Request QuoteProduct Overview
Designed for harsh industrial conditions, the TTC-6-3-HF-F-M-EX-12DC-UT-I 2906822 PHOENIX CONTACT Surge protection with integrated status indicator and kn.. provides reliable transient suppression for critical instrumentation loops. DIN-rail mountable surge devices are standard across manufacturing plants to prevent electrical spikes from disabling sensitive controllers. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Orderkey: 2906822
- Packing unit: 1 pc
- Catalog page: Page 180 (C-4-2019)
- GTIN: 4055626235097
- Weight per Piece (excluding packing): 60.000 g
- Custom tariff number: 85363010
- Country of origin: DE (Germany)
- Height: 105.8 mm
- Width: 6.2 mm +0.1 mm
- Depth: 83.5 mm (incl. DIN rail 7.5 mm)
- Ambient temperature (operation): -40 °C ... 85 °C
- Ambient temperature (storage/transport): -40 °C ... 85 °C
- Permissible humidity (operation): 5 % ... 95 %
- Altitude: ≤ 2000 m (amsl (above mean sea level))
- Degree of protection: IP20
- Housing material: PBT
More info
▲Key Commercial Data
| Orderkey | 2906822 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 180 (C-4-2019) |
| GTIN | 4055626235097 |
| Weight per Piece (excluding packing) | 60.000 g |
| Custom tariff number | 85363010 |
| Country of origin | DE (Germany) |
Ambient conditions
| Ambient temperature (operation) | -40 °C ... 85 °C |
|---|---|
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Permissible humidity (operation) | 5 % ... 95 % |
| Altitude | ≤ 2000 m (amsl (above mean sea level)) |
| Degree of protection | IP20 |
General
| Housing material | PBT |
|---|---|
| Flammability rating according to UL 94 | V-0 |
| Color | sky blue RAL 5015 |
| Mounting type | DIN rail: TH 35 - 7.5 mm |
| Type | DIN rail module, one-piece |
| Direction of action | Line-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-Earth Ground |
Protective circuit
| IEC test classification | C1 |
|---|---|
| C2 | |
| C3 | |
| D1 | |
| Nominal voltage UN | 12 V DC |
| Maximum continuous voltage UC | 15 V DC |
| Rated current | 600 mA (40 °C) |
| Operating effective current ICat UC | ≤ 100 µA |
| Residual current IPE | ≤ 1 µA |
| Nominal discharge current In(8/20) µs (line-line) | 5 kA |
| Nominal discharge current In(8/20) µs (line-earth) | 5 kA |
| Nominal discharge current In(8/20) µs (line-signal ground) | 5 kA |
| Pulse discharge current Iimp(10/350) µs (line-line) | 0.5 kA |
| Pulse discharge current Iimp(10/350) µs (line-earth) | 0.5 kA |
| Pulse discharge current Iimp(10/350) µs (line-signalground) | 0.5 kA |
| Total discharge current Itotal(8/20) µs | 10 kA |
| Voltage protection level Up(line-line) | ≤ 145 V (C1 - 1 kV/500 A) |
| ≤ 120 V (C2 - 10 kV / 5 kA) | |
| ≤ 30 V (C3 - 100 A) | |
| Voltage protection level Up(line-earth) | ≤ 750 V (C1 - 1 kV/500 A) |
| ≤ 750 V (C2 - 10 kV / 5 kA) | |
| ≤ 1.2 kV (C3 - 100 A) | |
| Voltage protection level Up(line-signalground) | ≤ 80 V (C1 - 1 kV/500 A) |
| ≤ 80 V (C2 - 10 kV / 5 kA) | |
| ≤ 30 V (C3 - 100 A) | |
| Voltage protection level Upstatic (line-line) | ≤ 40 V (C1 - 1 kV/500 A) |
| ≤ 95 V (C2 - 10 kV / 5 kA) | |
