View larger
TTC-6-TVSD-C-12DC-UT-I 2906829 PHOENIX CONTACT Fine surge protection with integrated status indicator for a ..
TTC-6-TVSD-C-12DC-UT-I
2906829
PHOENIX CONTACT
1 Pcs.
Automation > Surge protection device for data networks/MCR-technology
Trabtech (TT)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Providing precise voltage limitation, the Phoenix Contact TTC-6-TVSD-C-12DC-UT-I 2906829 PHOENIX CONTACT Fine surge protection with integrated status indicator for a .. shields sensitive automation electronics from high-frequency and transient electrical disturbances. Fine surge protection devices are widely implemented in measurement and control routing to protect low-voltage electronic nodes from potential surge damage.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Product type: Surge protection for MCR technology
- Product family: TERMITRAB complete
- IEC test classification: C1
- Type: DIN rail module, one-piece
- Surge protection fault message: optical
- Data management status Article revision: 08
- Insulation characteristics Overvoltage category: III
- Pollution degree: 2
- Nominal voltage U N: 12 V DC
- Connection method: Screw connection
- Screw thread: M3
- Tightening torque: 0.5 Nm ... 0.6 Nm
- Conductor cross section flexible: 0.2 mm² ... 2.5 mm²
- Conductor cross section rigid: 0.2 mm² ... 4 mm²
- Conductor cross section AWG: 24 ... 12
- Width: 6.2 mm
More info
▲| Product type | Surge protection for MCR technology |
| Product family | TERMITRAB complete |
| IEC test classification | C1 |
| C3 | |
| Type | DIN rail module, one-piece |
| Surge protection fault message | optical |
| Data management status | |
| Article revision | 08 |
| Insulation characteristics | |
| Overvoltage category | III |
| Pollution degree | 2 |
| Nominal voltage UN | 12 V DC |
| Connection method | Screw connection |
| Screw thread | M3 |
| Tightening torque | 0.5 Nm ... 0.6 Nm |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross section rigid | 0.2 mm² ... 4 mm² |
| Conductor cross section AWG | 24 ... 12 |
| Dimensional drawing | |
| Width | 6.2 mm |
| Height | 92 mm |
| Depth | 69.5 mm (incl. DIN rail 7.5 mm) |
| Color | gray (RAL 7042) |
| Flammability rating according to UL 94 | V-0 |
| Insulating material | PBT |
| Housing material | PBT |
| Mechanical data | |
| Open side panel | Yes |
| Direction of action | Line-Earth Ground |
| Maximum continuous voltage UC | 15 V DC |
| 10 V AC | |
| Rated current | 10 A (60 °C) |
| Operating effective current ICat UC | ≤ 5 µA |
| Residual current IPE | ≤ 5 µA |
| Nominal discharge current In(8/20) µs (line-ground) | 300 A |
| Voltage protection level Up(line-earth) | ≤ 25 V (C1 - 0,6 kV / 300 A) |
| ≤ 22 V (C3 - 25 A) | |
| ≤ 25 V (C3 - 60 A) | |
| Response time tA(line-earth) | ≤ 1 ns |
| Input attenuation aE, asym. | typ. 0.3 dB (≤ 340 kHz/150 Ω) |
| Cut-off frequency fg (3 dB), asym. (PE) in 150 Ω system | typ. 1.1 MHz |
| Capacity (Core-Earth) | 2 nF |
| Resistance per path | ≤ 100 mΩ |
| Surge protection fault message | optical |
| Impulse durability (line-earth) | C1 - 0.6 kV/300 A |
| C3 - 60 A |
| Ambient conditions | |
| Degree of protection | IP20 (with end cover) |
| Ambient temperature (operation) | -40 °C ... 85 °C |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Altitude | ≤ 4000 m (amsl) |
| Permissible humidity (operation) | 5 % ... 95 % |
| Standards/specifications | IEC 61643-21 |
| Note | 2000 + corrigendum 2001 + A1:2008, modified + A2:2012 |
| EN 61643-21 | |
| Standards/specifications | EN 61643-21 |
| Note | 2001 + A1:2009 + A2:2013 |
| Mounting type | DIN rail: 35 mm |