Comprising a protective plug and base element, the Phoenix Contact TTC-6P-1X2-F-48DC-PT-I surge protection unit is designed to prevent transient overvoltages from disrupting instrumentation and control lines. These modular devices allow quick replacement of protection elements during maintenance without rewiring the cabinet. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Orderkey: 2908200
- Packing unit: 1 pc
- Catalog page: Page 117 (C-4-2019)
- GTIN: 4055626282831
- Weight per Piece (excluding packing): 60.000 g
- Custom tariff number: 85363010
- Country of origin: DE (Germany)
More info
▲Key Commercial Data
| Orderkey | 2908200 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 117 (C-4-2019) |
| GTIN | 4055626282831 |
| Weight per Piece (excluding packing) | 60.000 g |
| Custom tariff number | 85363010 |
| Country of origin | DE (Germany) |
Ambient conditions
| Ambient temperature (operation) | -40 °C ... 85 °C |
|---|---|
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Permissible humidity (operation) | 5 % ... 95 % |
| Altitude | ≤ 4000 m (amsl (above mean sea level)) |
| Degree of protection | IP20 |
General
| Housing material | PBT |
|---|---|
| Flammability rating according to UL 94 | V-0 |
| Color | traffic grey A RAL 7042 |
| light grey RAL 7035 | |
| Mounting type | DIN rail: TH 35 - 7.5 mm |
| Type | DIN rail module, two-section, divisible |
| Direction of action | Line-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-Earth Ground |
Protective circuit
| IEC test classification | C1 |
|---|---|
| C2 | |
| C3 | |
| D1 | |
| Nominal voltage UN | 48 V DC |
| Maximum continuous voltage UC | 55.2 V DC |
| 30 V AC | |
| Rated current | 160 mA DC (75 °C) |
| 600 mA AC (56 °C) | |
| Operating effective current ICat UC | ≤ 5 µA |
| Residual current IPE | ≤ 1 µA |
| Nominal discharge current In(8/20) µs (line-line) | 5 kA |
| Nominal discharge current In(8/20) µs (line-earth) | 5 kA |
| Nominal discharge current In(8/20) µs (line-signal ground) | 5 kA |
| Pulse discharge current Iimp(10/350) µs (line-line) | 0.5 kA |
| Pulse discharge current Iimp(10/350) µs (line-earth) | 0.5 kA |
| Pulse discharge current Iimp(10/350) µs (line-signalground) | 0.5 kA |
| Total discharge current Itotal(8/20) µs | 10 kA |
| Voltage protection level Up(line-line) | ≤ 180 V (C1 - 1 kV/500 A) |
| ≤ 400 V (C2 - 10 kV / 5 kA) | |
| ≤ 85 V (C3 - 25 A) | |
| ≤ 90 V (C3 - 100 A) | |
| Voltage protection level Up(line-earth) | ≤ 900 V (C1 - 1 kV/500 A) |
| ≤ 1.05 kV (C2 - 10 kV / 5 kA) | |
| ≤ 1.3 kV (C3 - 25 A) | |
| ≤ 1.4 kV (C3 - 100 A) | |
| Voltage protection level Up(line-signalground) | ≤ 750 V (C1 - 1 kV/500 A) |
| ≤ 750 V (C2 - 10 kV / 5 kA) | |
| ≤ 700 V (C3 - 25 A) | |
| ≤ 750 V (C3 - 100 A) | |
| Voltage protection level Upstatic (line-line) | ≤ 45 V (C1 - 1 kV/500 A) |
| ≤ 160 V (C2 - 10 kV / 5 kA) | |
| Voltage protection level Upstatic (line-earth) | ≤ 900 V (C1 - 1 kV/500 A) |
| ≤ 1.05 kV (C2 - 10 kV / 5 kA) | |
| Voltage protection level Upstatic (line-signalground) | ≤ 750 V (C1 - 1 kV/500 A) |
| ≤ 750 V (C2 - 10 kV / 5 kA) | |
| Response time tA(line-line) | ≤ 1 ns |
| Response time tA(line-signalground) | ≤ 100 ns |
| Response time tA(line-earth) | ≤ 100 ns |
| Input attenuation aE, sym. | typ. 0.3 dB (≤ 470 kHz / 150 Ω) |
| Cut-off frequency fg (3 dB), sym. in 150 Ohm system | typ. 1.8 MHz |
| Capacity (line-line) | typ. 1.1 nF |
| Resistance per path | 1.65 Ω ±20 % |
| Max. required back-up fuse | 160 mA DC (FF) |
| 630 mA AC (FF) | |
| Impulse durability (line-line) | C1 - 1 kV / 500 A |
| C2 - 10 kV / 5 kA | |
| C3 - 50 A | |
| Impulse durability (line-earth) | C1 - 1 kV / 500 A |
| C2 - 10 kV / 5 kA | |
| C3 - 100 A | |
| D1 - 500 A | |
| Impulse durability (line-signalground) | C1 - 1 kV / 500 A |
| C2 - 10 kV / 5 kA | |
| C3 - 100 A | |
| D1 - 500 A | |
| Pulse reset time (line-line) | ≤ 700 ms |
| Pulse reset time (line-earth) | ≤ 30 ms |
| Pulse reset time (line-signalground) | ≤ 1500 ms |
Connection data
| Connection method | Push-in connection |
|---|---|
| Stripping length | 8 mm |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross section solid | 0.2 mm² ... 4 mm² |
| Conductor cross section AWG | 24 ... 12 |
Standards and Regulations
| Standards/specifications | IEC 61643-21 2000 + corrigendum 2001 + A1:2008, modified + A2:2012 |
|---|---|
| EN 61643-21 2001 + A1:2009 + A2:2013 |
Environmental Product Compliance
| REACh SVHC | Lead 7439-92-1 |
|---|---|
| China RoHS | Environmentally Friendly Use Period = 50 |
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |
Classifications
eCl@ss
| eCl@ss 4.0 | 27140201 |
|---|---|
| eCl@ss 4.1 | 27130801 |
| eCl@ss 5.0 | 27130801 |
| eCl@ss 5.1 | 27130801 |
| eCl@ss 6.0 | 27130800 |
| eCl@ss 7.0 | 27130807 |
| eCl@ss 8.0 | 27130807 |
| eCl@ss 9.0 | 27130807 |
UNSPSC
| UNSPSC 6.01 | 30212010 |
|---|---|
| UNSPSC 7.0901 | 39121610 |
| UNSPSC 11 | 39121610 |
| UNSPSC 12.01 | 39121610 |
| UNSPSC 13.2 | 39121620 |
| UNSPSC 18.0 | 39121620 |
| UNSPSC 19.0 | 39121620 |
| UNSPSC 20.0 | 39121620 |
| UNSPSC 21.0 | 39121620 |