Type 2 surge protection plug Plug-in type 2 surge protection with high-power varistor for VAL-MS base element, with thermal control, optical fault indication. Workmanship: 580 V AC

Automation > Accessories/spare parts for surge protection power supply systems
Trabtech (TT)

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

The VAL-MS 580-ST type 2 surge protection plug manufactured by Phoenix Contact provides reliable clamping and diversion of overvoltage transients in high-voltage industrial distribution systems. Pluggable arrestor units ensure continuous facility safety with minimal maintenance interruption.

Pricing, availability and lead time are confirmed per enquiry through an RFQ.

  • Orderkey: 2920434
  • Packing unit: 10 pc
  • Catalog page: Page 62 (C-4-2017)
  • GTIN: 4046356163682
  • Weight per Piece (excluding packing): 59.630 g
  • Custom tariff number: 85363030
  • Country of origin: DE (Germany)
  • Height: 52.4 mm
  • Width: 17.5 mm
  • Depth: 55.3 mm
  • Horizontal pitch: 1 Div.
  • Degree of protection: IP20
  • Ambient temperature (operation): -40 °C ... 80 °C
  • Ambient temperature (storage/transport): -40 °C ... 80 °C
  • Altitude: ≤ 2000 m (amsl (above mean sea level))
  • Permissible humidity (operation): 5 % ... 95 %

More info

▲

Key Commercial Data

Orderkey2920434
Packing unit10 pc
Catalog pagePage 62 (C-4-2017)
GTIN4046356163682
Weight per Piece (excluding packing)59.630 g
Custom tariff number85363030
Country of originDE (Germany)

Dimensions

Height52.4 mm
Width17.5 mm
Depth55.3 mm
Horizontal pitch1 Div.

Ambient conditions

Degree of protectionIP20
Ambient temperature (operation)-40 °C ... 80 °C
Ambient temperature (storage/transport)-40 °C ... 80 °C
Altitude≤ 2000 m (amsl (above mean sea level))
Permissible humidity (operation)5 % ... 95 %
Shock (operation)25g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
Vibration (operation)5g (10 ... 500 Hz / 2.5 h / X, Y, Z)

General

IEC test classificationII
T2
EN typeT2
IEC power supply systemTN
IT
Mode of protectionL-PE
L-PEN
Mounting typeon base element
Colorjet black RAL 9005
Housing materialPA 6.6
Degree of pollution2
Distance between live and grounded parts5 mm
Flammability rating according to UL 94V-0
TypeMale
Number of positions1
Surge protection fault messageoptical

Additional descriptions

NoteFor use in all low-voltage systems between L-PEN.
Only for use in IT systems between L-PE if the bodies of the equipment in the low-voltage system are connected to the grounding system of the transformer station. (common grounding of the HV transformer station and the bodies of the LV consumer's installation. RE= RAaccording to IEC 60364-4-442/VDE 0100-442 Figure 44D/example a)

Protective circuit

Nominal voltage UN400/690 V AC (TN)
500 V AC (IT)
Nominal frequency fN50 Hz (60 Hz)
Maximum continuous voltage UC580 V AC
Residual current IPE≤ 0.25 mA
Standby power consumption PC≤ 150 mVA
Nominal discharge current In(8/20) µs15 kA
Maximum discharge current Imax(8/20) µs30 kA
Short-circuit current rating ISCCR25 kA
Voltage protection level Up≤ 2.5 kV
Residual voltage Ures≤ 2.5 kV (at In)
≤ 2.3 kV (at 10 kA)
≤ 2.1 kV (at 5 kA)
≤ 1.9 kV (at 3 kA)
TOV behavior at UT690 V AC (5 s / withstand mode)
762 V AC (120 min / withstand mode)
Response time tA≤ 25 ns
Max. backup fuse with branch wiring125 A (gG)

Connection data

Connection methodpluggable

UL specifications

SPD Type4CA
Maximum continuous operating voltage MCOV (L-N)580 V AC
Nom. voltage400 V AC
Mode of protectionL-N
Power distribution systemSingle phase
Nominal frequency50/60 Hz
Measured limiting voltage MLV (L-N)2310 V
Nominal discharge current In(L-N)10 kA

Standards and Regulations

Standards/regulationsIEC 61643-11 2011
EN 61643-11 2012

Environmental Product Compliance

China RoHSEnvironmentally friendly use period: unlimited = EFUP-e
No hazardous substances above threshold values

Classifications


Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.