View larger
TTC-6-TVSD-D-48DC-PT-I 2906852 PHOENIX CONTACT Fine surge protection with integrated status indicator for a ..
TTC-6-TVSD-D-48DC-PT-I
2906852
PHOENIX CONTACT
1 Pcs.
Automation > Surge protection device for data networks/MCR-technology
Trabtech (TT)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
The Phoenix Contact TTC-6-TVSD-D-48DC-PT-I fine surge protection with integrated status indicator for a .. provides precise voltage limitation for sensitive low-voltage instrumentation loops. Fine protection modules act downstream to clamp residual overvoltages to safe levels, ensuring stable operation of delicate industrial electronics. Pricing, availability, and lead time are confirmed per enquiry through an RFQ.
- Orderkey: 2906852
- Packing unit: 1 pc
- Catalog page: Page 149 (C-4-2019)
- GTIN: 4055626137087
- Weight per Piece (excluding packing): 20.000 g
- Custom tariff number: 85363010
- Country of origin: DE (Germany)
More info
▲Key Commercial Data
| Orderkey | 2906852 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 149 (C-4-2019) |
| GTIN | 4055626137087 |
| Weight per Piece (excluding packing) | 20.000 g |
| Custom tariff number | 85363010 |
| Country of origin | DE (Germany) |
Ambient conditions
| Ambient temperature (operation) | -40 °C ... 85 °C |
|---|---|
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Permissible humidity (operation) | 5 % ... 95 % |
| Altitude | ≤ 4000 m (amsl (above mean sea level)) |
| Degree of protection | IP20 (with end cover) |
General
| Housing material | PBT |
|---|---|
| Flammability rating according to UL 94 | V-0 |
| Color | traffic grey A RAL 7042 |
| Mounting type | DIN rail: 35 mm |
| Type | DIN rail module, one-piece |
| Direction of action | Line-Earth Ground |
Protective circuit
| IEC test classification | C3 |
|---|---|
| Nominal voltage UN | 48 V DC |
| Maximum continuous voltage UC | 53 V DC |
| 37 V AC | |
| Rated current | 10 A (60 °C) |
| Operating effective current ICat UC | ≤ 5 µA |
| Nominal discharge current In(8/20) µs (line-line) | 90 A |
| Voltage protection level Up(line-line) | ≤ 80 V (C3 - 18 A) |
| Response time tA(line-line) | ≤ 1 ns |
| Input attenuation aE, sym. | typ. 0.3 dB (≤ 1 MHz / 150 Ω) |
| Cut-off frequency fg (3 dB), sym. in 150 Ohm system | typ. 3.5 MHz |
| Capacity (line-line) | 1 nF |
| Resistance per path | ≤ 100 mΩ |
| Surge protection fault message | optical |
| Impulse durability (line-line) | C3 - 18 A |
Connection data
| Connection method | Push-in connection |
|---|---|
| Stripping length | 8 mm |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross section solid | 0.2 mm² ... 4 mm² |
| Conductor cross section AWG | 24 ... 12 |
Standards and Regulations
| Standards/specifications | IEC 61643-21 2000 + corrigendum 2001 + A1:2008, modified + A2:2012 |
|---|---|
| EN 61643-21 2001 + A1:2009 + A2:2013 |
Environmental Product Compliance
| China RoHS | Environmentally Friendly Use Period = 50 |
|---|---|
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |
Classifications
eCl@ss
| eCl@ss 4.0 | 27140201 |
|---|---|
| eCl@ss 4.1 | 27130801 |
| eCl@ss 5.0 | 27130801 |
| eCl@ss 5.1 | 27130801 |
| eCl@ss 6.0 | 27130800 |
| eCl@ss 7.0 | 27130807 |
| eCl@ss 8.0 | 27130807 |
| eCl@ss 9.0 | 27130807 |
ETIM
| ETIM 2.0 | EC000943 |
|---|---|
| ETIM 3.0 | EC000943 |
| ETIM 4.0 | EC000943 |
| ETIM 5.0 | EC000943 |
| ETIM 6.0 | EC000943 |
| ETIM 7.0 | EC000943 |
UNSPSC
| UNSPSC 6.01 | 30212010 |
|---|---|
| UNSPSC 7.0901 | 39121610 |
| UNSPSC 11 | 39121610 |
| UNSPSC 12.01 | 39121610 |
| UNSPSC 13.2 | 39121620 |
| UNSPSC 18.0 | 39121620 |
| UNSPSC 19.0 | 39121620 |
| UNSPSC 20.0 | 39121620 |
| UNSPSC 21.0 | 39121620 |