| Voltage protection level Upstatic (line-earth) | ≤ 750 V (C1 - 1 kV/500 A) |
| ≤ 750 V (C2 - 10 kV / 5 kA) | |
| Voltage protection level Upstatic (line-signalground) | ≤ 40 V (C1 - 1 kV/500 A) |
| ≤ 95 V (C2 - 10 kV / 5 kA) | |
| Response time tA(line-line) | ≤ 1 ns |
| Response time tA(line-signalground) | ≤ 1 ns |
| Response time tA(line-earth) | ≤ 100 ns |
| Input attenuation aE, sym. | typ. 0.3 dB (≤ 8.7 MHz / 150 Ω) |
| Input attenuation aE, asym. | typ. 0.3 dB (≤ 10.5 MHz / 150 Ω) |
| Cut-off frequency fg (3 dB), sym. in 150 Ohm system | typ. 60 MHz |
| Cut-off frequency fg (3 dB), asym. (GND) in 150 Ohm system | typ. 60 MHz |
| Capacity (line-line) | typ. 32 pF |
| Capacity (line-signalground) | typ. 32 pF |
| Resistance per path | 1.65 Ω ±20 % |
| Surge protection fault message | optical |
| Max. required back-up fuse | 630 mA (FF) |
| Impulse durability (line-line) | C1 - 1 kV / 500 A |
| C2 - 10 kV / 5 kA | |
| C3 - 100 A | |
| Impulse durability (line-earth) | C1 - 1 kV / 500 A |
| C2 - 10 kV / 5 kA | |
| C3 - 100 A | |
| D1 - 500 A | |
| Impulse durability (line-signalground) | C1 - 1 kV / 500 A |
| C2 - 10 kV / 5 kA | |
| C3 - 100 A | |
| D1 - 500 A | |
| Pulse reset time (line-line) | ≤ 30 ms |
| Pulse reset time (line-earth) | ≤ 30 ms |
| Pulse reset time (line-signalground) | ≤ 30 ms |
Connection data
| Connection method | Screw connection |
|---|---|
| Screw thread | M3 |
| Tightening torque | 0.5 Nm ... 0.6 Nm |
| Stripping length | 8 mm |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross section solid | 0.2 mm² ... 4 mm² |
| Conductor cross section AWG | 24 ... 12 |
Standards and Regulations
| Standards/specifications | EN 60079-0 2012 + A11:2013 |
|---|---|
| EN 60079-11 2012 | |
| EN 61643-21 2001 + A1:2009 + A2:2013 | |
| IEC 60079-0 2011 (modified) + corrigendum 2012 + corrigendum 2013 | |
| IEC 60079-11 2008 | |
| IEC 61643-21 2000 + corrigendum 2001 + A1:2008, modified + A2:2012 |
General
| Maximum inner capacitance Ci | negligible |
|---|---|
| Max. internal inductance Li | negligible |
| Max. input current Ii | 400 mA (T4 / ≤ 50 °C) |
| 350 mA (T6 / ≤ 35 °C) | |
| Max. input voltage Ui | 15 V DC |
| Insulation voltage to ground | > 180 V DC |
| Ambient temperature (operation) | -40 °C ... 35 °C (T6 / 85 °C) |
| -40 °C ... 50 °C (T4 / 135 °C) |
Environmental Product Compliance
| REACh SVHC | Lead 7439-92-1 |
|---|---|
| China RoHS | Environmentally Friendly Use Period = 50 |
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |
Classifications
eCl@ss
| eCl@ss 4.0 | 27140201 |
|---|---|
| eCl@ss 4.1 | 27130801 |
| eCl@ss 5.0 | 27130801 |
| eCl@ss 5.1 | 27130801 |
| eCl@ss 6.0 | 27130800 |
| eCl@ss 7.0 | 27130807 |
| eCl@ss 8.0 | 27130807 |
| eCl@ss 9.0 | 27130807 |
ETIM
| ETIM 2.0 | EC000943 |
|---|---|
| ETIM 3.0 | EC000943 |
| ETIM 4.0 | EC000943 |
| ETIM 5.0 | EC000943 |
| ETIM 6.0 | EC000943 |
| ETIM 7.0 | EC000943 |
UNSPSC
| UNSPSC 6.01 | 30212010 |
|---|---|
| UNSPSC 7.0901 | 39121610 |
| UNSPSC 11 | 39121610 |
| UNSPSC 12.01 | 39121610 |
| UNSPSC 13.2 | 39121620 |
| UNSPSC 18.0 | 39121620 |
| UNSPSC 19.0 | 39121620 |
| UNSPSC 20.0 | 39121620 |
| UNSPSC 21.0 | 39121620 |