PHOENIX CONTACT TTC-6-GDT-C-24AC-UT-I TTC-6-GDT-C-24AC-UT-I 2906842 PHOENIX CONTACT Coarse surge protection with integrated status indicator for a.. View larger
Images are for illustrative purposes only. Please refer to data sheet for details

TTC-6-GDT-C-24AC-UT-I 2906842 PHOENIX CONTACT Coarse surge protection with integrated status indicator for a..

TTC-6-GDT-C-24AC-UT-I

2906842

PHOENIX CONTACT

1 Pcs.

Coarse surge protection with integrated status indicator for a signal wire with grounded reference potential. Sufficient surge protection with integrated status indication for a signal conductor with grounded reference potential. Coarse surge protection with integrated status indicator for a signal wire with grounded reference potential. Can be used in safety-related circuits up to SIL 3.

Automation > Surge protection device for data networks/MCR-technology
Trabtech (TT)

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

The Phoenix Contact TTC-6-GDT-C-24AC-UT-I 2906842 is a coarse surge protection with integrated status indicator for a.. designed to intercept high-energy electrical impulses before they can reach delicate instrumentation loops. In process automation and industrial control environments, such components protect low-voltage communication paths from operational surges and atmospheric discharges. Pricing, availability and lead time are confirmed per enquiry through an RFQ.

  • Product type: Surge protection for MCR technology
  • Product family: TERMITRAB complete
  • IEC test classification: C1
  • Type: DIN rail module, one-piece
  • Surge protection fault message: optical
  • Data management status Article revision: 08
  • Insulation characteristics Overvoltage category: III
  • Pollution degree: 2
  • Nominal voltage U N: 24 V AC
  • Connection method: Screw connection
  • Screw thread: M3
  • Tightening torque: 0.5 Nm ... 0.6 Nm
  • Conductor cross section flexible: 0.2 mm² ... 2.5 mm²
  • Conductor cross section rigid: 0.2 mm² ... 4 mm²
  • Conductor cross section AWG: 24 ... 12
  • Width: 6.2 mm

More info

▲
Technical data

Product properties
Product typeSurge protection for MCR technology
Product familyTERMITRAB complete
IEC test classificationC1
C2
C3
D1
TypeDIN rail module, one-piece
Surge protection fault messageoptical
Data management status
Article revision08
Insulation characteristics
Overvoltage categoryIII
Pollution degree2

Electrical properties
Nominal voltage UN24 V AC

Connection data
Connection methodScrew connection
Screw threadM3
Tightening torque0.5 Nm ... 0.6 Nm
Conductor cross section flexible0.2 mm² ... 2.5 mm²
Conductor cross section rigid0.2 mm² ... 4 mm²
Conductor cross section AWG24 ... 12

Dimensions
Dimensional drawing
Width6.2 mm
Height92 mm
Depth69.5 mm (incl. DIN rail 7.5 mm)

Material specifications
Colorgray (RAL 7042)
Flammability rating according to UL 94V-0
Insulating materialPBT
Housing materialPBT

Mechanical properties
Mechanical data
Open side panelYes

Protective circuit
Direction of actionLine-Earth Ground
Maximum continuous voltage UC28 V DC
36 V AC
Rated current1 A DC (60 °C)
2 A AC (60 °C)
Operating effective current ICat UC≤ 1 µA
Residual current IPE≤ 1 µA
Nominal discharge current In(8/20) µs (line-ground)5 kA
Pulse discharge current Iimp(10/350) µs (line-earth)0.5 kA
Voltage protection level Up(line-earth)≤ 800 V (C1 - 2 kV)
≤ 1 kV (C2 - 10 kV)
≤ 800 V (C3 - 25 A)
≤ 900 V (C3 - 100 A)
Response time tA(line-earth)≤ 100 ns
Input attenuation aE, asym.typ. 0.3 dB (≤ 8 MHz/150 Ω)
typ. 0.3 dB (≤ 30 MHz/50 Ω)
Cut-off frequency fg (3 dB), asym. (PE) in 50 Ω systemtyp. 130 MHz
Cut-off frequency fg (3 dB), asym. (PE) in 150 Ω systemtyp. 25 MHz
Capacity (Core-Earth)5 pF
Resistance per path≤ 100 mΩ
Surge protection fault messageoptical
Impulse durability (line-earth)C1 - 1 kA
C2 - 5 kA
C3 - 100 A
D1 - 500 A
Pulse reset time (line-earth)≤ 1 ms

Environmental and real-life conditions
Ambient conditions
Degree of protectionIP20 (with end cover)
Ambient temperature (operation)-40 °C ... 85 °C
Ambient temperature (storage/transport)-40 °C ... 85 °C
Altitude≤ 4000 m (amsl)
Permissible humidity (operation)5 % ... 95 %

Standards and regulations
Standards/specificationsIEC 61643-21
Note2000 + corrigendum 2001 + A1:2008, modified + A2:2012
EN 61643-21
Standards/specificationsEN 61643-21
Note2001 + A1:2009 + A2:2013

Mounting
Mounting typeDIN rail: 35 mm

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.