View larger
TTC-6P-2-HC-M-24DC-PT-I 2906755 PHOENIX CONTACT Surge protection, consisting of protective plug and base ele..
TTC-6P-2-HC-M-24DC-PT-I
2906755
PHOENIX CONTACT
1 Pcs.
Automation > Surge protection device for data networks/MCR-technology
Trabtech (TT)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
The Phoenix Contact TTC-6P-2-HC-M-24DC-PT-I 2906755 PHOENIX CONTACT Surge protection, consisting of protective plug and base ele.. provides robust transient overvoltage protection for industrial automation and process control systems. Such modular protection assemblies are regularly installed on standard DIN rails to shield low-voltage control loops and sensitive signal lines from electrical noise and surges.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Nominal voltage DC (EF008799): 24 V
More info
▲Key Commercial Data
| Orderkey | 2906755 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 136 (C-4-2019) |
| GTIN | 4055626134864 |
| Weight per Piece (excluding packing) | 40.000 g |
| Custom tariff number | 85363010 |
| Country of origin | DE (Germany) |
Ambient conditions
| Ambient temperature (operation) | -40 °C ... 85 °C |
|---|---|
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Permissible humidity (operation) | 5 % ... 95 % |
| Altitude | ≤ 4000 m (amsl (above mean sea level)) |
| Degree of protection | IP20 |
General
| Housing material | PBT |
|---|---|
| Flammability rating according to UL 94 | V-0 |
| Color | traffic grey A RAL 7042 |
| light grey RAL 7035 | |
| Mounting type | DIN rail: TH 35 - 7.5 mm |
| Type | DIN rail module, two-section, divisible |
| Direction of action | Line-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-Earth Ground |
Protective circuit
| IEC test classification | C1 |
|---|---|
| C2 | |
| C3 | |
| D1 | |
| Nominal voltage UN | 24 V DC |
| Maximum continuous voltage UC | 30 V DC |
| 21 V AC | |
| Rated current | 6 A (55 °C) |
| Operating effective current ICat UC | ≤ 5 µA |
| Residual current IPE | ≤ 1 µA |
| Nominal discharge current In(8/20) µs (line-line) | 0.5 kA |
| Nominal discharge current In(8/20) µs (line-earth) | 5 kA |
| Pulse discharge current Iimp(10/350) µs (line-earth) | 0.5 kA |
| Total discharge current Itotal(8/20) µs | 5 kA |
| Voltage protection level Up(line-line) | ≤ 50 V (C1 - 1 kV/500 A) |
| ≤ 45 V (C3 - 25 A) | |
| ≤ 50 V (C3 - 100 A) | |
| Voltage protection level Up(line-earth) | ≤ 1.35 kV (C1 - 1 kV/500 A) |
| ≤ 1.45 kV (C2 - 10 kV / 5 kA) | |
| ≤ 850 V (C3 - 25 A) | |
| ≤ 1.1 kV (C3 - 100 A) | |
| Response time tA(line-line) | ≤ 1 ns |
| Response time tA(line-earth) | ≤ 100 ns |
| Input attenuation aE, sym. | typ. 0.3 dB (≤ 300 kHz / 150 Ω) |
| Cut-off frequency fg (3 dB), sym. in 150 Ohm system | typ. 1 MHz |
| Capacity (line-earth) | typ. 2.2 nF |
| Resistance per path | ≤ 100 mΩ |
| Max. required back-up fuse | 6.3 A (FF) |
| Impulse durability (line-line) | C1 - 1 kV / 500 A |
| C3 - 100 A | |
| Impulse durability (line-earth) | C1 - 1 kV / 500 A |
| C2 - 10 kV / 5 kA | |
| C3 - 100 A | |
| D1 - 500 A | |
| Pulse reset time (line-earth) | ≤ 40 ms |
Connection data
| Connection method | Push-in connection |
|---|---|
| Stripping length | 8 mm |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross section solid | 0.2 mm² ... 4 mm² |
| Conductor cross section AWG | 24 ... 12 |
Standards and Regulations
| Standards/specifications | IEC 61643-21 2000 + corrigendum 2001 + A1:2008, modified + A2:2012 |
|---|---|
| EN 61643-21 2001 + A1:2009 + A2:2013 |
Environmental Product Compliance
| REACh SVHC | Lead 7439-92-1 |
|---|---|
| China RoHS | Environmentally Friendly Use Period = 50 |
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |
Classifications
eCl@ss
| eCl@ss 4.0 | 27140201 |
|---|---|
| eCl@ss 4.1 | 27130801 |
| eCl@ss 5.0 | 27130801 |
| eCl@ss 5.1 | 27130801 |
| eCl@ss 6.0 | 27130800 |
| eCl@ss 7.0 | 27130807 |
| eCl@ss 8.0 | 27130807 |
| eCl@ss 9.0 | 27130807 |
ETIM
| ETIM 2.0 | EC000943 |
|---|---|
| ETIM 3.0 | EC000943 |
| ETIM 4.0 | EC000943 |
| ETIM 5.0 | EC000943 |
| ETIM 6.0 | EC000943 |
| ETIM 7.0 | EC000943 |
UNSPSC
| UNSPSC 6.01 | 30212010 |
|---|---|
| UNSPSC 7.0901 | 39121610 |
| UNSPSC 11 | 39121610 |
| UNSPSC 12.01 | 39121610 |
| UNSPSC 13.2 | 39121620 |
| UNSPSC 18.0 | 39121620 |
| UNSPSC 19.0 | 39121620 |
| UNSPSC 20.0 | 39121620 |
| UNSPSC 21.0 | 39121620 |