PHOENIX CONTACT VAL-MS 385/80 ST VAL-MS 385/80 ST 2920353 PHOENIX CONTACT Type 2 surge protection plug View larger
Images are for illustrative purposes only. Please refer to data sheet for details

VAL-MS 385/80 ST 2920353 PHOENIX CONTACT Type 2 surge protection plug

VAL-MS 385/80 ST

2920353

PHOENIX CONTACT

10 Pcs.

Type 2 surge protection plug Plug-in surge protection type 2 with varistor for VAL-MS 385/80/..., with thermal control, optical defect indication.

Automation > Accessories/spare parts for surge protection power supply systems
Trabtech (TT)

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

Phoenix Contact item VAL-MS 385/80 ST acts as a heavy-duty Type 2 surge protection plug engineered to discharge high transient currents in industrial electrical distributions. These pluggable arresters provide reliable overvoltage defense for machinery and control infrastructure against grid-side disturbances. Specific pricing, availability, and lead time are confirmed per enquiry through an RFQ.

  • Orderkey: 2920353
  • Packing unit: 10 pc
  • Minimum order quantity: 10 pc
  • Note: Made to Order (non-returnable)
  • Catalog page: Page 49 (C-6-2015)
  • GTIN: 4046356157353
  • Weight per Piece (excluding packing): 91.000 g
  • Custom tariff number: 85363030
  • Country of origin: DE (Germany)
  • Height: 47 mm
  • Width: 17.7 mm
  • Depth: 67.3 mm
  • Horizontal pitch: 1 Div.
  • Degree of protection: IP20
  • Ambient temperature (operation): -40 °C ... 80 °C
  • Ambient temperature (storage/transport): -40 °C ... 80 °C

More info

▲

Key Commercial Data

Orderkey2920353
Packing unit10 pc
Minimum order quantity10 pc
NoteMade to Order (non-returnable)
Catalog pagePage 49 (C-6-2015)
GTIN4046356157353
Weight per Piece (excluding packing)91.000 g
Custom tariff number85363030
Country of originDE (Germany)

Dimensions

Height47 mm
Width17.7 mm
Depth67.3 mm
Horizontal pitch1 Div.

Ambient conditions

Degree of protectionIP20
Ambient temperature (operation)-40 °C ... 80 °C
Ambient temperature (storage/transport)-40 °C ... 80 °C
Altitude≤ 2000 m (amsl (above mean sea level))
Permissible humidity (operation)5 % ... 95 %
Shock (operation)30g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
Vibration (operation)7.5g (10 ... 500 Hz / 2.5 h / X, Y, Z)

General

IEC test classificationII
T2
EN typeT2
IEC power supply systemTN-C
TT
Mode of protectionL-N
L-PEN
Mounting typeon base element
Colorjet black RAL 9005
Housing materialPA 6.6
PBT
Degree of pollution2
Flammability rating according to UL 94V-0
TypeMale
Surge protection fault messageoptical

Protective circuit

Nominal voltage UN240/415 V AC (TN-C)
240/415 V AC (TT)
Nominal frequency fN50 Hz (60 Hz)
Maximum continuous voltage UC385 V AC
Residual current IPE≤ 600 µA
Standby power consumption PC≤ 230 mVA
Nominal discharge current In(8/20) µs40 kA
Maximum discharge current Imax(8/20) µs80 kA
Impulse discharge current (10/350) µs, charge1.25 As
Impulse discharge current (10/350) µs, specific energy1.56 kJ/Ω
Impulse discharge current (10/350) µs, peak value limp2.5 kA
Short-circuit current rating ISCCR25 kA
Voltage protection level Up≤ 2 kV
Residual voltage Ures≤ 2 kV (at In)
≤ 1.3 kV (at 10 kA)
≤ 1.2 kV (at 5 kA)
≤ 1.15 kV (at 3 kA)
TOV behavior at UT480 V AC (5 s / withstand mode)
457 V AC (120 min / withstand mode)
Response time tA≤ 25 ns
Max. backup fuse with branch wiring250 A (gG)

Connection data

Connection methodpluggable

UL specifications

SPD Type4CA
Maximum continuous operating voltage MCOV (L-N)385 V AC
Nom. voltage240 V AC
Mode of protectionL-N
Power distribution systemSingle phase
Nominal frequency50/60 Hz
Measured limiting voltage MLV (L-N)2710 V
Nominal discharge current In(L-N)20 kA

Standards and Regulations

Standards/regulationsIEC 61643-11 2011
EN 61643-11 2012

Classifications


Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.