Request QuoteProduct Overview
The Phoenix Contact TTC-6-FMRS-UT module set provides optical monitoring and floating remote signaling for modular surge protection arrays. These module sets are typically installed within industrial control panels for comprehensive fault diagnostics. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Product type: Remote signaling set
- Product family: TERMITRAB complete
- Type: DIN rail module, one-piece
- Data management status Article revision: 12
- Insulation characteristics Pollution degree: 2
- Indicator/remote signaling Switching function: N/C contact
- Supply: Status indicator/remote signaling Operating voltage: 10 V DC ... 36 V DC
- Operating current: 30 mA DC (24 V)
- Connection method: Screw connection
- Screw thread: M3
- Tightening torque: 0.5 Nm ... 0.6 Nm
- Conductor cross section flexible: 0.2 mm² ... 2.5 mm²
- Conductor cross section rigid: 0.2 mm² ... 4 mm²
- Conductor cross section AWG: 24 ... 12
- Altitude: ≤ 2000 m (amsl)
- Width: 6.2 mm +0.1 mm
More info
▲| Product type | Remote signaling set |
| Product family | TERMITRAB complete |
| Type | DIN rail module, one-piece |
| Data management status | |
| Article revision | 12 |
| Insulation characteristics | |
| Pollution degree | 2 |
| Indicator/remote signaling | |
| Switching function | N/C contact |
| Supply: Status indicator/remote signaling | |
| Operating voltage | 10 V DC ... 36 V DC |
| Operating current | 30 mA DC (24 V) |
| 60 mA DC (10 V) | |
| Connection method | Screw connection |
| Screw thread | M3 |
| Tightening torque | 0.5 Nm ... 0.6 Nm |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross section rigid | 0.2 mm² ... 4 mm² |
| Conductor cross section AWG | 24 ... 12 |
| Altitude | ≤ 2000 m (amsl) |
| Dimensional drawing | |
| Width | 6.2 mm +0.1 mm |
| Height | 105.8 mm |
| Depth | 83.5 mm (incl. DIN rail 7.5 mm) |
| Color | gray (RAL 7042) |
| gray (RAL 7042) | |
| Flammability rating according to UL 94 | V-0 |
| Insulating material | PBT |
| Housing material | PBT |
| Surge protection fault message | Optical, remote indicator contact |
| Ambient conditions | |
| Degree of protection | IP20 |
| Ambient temperature (operation) | -40 °C ... 60 °C |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Altitude | ≤ 4000 m (amsl) |
| Permissible humidity (operation) | 5 % ... 95 % |
| Conformity/Approvals | |
| UL, USA / Canada | Class I, Div. 2, Groups A, B, C, D T4A |
| Standards/specifications | EN 61000-6-2 |
| Note | 2005 |
| Standards/specifications | EN 61000-6-3 |
| Note | 2007 + A1:2011 |
| Standards/specifications | EN IEC 60079-0 |
| Note | 2018 |
| Standards/specifications | EN IEC 60079-7 |
| Note | 2015 + A1:2018 |
| Standards/specifications | IEC 60079-0 |
| Note | 2017 |
| Standards/specifications | IEC 60079-7 |
| Note | 2017 |
| Mounting type | DIN rail: TH 35 - 7.5 mm |