View larger
TTC-6P-2X1-M-24DC-UT-I 2906741 PHOENIX CONTACT Surge protection, consisting of protective plug and base elem..
TTC-6P-2X1-M-24DC-UT-I
2906741
PHOENIX CONTACT
1 Pcs.
Automation > Surge protection device for data networks/MCR-technology
Trabtech (TT)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Manufactured by Phoenix Contact, the TTC-6P-2X1-M-24DC-UT-I surge protection, consisting of protective plug and base elem. provides reliable diversion of high-energy electrical transients in modern control systems. Multi-tier surge suppressors of this design are widely deployed to protect signal circuits on DIN rail assemblies within harsh industrial sectors. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Product type: Surge protection for MCR technology
- Product family: TERMITRAB complete
- IEC test classification: C1
- Type: DIN rail module, two-section, divisible
- Data management status Article revision: 04
- Insulation characteristics Overvoltage category: III
- Pollution degree: 2
- Nominal voltage U N: 24 V DC
- Connection method: Screw connection
- Screw thread: M3
- Tightening torque: 0.5 Nm ... 0.6 Nm
- Conductor cross section flexible: 0.2 mm² ... 2.5 mm²
- Conductor cross section rigid: 0.2 mm² ... 4 mm²
- Conductor cross section AWG: 24 ... 12
- Width: 6.2 mm +0.1 mm
- Height: 105.8 mm
More info
▲| Product type | Surge protection for MCR technology |
| Product family | TERMITRAB complete |
| IEC test classification | C1 |
| C2 | |
| C3 | |
| D1 | |
| Type | DIN rail module, two-section, divisible |
| Data management status | |
| Article revision | 04 |
| Insulation characteristics | |
| Overvoltage category | III |
| Pollution degree | 2 |
| Nominal voltage UN | 24 V DC |
| Connection method | Screw connection |
| Screw thread | M3 |
| Tightening torque | 0.5 Nm ... 0.6 Nm |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross section rigid | 0.2 mm² ... 4 mm² |
| Conductor cross section AWG | 24 ... 12 |
| Dimensional drawing | |
| Width | 6.2 mm +0.1 mm |
| Height | 105.8 mm |
| Depth | 100 mm (incl. DIN rail 7.5 mm) |
| Color (Base element) | gray (RAL 7042) |
| Color (Male connector) | light gray (RAL 7035) |
| Flammability rating according to UL 94 | V-0 |
| Insulating material | PBT |
| Housing material | PBT |
| Mechanical data | |
| Open side panel | No |
| Direction of action | Line-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-Earth Ground |
| Maximum continuous voltage UC | 30 V DC |
| 21 V AC | |
| Rated current | 600 mA (56 °C) |
| Operating effective current ICat UC | ≤ 5 µA |
| Residual current IPE | ≤ 10 µA |
| Nominal discharge current In(8/20) µs (line-ground) | 5 kA |
| Pulse discharge current Iimp(10/350) µs (line-earth) | 0.5 kA |
| Total discharge current Itotal(8/20) µs | 10 kA |
| Voltage protection level Up(line-earth) | ≤ 140 V (C1 - 1 kV / 500 A) |
| ≤ 190 V (C2 - 10 kV / 5 kA) | |
| ≤ 45 V (C3 - 25 A) | |
| ≤ 50 V (C3 - 100 A) | |
| Voltage protection level Upstatic (line-earth) | ≤ 55 V (C1 - 1 kV / 500 A) |
| ≤ 120 V (C2 - 10 kV / 5 kA) | |
| Response time tA(line-earth) | ≤ 1 ns |
| Input attenuation aE, asym. | typ. 0.3 dB (≤ 270 kHz/150 Ω) |
| Cut-off frequency fg (3 dB), asym. (PE) in 150 Ω system | typ. 960 kHz |
| Capacity (Core-Earth) | typ. 2.2 nF |
| Resistance per path | 1.65 Ω ±20 % |
| Surge protection fault message | optical |
| Max. required back-up fuse | 630 mA (FF) |
| Impulse durability (line-earth) | C1 - 1 kV / 500 A |
| C2 - 10 kV / 5 kA | |
| C3 - 100 A | |
| D1 - 500 A | |
| Pulse reset time (line-earth) | ≤ 300 ms |
| Additional technical data | |
| Max. total discharge current Itotal max(8/20) µs | 20 kA (1x) |
| Ambient conditions | |
| Degree of protection | IP20 |
| Ambient temperature (operation) | -40 °C ... 85 °C |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Altitude | ≤ 4000 m (amsl) |
| Permissible humidity (operation) | 5 % ... 95 % |
| Standards/specifications | IEC 61643-21 |
| Note | 2000 + corrigendum 2001 + A1:2008, modified + A2:2012 |
| EN 61643-21 | |
| Standards/specifications | EN 61643-21 |
| Note | 2001 + A1:2009 + A2:2013 |
| Mounting type | DIN rail: TH 35 - 7.5 mm |