View larger
TTC-6-2X1-M-EX-24DC-UT-I 2906821 PHOENIX CONTACT Surge protection with integrated status indicator and disco..
TTC-6-2X1-M-EX-24DC-UT-I
2906821
PHOENIX CONTACT
1 Pcs.
Automation > Combined arrester for data networks/MCR-technology
Trabtech (TT)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
The Phoenix Contact TTC-6-2X1-M-EX-24DC-UT-I surge protection unit features an integrated status indicator and disconnect function for safeguarding multi-conductor signal applications. Industrial automation panels utilize these protective terminals to ensure safe signal transmission and provide immediate visual indication of surge arrester status. Final pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Orderkey: 2906821
- Packing unit: 1 pc
- Catalog page: Page 157 (C-4-2019)
- GTIN: 4055626135847
- Weight per Piece (excluding packing): 60.000 g
- Custom tariff number: 85363010
- Country of origin: DE (Germany)
- Height: 105.8 mm
- Width: 6.2 mm +0.1 mm
- Depth: 83.5 mm (incl. DIN rail 7.5 mm)
- Ambient temperature (operation): -40 °C ... 85 °C
- Ambient temperature (storage/transport): -40 °C ... 85 °C
- Permissible humidity (operation): 5 % ... 95 %
- Altitude: ≤ 2000 m (amsl (above mean sea level))
- Degree of protection: IP20
- Housing material: PBT
More info
▲Key Commercial Data
| Orderkey | 2906821 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 157 (C-4-2019) |
| GTIN | 4055626135847 |
| Weight per Piece (excluding packing) | 60.000 g |
| Custom tariff number | 85363010 |
| Country of origin | DE (Germany) |
Ambient conditions
| Ambient temperature (operation) | -40 °C ... 85 °C |
|---|---|
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Permissible humidity (operation) | 5 % ... 95 % |
| Altitude | ≤ 2000 m (amsl (above mean sea level)) |
| Degree of protection | IP20 |
General
| Housing material | PBT |
|---|---|
| Flammability rating according to UL 94 | V-0 |
| Color | sky blue RAL 5015 |
| Mounting type | DIN rail: TH 35 - 7.5 mm |
| Type | DIN rail module, one-piece |
| Direction of action | Line-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-Earth Ground |
Protective circuit
| IEC test classification | C1 |
|---|---|
| C2 | |
| C3 | |
| D1 | |
| Nominal voltage UN | 24 V DC |
| Maximum continuous voltage UC | 30 V DC |
| Rated current | 600 mA (40 °C) |
| Operating effective current ICat UC | ≤ 5 µA |
| Residual current IPE | ≤ 10 µA |
| Nominal discharge current In(8/20) µs (line-earth) | 5 kA |
| Pulse discharge current Iimp(10/350) µs (line-earth) | 0.5 kA |
| Total discharge current Itotal(8/20) µs | 10 kA |
| Voltage protection level Up(line-earth) | ≤ 140 V (C1 - 1 kV/500 A) |
| ≤ 130 V (C2 - 10 kV / 5 kA) | |
| ≤ 50 V (C3 - 100 A) | |
| Voltage protection level Upstatic (line-earth) | ≤ 55 V (C1 - 1 kV/500 A) |
| ≤ 80 V (C2 - 10 kV / 5 kA) | |
| Response time tA(line-earth) | ≤ 1 ns |
| Input attenuation aE, asym. | typ. 0.3 dB (≤ 270 kHz/150 Ω) |
| Cut-off frequency fg (3 dB), asym. (PE) in 150 Ohm system | typ. 960 kHz |
| Capacity (line-earth) | typ. 2.2 nF |
| Resistance per path | 1.65 Ω ±20 % |
| Surge protection fault message | optical |
| Max. required back-up fuse | 630 mA (FF) |
| Impulse durability (line-earth) | C1 - 1 kV / 500 A |
| C2 - 10 kV / 5 kA | |
| C3 - 100 A | |
| D1 - 500 A | |
| Pulse reset time (line-earth) | ≤ 300 ms |
Connection data
| Connection method | Screw connection |
|---|---|
| Screw thread | M3 |
| Tightening torque | 0.5 Nm ... 0.6 Nm |
| Stripping length | 8 mm |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross section solid | 0.2 mm² ... 4 mm² |
| Conductor cross section AWG | 24 ... 12 |
Standards and Regulations
| Standards/specifications | EN 60079-0 2012 + A11:2013 |
|---|---|
| EN 60079-11 2012 | |
| EN 61643-21 2001 + A1:2009 + A2:2013 | |
| IEC 60079-0 2011 (modified) + corrigendum 2012 + corrigendum 2013 | |
| IEC 60079-11 2008 | |
| IEC 61643-21 2000 + corrigendum 2001 + A1:2008, modified + A2:2012 |
General
| Maximum inner capacitance Ci | negligible |
|---|---|
| Max. internal inductance Li | negligible |
| Max. input current Ii | 400 mA (T4 / ≤ 50 °C) |
| 350 mA (T6 / ≤ 35 °C) | |
| Max. input voltage Ui | 30 V DC |
| Ambient temperature (operation) | -40 °C ... 35 °C (T6 / 85 °C) |
| -40 °C ... 50 °C (T4 / 135 °C) |
Environmental Product Compliance
| REACh SVHC | Lead 7439-92-1 |
|---|---|
| China RoHS | Environmentally Friendly Use Period = 50 |
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |
Classifications
eCl@ss
| eCl@ss 4.0 | 27140201 |
|---|---|
| eCl@ss 4.1 | 27130801 |
| eCl@ss 5.0 | 27130801 |
| eCl@ss 5.1 | 27130801 |
| eCl@ss 6.0 | 27130800 |
| eCl@ss 7.0 | 27130807 |
| eCl@ss 8.0 | 27130807 |
| eCl@ss 9.0 | 27130807 |
ETIM
| ETIM 2.0 | EC000943 |
|---|---|
| ETIM 3.0 | EC000943 |
| ETIM 4.0 | EC000943 |
| ETIM 5.0 | EC000943 |
| ETIM 6.0 | EC000943 |
| ETIM 7.0 | EC000943 |
UNSPSC
| UNSPSC 6.01 | 30212010 |
|---|---|
| UNSPSC 7.0901 | 39121610 |
| UNSPSC 11 | 39121610 |
| UNSPSC 12.01 | 39121610 |
| UNSPSC 13.2 | 39121620 |
| UNSPSC 18.0 | 39121620 |
| UNSPSC 19.0 | 39121620 |
| UNSPSC 20.0 | 39121620 |
| UNSPSC 21.0 | 39121620 |