PHOENIX CONTACT TTC-6P-3-HF-F-12DC-PT-I TTC-6P-3-HF-F-12DC-PT-I 1065314 PHOENIX CONTACT Surge protection, consisting of protective plug and base ele.. View larger
Images are for illustrative purposes only. Please refer to data sheet for details

TTC-6P-3-HF-F-12DC-PT-I 1065314 PHOENIX CONTACT Surge protection, consisting of protective plug and base ele..

TTC-6P-3-HF-F-12DC-PT-I

1065314

PHOENIX CONTACT

1 Pcs.

Surge protection, consisting of protective plug and base element, with integrated status indicator for three signal wires with common reference potential. For HF applications and telecommunications interfaces without supply voltage. Indirect grounding via gas-filled surge arrester. Surge protection, consisting of plug-in protection and base element, with integrated status indicator for three signal conductors with common reference potential. For high-frequency applications and telecommunication interfaces without supply voltage. Indirect grounding by gas discharger.

Automation > Surge protection device for data networks/MCR-technology
Trabtech (TT)

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

Phoenix Contact manufactures the TTC-6P-3-HF-F-12DC-PT-I surge protection assembly, consisting of a protective plug and base element built to divert harmful electrical transients away from delicate electronics. Devices of this configuration are typically deployed on signal and measurement lines within industrial control architectures. Pricing, availability and lead time are confirmed per enquiry through an RFQ.

  • Orderkey: 1065314
  • Packing unit: 1 pc
  • Catalog page: Page 171 (C-4-2019)
  • GTIN: 4055626725789
  • Weight per Piece (excluding packing): 0.000 g
  • Custom tariff number: 85363010
  • Country of origin: DE (Germany)

More info

▲

Key Commercial Data

Orderkey1065314
Packing unit1 pc
Catalog pagePage 171 (C-4-2019)
GTIN4055626725789
Weight per Piece (excluding packing)0.000 g
Custom tariff number85363010
Country of originDE (Germany)

Drawings



Diagram

Dimensional drawing



Circuit diagram

Back to top

Dimensions

Height105.8 mm
Width6.2 mm +0.1 mm
Depth100 mm (incl. DIN rail 7.5 mm)
Back to top

Ambient conditions

Ambient temperature (operation)-40 °C ... 85 °C
Ambient temperature (storage/transport)-40 °C ... 85 °C
Permissible humidity (operation)5 % ... 95 %
Altitude≤ 4000 m (amsl (above mean sea level))
Degree of protectionIP20
Back to top

General

Housing materialPBT
Flammability rating according to UL 94V-0
Colortraffic grey A RAL 7042
light grey RAL 7035
Mounting typeDIN rail: TH 35 - 7.5 mm
TypeDIN rail module, two-section, divisible
Direction of actionLine-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-Earth Ground
Back to top

Protective circuit

IEC test classificationC1
C2
C3
D1
Nominal voltage UN12 V DC
Maximum continuous voltage UC15 V DC
10 V AC
Rated current600 mA (56 °C)
Operating effective current ICat UC≤ 100 µA
Residual current IPE≤ 1 µA
Nominal discharge current In(8/20) µs (line-line)5 kA
Nominal discharge current In(8/20) µs (line-earth)5 kA
Nominal discharge current In(8/20) µs (line-signal ground)5 kA
Pulse discharge current Iimp(10/350) µs (line-line)0.5 kA
Pulse discharge current Iimp(10/350) µs (line-earth)0.5 kA
Pulse discharge current Iimp(10/350) µs (line-signalground)0.5 kA
Total discharge current Itotal(8/20) µs10 kA
Voltage protection level Up(line-line)≤ 145 V (C1 - 1 kV/500 A)
≤ 260 V (C2 - 10 kV / 5 kA)
≤ 25 V (C3 - 25 A)
≤ 30 V (C3 - 100 A)
Voltage protection level Up(line-earth)≤ 750 V (C1 - 1 kV/500 A)
≤ 750 V (C2 - 10 kV / 5 kA)
≤ 1.1 kV (C3 - 25 A)
≤ 1.2 kV (C3 - 100 A)
Voltage protection level Up(line-signalground)≤ 80 V (C1 - 1 kV/500 A)
≤ 95 V (C2 - 10 kV / 5 kA)
≤ 25 V (C3 - 25 A)
≤ 30 V (C3 - 100 A)
Voltage protection level Upstatic (line-line)≤ 40 V (C1 - 1 kV/500 A)
≤ 95 V (C2 - 10 kV / 5 kA)
Voltage protection level Upstatic (line-earth)≤ 40 V (C1 - 1 kV/500 A)
≤ 95 V (C2 - 10 kV / 5 kA)
Voltage protection level Upstatic (line-signalground)≤ 750 V (C1 - 1 kV/500 A)
≤ 750 V (C2 - 10 kV / 5 kA)
Response time tA(line-line)≤ 1 ns
Response time tA(line-signalground)≤ 1 ns
Response time tA(line-earth)≤ 100 ns
Input attenuation aE, sym.typ. 0.3 dB (≤ 8.7 MHz / 150 Ω)
Input attenuation aE, asym.typ. 0.3 dB (≤ 10.5 MHz / 150 Ω)
Cut-off frequency fg (3 dB), sym. in 150 Ohm systemtyp. 60 MHz
Cut-off frequency fg (3 dB), asym. (GND) in 150 Ohm systemtyp. 60 MHz
Capacity (line-line)typ. 32 pF
Capacity (line-signalground)typ. 32 pF
Resistance per path1.65 Ω ±20 %
Max. required back-up fuse630 mA (FF)
Impulse durability (line-line)C1 - 1 kV / 500 A
C2 - 10 kV / 5 kA
C3 - 100 A
Impulse durability (line-earth)C1 - 1 kV / 500 A
C2 - 10 kV / 5 kA
C3 - 100 A
D1 - 500 A
Impulse durability (line-signalground)C1 - 1 kV / 500 A
C2 - 10 kV / 5 kA
C3 - 100 A
D1 - 500 A
Pulse reset time (line-line)≤ 30 ms
Pulse reset time (line-earth)≤ 30 ms
Pulse reset time (line-signalground)≤ 30 ms
Back to top

Additional technical data

Max. total discharge current Itotal max(8/20) µs20 kA (1x)
Back to top

Connection data

Connection methodPush-in connection
Stripping length8 mm
Conductor cross section flexible0.2 mm² ... 2.5 mm²
Conductor cross section solid0.2 mm² ... 4 mm²
Conductor cross section AWG24 ... 12
Back to top

Standards and Regulations

Standards/specificationsIEC 61643-21 2000 + corrigendum 2001 + A1:2008, modified + A2:2012
EN 61643-21 2001 + A1:2009 + A2:2013
Back to top

Environmental Product Compliance

REACh SVHC
Lead 7439-92-1
China RoHSEnvironmentally Friendly Use Period = 50
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”
Back to top

Classifications

eCl@ss

eCl@ss 6.027130800
eCl@ss 7.027130807
eCl@ss 8.027130807
eCl@ss 9.027130807
Back to top