View larger
TTC-6P-3-24DC-PT-I 1061383 PHOENIX CONTACT Surge protection, consisting of protective plug and base element,..
TTC-6P-3-24DC-PT-I
1061383
PHOENIX CONTACT
1 Pcs.
Automation > Surge protection device for data networks/MCR-technology
Trabtech (TT)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
The Phoenix Contact TTC-6P-3-24DC-PT-I surge protection, consisting of protective plug and base element,.. is designed to safeguard three-wire low-voltage control circuits against destructive transient voltages. Modular pluggable surge devices allow facility technicians to perform rapid component replacements without disturbing fixed field wiring. Pricing, availability, and lead time are confirmed per enquiry through an RFQ.
- Orderkey: 1061383
- Packing unit: 1 pc
- Catalog page: Page 143 (C-4-2019)
- GTIN: 4055626715742
- Weight per Piece (excluding packing): 0.000 g
- Custom tariff number: 85363010
- Country of origin: DE (Germany)
More info
▲Key Commercial Data
| Orderkey | 1061383 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 143 (C-4-2019) |
| GTIN | 4055626715742 |
| Weight per Piece (excluding packing) | 0.000 g |
| Custom tariff number | 85363010 |
| Country of origin | DE (Germany) |
Ambient conditions
| Ambient temperature (operation) | -40 °C ... 85 °C |
|---|---|
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Permissible humidity (operation) | 5 % ... 95 % |
| Altitude | ≤ 4000 m (amsl (above mean sea level)) |
| Degree of protection | IP20 |
General
| Housing material | PBT |
|---|---|
| Flammability rating according to UL 94 | V-0 |
| Color | traffic grey A RAL 7042 |
| light grey RAL 7035 | |
| Mounting type | DIN rail: TH 35 - 7.5 mm |
| Type | DIN rail module, two-section, divisible |
| Direction of action | Line-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-Earth Ground |
Protective circuit
| IEC test classification | C1 |
|---|---|
| C2 | |
| C3 | |
| D1 | |
| Nominal voltage UN | 24 V DC |
| Maximum continuous voltage UC | 30 V DC |
| 21 V AC | |
| Rated current | 5 A (55 °C) |
| Operating effective current ICat UC | ≤ 5 µA |
| Residual current IPE | ≤ 1 µA |
| Nominal discharge current In(8/20) µs (line-line) | 0.5 kA |
| Nominal discharge current In(8/20) µs (line-earth) | 5 kA |
| Pulse discharge current Iimp(10/350) µs (line-earth) | 0.5 kA |
| Total discharge current Itotal(8/20) µs | 10 kA |
| Voltage protection level Up(line-line) | ≤ 68 V (C1 - 1 kV/500 A) |
| ≤ 50 V (C3 - 100 A) | |
| ≤ 50 V (C3 - 25 A) | |
| Voltage protection level Up(line-earth) | ≤ 700 V (C1 - 1 kV/500 A) |
| ≤ 900 V (C2 - 10 kV / 5 kA) | |
| Response time tA(line-line) | ≤ 1 ns |
| Response time tA(line-earth) | ≤ 100 ns |
| Input attenuation aE, sym. | typ. 0.3 dB (≤ 12 MHz / 150 Ω) |
| Cut-off frequency fg (3 dB), sym. in 150 Ohm system | typ. 60 MHz |
| Capacity (line-line) | typ. 30 pF |
| Capacity (line-earth) | typ. 30 pF |
| Resistance per path | < 0.1 Ω |
| Max. required back-up fuse | 5 A (F) |
| Impulse durability (line-line) | C1 - 1 kV / 500 A |
| C3 - 100 A | |
| Impulse durability (line-earth) | C1 - 1 kV / 500 A |
| C2 - 10 kV / 5 kA | |
| D1 - 500 A | |
| Pulse reset time (line-line) | ≤ 30 ms |
| Pulse reset time (line-earth) | ≤ 500 ms |
Connection data
| Connection method | Push-in connection |
|---|---|
| Stripping length | 8 mm |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross section solid | 0.2 mm² ... 4 mm² |
| Conductor cross section AWG | 24 ... 12 |
Standards and Regulations
| Standards/specifications | IEC 61643-21 2000 + corrigendum 2001 + A1:2008, modified + A2:2012 |
|---|---|
| EN 61643-21 2001 + A1:2009 + A2:2013 |
Environmental Product Compliance
| REACh SVHC | Lead 7439-92-1 |
|---|---|
| China RoHS | Environmentally Friendly Use Period = 50 |
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |