View larger
TTC-6-MOV-D-120AC-UT-I 1109673 PHOENIX CONTACT Medium surge protection with integrated status indicator for ..
TTC-6-MOV-D-120AC-UT-I
1109673
PHOENIX CONTACT
1 Pcs.
Automation > Surge protection device for data networks/MCR-technology
Trabtech (TT)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Medium surge protection with integrated status indicator for applications such as the Phoenix Contact TTC-6-MOV-D-120AC-UT-I guards electrical equipment against sudden voltage surges on power lines. These protective modules are commonly implemented in control cabinets to ensure continuous operation of sensitive control electronics. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Orderkey: 1109673
- Packing unit: 1 pc
- GTIN: 4063151022372
- Weight per Piece (excluding packing): 0.000 g
- Custom tariff number: 85363010
- Country of origin: DE (Germany)
More info
▲Key Commercial Data
| Orderkey | 1109673 |
|---|---|
| Packing unit | 1 pc |
| GTIN | 4063151022372 |
| Weight per Piece (excluding packing) | 0.000 g |
| Custom tariff number | 85363010 |
| Country of origin | DE (Germany) |
Ambient conditions
| Ambient temperature (operation) | -40 °C ... 85 °C |
|---|---|
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Permissible humidity (operation) | 5 % ... 95 % |
| Altitude | ≤ 2000 m (amsl (above mean sea level)) |
| Degree of protection | IP20 (with end cover) |
General
| Housing material | PBT |
|---|---|
| Flammability rating according to UL 94 | V-0 |
| Color | traffic grey A RAL 7042 |
| Mounting type | DIN rail: 35 mm |
| Type | DIN rail module, one-piece |
| Direction of action | Line-Earth Ground |
Protective circuit
| IEC test classification | C1 |
|---|---|
| C2 | |
| C3 | |
| Nominal voltage UN | 120 V AC |
| Maximum continuous voltage UC | 150 V DC |
| 150 V AC | |
| Rated current | 10 A (60 °C) |
| Operating effective current ICat UC | ≤ 100 µA |
| Residual current IPE | ≤ 100 µA |
| Nominal discharge current In(8/20) µs (line-line) | 2.5 kA |
| Voltage protection level Up(line-line) | ≤ 200 V (C1 - 800 A) |
| ≤ 500 V (C2 - 5 kV) | |
| ≤ 380 V (C3 - 25 A) | |
| ≤ 380 V (C3 - 35 A) | |
| Response time tA(line-line) | ≤ 25 ns |
| Input attenuation aE, sym. | typ. 0.3 dB (≤ 300 kHz / 150 Ω) |
| Cut-off frequency fg (3 dB), sym. in 150 Ohm system | typ. 1 MHz |
| Capacity (line-line) | 5 nF |
| Resistance per path | ≤ 100 mΩ |
| Impulse durability (line-line) | C1 - 800 A |
| C2 - 2,5 kA | |
| C3 - 35 A |
Connection data
| Connection method | Screw connection |
|---|---|
| Screw thread | M3 |
| Tightening torque | 0.5 Nm ... 0.6 Nm |
| Stripping length | 8 mm |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross section solid | 0.2 mm² ... 4 mm² |
| Conductor cross section AWG | 24 ... 12 |
Standards and Regulations
| Standards/specifications | IEC 61643-21 2000 + corrigendum 2001 + A1:2008, modified + A2:2012 |
|---|---|
| EN 61643-21 2001 + A1:2009 + A2:2013 |