View larger
TTC-6P-3-EX-24DC-UT-I 1064665 PHOENIX CONTACT Surge protection, consisting of protective plug and base eleme..
TTC-6P-3-EX-24DC-UT-I
1064665
PHOENIX CONTACT
1 Pcs.
Automation > Combined arrester for data networks/MCR-technology
Trabtech (TT)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Consisting of a protective plug and base element, the Phoenix Contact TTC-6P-3-EX-24DC-UT-I surge protection system acts as a modular transient voltage limiter for industrial signal loops. Such surge protection assemblies are typically mounted on DIN rails inside control enclosures to shield delicate automation electronics from electrical disturbances. Final pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Orderkey: 1064665
- Packing unit: 1
- Catalog page: Page 158 (C-4-2019)
- GTIN: 4055626722733
- Custom tariff number: 85363010
- Height: 105.8 mm
- Width: 6.2 mm +0.1 mm
- Depth: 100 mm (incl. DIN rail 7.5 mm)
- Ambient temperature (operation): -40 °C ... 85 °C
- Ambient temperature (storage/transport): -40 °C ... 85 °C
- Permissible humidity (operation): 5 % ... 95 %
- Altitude: ≤ 2000 m (amsl (above mean sea level))
- Degree of protection: IP20
- Housing material: PBT
- Flammability rating according to UL 94: V-0
- Color: sky blue RAL 5015
More info
▲Key Commercial Data
| Orderkey | 1064665 |
|---|---|
| Packing unit | 1 |
| Catalog page | Page 158 (C-4-2019) |
| GTIN | 4055626722733 |
| Custom tariff number | 85363010 |
Ambient conditions
| Ambient temperature (operation) | -40 °C ... 85 °C |
|---|---|
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Permissible humidity (operation) | 5 % ... 95 % |
| Altitude | ≤ 2000 m (amsl (above mean sea level)) |
| Degree of protection | IP20 |
General
| Housing material | PBT |
|---|---|
| Flammability rating according to UL 94 | V-0 |
| Color | sky blue RAL 5015 |
| Mounting type | DIN rail: TH 35 - 7.5 mm |
| Type | DIN rail module, two-section, divisible |
| Direction of action | Line-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-Earth Ground |
Protective circuit
| IEC test classification | C1 |
|---|---|
| C2 | |
| C3 | |
| D1 | |
| Nominal voltage UN | 24 V DC |
| Maximum continuous voltage UC | 30 V DC |
| Rated current | 5 A (55 °C) |
| Operating effective current ICat UC | ≤ 5 µA |
| Residual current IPE | ≤ 1 µA |
| Nominal discharge current In(8/20) µs (line-line) | 0.5 kA |
| Nominal discharge current In(8/20) µs (line-earth) | 5 kA |
| Pulse discharge current Iimp(10/350) µs (line-earth) | 0.5 kA |
| Total discharge current Itotal(8/20) µs | 10 kA |
| Voltage protection level Up(line-line) | ≤ 68 V (C1 - 1 kV/500 A) |
| ≤ 50 V (C3 - 100 A) | |
| ≤ 50 V (C3 - 25 A) | |
| Voltage protection level Up(line-earth) | ≤ 700 V (C1 - 1 kV/500 A) |
| ≤ 900 V (C2 - 10 kV / 5 kA) | |
| Response time tA(line-line) | ≤ 1 ns |
| Response time tA(line-earth) | ≤ 100 ns |
| Input attenuation aE, sym. | typ. 0.3 dB (≤ 12 MHz / 150 Ω) |
| Cut-off frequency fg (3 dB), sym. in 150 Ohm system | typ. 60 MHz |
| Capacity (line-line) | typ. 30 pF |
| Capacity (line-earth) | typ. 30 pF |
| Resistance per path | < 0.1 Ω |
| Max. required back-up fuse | 5 A (F) |
| Impulse durability (line-line) | C1 - 1 kV / 500 A |
| C3 - 100 A | |
| Impulse durability (line-earth) | C1 - 1 kV / 500 A |
| C2 - 10 kV / 5 kA | |
| D1 - 500 A | |
| Pulse reset time (line-line) | ≤ 30 ms |
| Pulse reset time (line-earth) | ≤ 500 ms |
Connection data
| Connection method | Screw connection |
|---|---|
| Screw thread | M3 |
| Tightening torque | 0.5 Nm ... 0.6 Nm |
| Stripping length | 8 mm |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross section solid | 0.2 mm² ... 4 mm² |
| Conductor cross section AWG | 24 ... 12 |
Standards and Regulations
| Standards/specifications | EN 60079-0 2012 + A11:2013 |
|---|---|
| EN 60079-11 2012 | |
| EN 61643-21 2001 + A1:2009 + A2:2013 | |
| IEC 60079-0 2011 (modified) + corrigendum 2012 + corrigendum 2013 | |
| IEC 60079-11 2008 | |
| IEC 61643-21 2000 + corrigendum 2001 + A1:2008, modified + A2:2012 |
General
| Maximum inner capacitance Ci | negligible |
|---|---|
| Max. internal inductance Li | negligible |
| Max. input current Ii | 400 mA (T4 / ≤ 50 °C) |
| 350 mA (T6 / ≤ 35 °C) | |
| Max. input voltage Ui | 30 V DC |
| Ambient temperature (operation) | -40 °C ... 35 °C (T6 / 85 °C) |
| -40 °C ... 50 °C (T4 / 135 °C) |
Environmental Product Compliance
| REACh SVHC | Lead 7439-92-1 |
|---|---|
| China RoHS | Environmentally Friendly Use Period = 50 |
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |