View larger
TTC-6P-3-HF-M-12DC-UT-I 2906744 PHOENIX CONTACT Surge protection, consisting of protective plug and base ele..
TTC-6P-3-HF-M-12DC-UT-I
2906744
PHOENIX CONTACT
1 Pcs.
Automation > Surge protection device for data networks/MCR-technology
Trabtech (TT)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Built for precise modular installation, the TTC-6P-3-HF-M-12DC-UT-I 2906744 PHOENIX CONTACT surge protection, consisting of protective plug and base ele protects high-frequency signal circuits from damaging electrical transients. Control system integrators utilize these divisible DIN-rail modules to safeguard sensitive communication and measurement loops in complex industrial architectures.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Product type: Surge protection for information technology
- Product family: TERMITRAB complete
- IEC test classification: C1
- Type: DIN rail module, two-section, divisible
- Data management status Article revision: 07
- Insulation characteristics Overvoltage category: III
- Pollution degree: 2
- Nominal voltage U N: 12 V DC
- Connection method: Screw connection
- Screw thread: M3
- Tightening torque: 0.5 Nm ... 0.6 Nm
- Conductor cross section flexible: 0.2 mm² ... 2.5 mm²
- Conductor cross section rigid: 0.2 mm² ... 4 mm²
- Conductor cross section AWG: 24 ... 12
- Maximum input current: 600 mA (T4 / ≤ 30 °C)
- Maximum input voltage: 15 V DC
More info
▲| Product type | Surge protection for information technology |
| Product family | TERMITRAB complete |
| IEC test classification | C1 |
| C2 | |
| C3 | |
| D1 | |
| Type | DIN rail module, two-section, divisible |
| Data management status | |
| Article revision | 07 |
| Insulation characteristics | |
| Overvoltage category | III |
| Pollution degree | 2 |
| Nominal voltage UN | 12 V DC |
| Connection method | Screw connection |
| Screw thread | M3 |
| Tightening torque | 0.5 Nm ... 0.6 Nm |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross section rigid | 0.2 mm² ... 4 mm² |
| Conductor cross section AWG | 24 ... 12 |
| Maximum input current | 600 mA (T4 / ≤ 30 °C) |
| 500 mA (T4 / > 30 °C ... ≤ 50 °C) | |
| 400 mA (T4 / > 50 °C ... ≤ 70 °C) | |
| Maximum input voltage | 15 V DC |
| Altitude | ≤ 2000 m (amsl) |
| Ambient temperature (operation) | -40 °C ... 70 °C (T4) |
| Dimensional drawing | |
| Width | 6.2 mm +0.1 mm |
| Height | 105.8 mm |
| Depth | 100 mm (incl. DIN rail 7.5 mm) |
| Color (Base element) | gray (RAL 7042) |
| Color (Male connector) | light gray (RAL 7035) |
| Flammability rating according to UL 94 | V-0 |
| Insulating material | PBT |
| Housing material | PBT |
| Mechanical data | |
| Open side panel | No |
| Direction of action | Line-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-Earth Ground |
| Maximum continuous voltage UC | 15 V DC |
| 10 V AC | |
| Rated current | 600 mA (56 °C) |
| Operating effective current ICat UC | ≤ 100 µA |
| Residual current IPE | ≤ 200 µA |
| Nominal discharge current In(8/20) µs (line-line) | 5 kA |
| Nominal discharge current In(8/20) µs (line-ground) | 5 kA |
| Pulse discharge current Iimp(10/350) µs (line-line) | 0.5 kA |
| Pulse discharge current Iimp(10/350) µs (line-earth) | 0.5 kA |
| Total discharge current Itotal(8/20) µs | 10 kA |
| Voltage protection level Up(line-line) | ≤ 145 V (C1 - 1 kV / 500 A) |
| ≤ 260 V (C2 - 10 kV / 5 kA) | |
| ≤ 25 V (C3 - 25 A) | |
| ≤ 30 V (C3 - 100 A) | |
| Voltage protection level Up(line-earth) | ≤ 80 V (C1 - 1 kV / 500 A) |
| ≤ 95 V (C2 - 10 kV / 5 kA) | |
| ≤ 25 V (C3 - 25 A) | |
| ≤ 30 V (C3 - 100 A) | |
| Voltage protection level Upstatic (line-line) | ≤ 40 V (C1 - 1 kV / 500 A) |
| ≤ 95 V (C2 - 10 kV / 5 kA) | |
| Voltage protection level Upstatic (line-earth) | ≤ 40 V (C1 - 1 kV / 500 A) |
| ≤ 95 V (C2 - 10 kV / 5 kA) | |
| Response time tA(line-line) | ≤ 1 ns |
| Response time tA(line-earth) | ≤ 1 ns |
| Input attenuation aE, sym. | typ. 0.3 dB (≤ 8.7 MHz/150 Ω) |
| Input attenuation aE, asym. | typ. 0.3 dB (≤ 10.5 MHz / 150 Ω) |
| Cut-off frequency fg (3 dB), sym. in 150 Ω system | typ. 60 MHz |
| Cut-off frequency fg (3 dB), asym. (PE) in 150 Ω system | typ. 60 MHz |
| Capacity (Core-Core) | typ. 32 pF |
| Capacity (Core-Earth) | typ. 32 pF |
| Resistance per path | 1.65 Ω ±20 % |
| Surge protection fault message | optical |
| Max. required back-up fuse | 630 mA (FF) |
| Impulse durability (line-line) | C1 - 1 kV / 500 A |
| C2 - 10 kV / 5 kA | |
| C3 - 100 A | |
| Impulse durability (line-earth) | C1 - 1 kV / 500 A |
| C2 - 10 kV / 5 kA | |
| C3 - 100 A | |
| D1 - 500 A | |
| Pulse reset time (line-line) | ≤ 30 ms |
| Pulse reset time (line-earth) | ≤ 30 ms |
| Additional technical data | |
| Max. total discharge current Itotal max(8/20) µs | 20 kA (1x - non Ex) |
| Ambient conditions | |
| Degree of protection | IP20 |
| Ambient temperature (operation) | -40 °C ... 85 °C |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Altitude | ≤ 4000 m (amsl) |
| Permissible humidity (operation) | 5 % ... 95 % |
| Standards/specifications | IEC 61643-21 |
| Note | 2000 + corrigendum 2001 + A1:2008, modified + A2:2012 |
| EN 61643-21 | |
| Standards/specifications | EN 61643-21 |
| Note | 2001 + A1:2009 + A2:2013 |
| Standards/specifications | IEC 60079-0 |
| Note | 2017 |
| Standards/specifications | IEC 60079-7 |
| Note | 2017 |
| Standards/specifications | EN IEC 60079-0 |
| Note | 2018 |
| Standards/specifications | EN IEC 60079-7 |
| Note | 2015 + A1:2018 |
| Mounting type | DIN rail: TH 35 - 7.5 mm |