dimensions
| Width | 10.2 mm |
|---|---|
| End cover width | 1.5 mm |
| Length | 42.5 mm |
| Height NS 35/7,5 | 54 mm |
| Height NS 35/15 | 61.5 mm |
| Height NS 32 | 59 mm |
Connection data
| Connection method | Screw connection |
|---|---|
| Connection in acc. with standard | IEC / EN |
| Conductor cross section solid min. | 0.5 mm² |
| Conductor cross section solid max. | 16 mm² |
| Conductor cross section AWG min. | 20 |
| Conductor cross section AWG max. | 6 |
| Conductor cross section flexible min. | 0.5 mm² |
| Conductor cross section flexible max. | 10 mm² |
| Min. AWG conductor cross section, flexible | 20 |
| Max. AWG conductor cross section, flexible | 8 |
| Conductor cross section flexible, with ferrule without plastic sleeve min. | 0.5 mm² |
| Conductor cross section flexible, with ferrule without plastic sleeve max. | 10 mm² |
| Conductor cross section flexible, with ferrule with plastic sleeve min. | 0.5 mm² |
| Conductor cross section flexible, with ferrule with plastic sleeve max. | 10 mm² |
| 2 conductors with same cross section, solid min. | 0.5 mm² |
| 2 conductors with same cross section, solid max. | 4 mm² |
| 2 conductors with same cross section, stranded min. | 0.5 mm² |
| 2 conductors with same cross section, stranded max. | 4 mm² |
| 2 conductors with same cross section, stranded, TWIN ferrules with plastic sleeve, min. | 0.5 mm² |
| 2 conductors with same cross section, stranded, TWIN ferrules with plastic sleeve, max. | 6 mm² |
| 2 conductors with same cross section, stranded, ferrules without plastic sleeve, min. | 0.5 mm² |
| 2 conductors with same cross section, stranded, ferrules without plastic sleeve, max. | 4 mm² |
| Connection in acc. with standard | UL |
| Conductor cross section AWG min. | 24 |
| Conductor cross section AWG max. | 6 |
| Stripping length | 11 mm |
| Internal cylindrical gage | B6 |
| Screw thread | M4 |
| Tightening torque, min | 1.5 Nm |
| Tightening torque max | 1.8 Nm |
Standards and Regulations
| Connection in acc. with standard | CUL |
|---|---|
| IEC / EN | |
| Flammability rating according to UL 94 | V2 |
Environmental Product Compliance
| China RoHS | Environmentally friendly use period: unlimited = EFUP-e |
|---|---|
| No hazardous substances above threshold values |