Phoenix Contact part number BT-1S-230AC/O (model BT-1S-230AC/O 2800625 PHOENIX CONTACT Type 3 surge protection device) serves as a Type 3 surge protection device, engineered to provide fine protection for terminal electrical loads against harmful voltage spikes. Such modules are standard components in industrial distribution boards.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Max. continuous voltage AC (EF004198): 440 V
- Voltage protection level L-N (EF004236): 1.3 kV
- With remote signalling contact (EF000422): No
- Signalling at the device (EF004241): Optic
- Category type 3 (EF004231): Yes
- Degree of protection (IP) (EF005474): IP20
More info
▲Key Commercial Data
| Orderkey | 2800625 |
|---|---|
| Packing unit | 1 pc |
| Note | Made to Order (non-returnable) |
| Catalog page | Page 73 (C-4-2017) |
| GTIN | 4046356620437 |
| Weight per Piece (excluding packing) | 42.400 g |
| Custom tariff number | 85363030 |
| Country of origin | DE (Germany) |
Ambient conditions
| Degree of protection | IP20 |
|---|---|
| Ambient temperature (operation) | -30 °C ... 75 °C |
| Ambient temperature (storage/transport) | -30 °C ... 75 °C |
| Altitude | ≤ 2000 m (amsl (above mean sea level)) |
| Permissible humidity (operation) | 5 % ... 95 % |
General
| EN type | T3 |
|---|---|
| IEC power supply system | TN-S |
| TT | |
| IT with N conductor | |
| Number of ports | One |
| Mode of protection | L-N |
| L-PE | |
| N-PE | |
| Mounting type | Screw mounting |
| Color | jet black RAL 9005 |
| Housing material | PA 6.6 |
| Degree of pollution | 2 |
| Distance between live and grounded parts | 3 mm |
| Flammability rating according to UL 94 | V-0 |
| Type | Installation module |
| Number of positions | 2 |
| Surge protection fault message | optical |
Protective circuit
| Nominal voltage UN | 230/400 V AC (TN-S) |
|---|---|
| 230/400 V AC (TT - only in use with RCD) | |
| Nominal frequency fN | 50 Hz (60 Hz) |
| Maximum continuous operating voltage UC(L-N) | 275 V AC |
| Maximum continuous operating voltage UC(L-PE) | 440 V AC |
| Maximum continuous operating voltage UC(N-PE) | 440 V AC |
| Rated load current IL | 16 A (30 °C) |
| Residual current IPE | ≤ 3 µA |
| Nominal discharge current In(8/20) µs | 3 kA |
| Standby power consumption PC | ≤ 400 mVA |
| Reference test voltage UREF | 255 V AC |
| Max. discharge current Imax(8/20) µs | 8 kA |
| Combination wave UOC | 6 kV |
| Energy absorption symmetrical | 200 J (L-N (L)) |
| Enery absorption, asymmetrical | 230 J (L(N)-PE) |
| Voltage protection level Up(L-N) | ≤ 1.3 kV |
| Voltage protection level Up(L-PE) | ≤ 1.5 kV |
| Voltage protection level Up(N-PE) | ≤ 1.5 kV |
| TOV behavior at UT(L-N) | 335 V AC (5 s / withstand mode) |
| 440 V AC (120 min / safe failure mode) | |
| TOV behavior at UT(L-PE) | 440 V AC (5 s / withstand mode) |
| 440 V AC (120 min / withstand mode) | |
| 1455 V AC (200 ms / safe failure mode) | |
| TOV behavior at UT(N-PE) | 1200 V AC (200 ms / safe failure mode) |
| Response time tA(L-N) | ≤ 25 ns |
| Response time tA(L-PE) | ≤ 100 ns |
| Max. required back-up fuse | 16 A (MCB B) |
| Short-circuit current rating ISCCR | 1 kA AC |
| Max. backup fuse with branch wiring | 16 A (MCB B) |
| Maximum backup fuse for through wiring | 16 A (MCB B) |
Connection data
| Connection method | Spring-cage connection |
|---|---|
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross section solid | 0.2 mm² ... 2.5 mm² |
| Conductor cross section AWG | 24 ... 14 |
| Stripping length | 10 mm |