PHOENIX CONTACT TTC-6-2-24DC-UT TTC-6-2-24DC-UT 2906800 PHOENIX CONTACT Surge protection for resistance-dependent measuring signals. View larger
Images are for illustrative purposes only. Please refer to data sheet for details

TTC-6-2-24DC-UT 2906800 PHOENIX CONTACT Surge protection for resistance-dependent measuring signals.

TTC-6-2-24DC-UT

2906800

PHOENIX CONTACT

1 Pcs.

Surge protection for resistance-dependent measuring signals. Surge protection for resistance-dependent measuring signals. Can be used in safety-related circuits up to SIL 3.

Automation > Surge protection device for data networks/MCR-technology
Trabtech (TT)

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

The Phoenix Contact TTC-6-2-24DC-UT is a slim DIN rail surge protection module engineered specifically for resistance-dependent measuring signals in industrial environments. One-piece terminal block suppressors protect sensitive automation hardware from indirect lightning strikes and switching overvoltages. Pricing, availability and lead time are confirmed per enquiry through an RFQ.

  • Product type: Surge protection for MCR technology
  • Product family: TERMITRAB complete
  • IEC test classification: C1
  • Type: DIN rail module, one-piece
  • Data management status Article revision: 04
  • Insulation characteristics Overvoltage category: III
  • Pollution degree: 2
  • Nominal voltage U N: 24 V DC
  • Connection method: Screw connection
  • Screw thread: M3
  • Tightening torque: 0.5 Nm ... 0.6 Nm
  • Conductor cross section flexible: 0.2 mm² ... 2.5 mm²
  • Conductor cross section rigid: 0.2 mm² ... 4 mm²
  • Conductor cross section AWG: 24 ... 12
  • Width: 6.2 mm +0.1 mm
  • Height: 105.8 mm

More info

▲
Technical data

Product properties
Product typeSurge protection for MCR technology
Product familyTERMITRAB complete
IEC test classificationC1
C2
C3
D1
TypeDIN rail module, one-piece
Data management status
Article revision04
Insulation characteristics
Overvoltage categoryIII
Pollution degree2

Electrical properties
Nominal voltage UN24 V DC

Connection data
Connection methodScrew connection
Screw threadM3
Tightening torque0.5 Nm ... 0.6 Nm
Conductor cross section flexible0.2 mm² ... 2.5 mm²
Conductor cross section rigid0.2 mm² ... 4 mm²
Conductor cross section AWG24 ... 12

Dimensions
Dimensional drawing
Width6.2 mm +0.1 mm
Height105.8 mm
Depth69.5 mm (incl. DIN rail 7.5 mm)

Material specifications
Colorgray (RAL 7042)
light gray (RAL 7035)
Flammability rating according to UL 94V-0
Insulating materialPBT
Housing materialPBT

Mechanical properties
Mechanical data
Open side panelNo

Protective circuit
Direction of actionLine-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-Earth Ground
Maximum continuous voltage UC30 V DC
21 V AC
Rated current450 mA (80 °C)
Operating effective current ICat UC≤ 5 µA
Residual current IPE≤ 1 µA
Nominal discharge current In(8/20) µs (line-line)0.5 kA
Nominal discharge current In(8/20) µs (line-ground)5 kA
Pulse discharge current Iimp(10/350) µs (line-earth)0.5 kA
Total discharge current Itotal(8/20) µs10 kA
Voltage protection level Up(line-line)≤ 60 V (C1 - 1 kV / 500 A)
≤ 45 V (C3 - 25 A)
≤ 50 V (C3 - 100 A)
Voltage protection level Up(line-earth)≤ 650 V (C1 - 1 kV / 500 A)
≤ 1.1 kV (C2 - 10 kV / 5 kA)
≤ 600 V (C3 - 25 A)
≤ 700 V (C3 - 100 A)
Voltage protection level Upstatic (line-earth)≤ 1.1 kV (C2 - 10 kV / 5 kA)
Response time tA(line-line)≤ 1 ns
Response time tA(line-earth)≤ 100 ns
Input attenuation aE, sym.typ. 0.3 dB (≤ 300 kHz / 150 Ω)
Cut-off frequency fg (3 dB), sym. in 150 Ω systemtyp. 965 kHz
Capacity (Core-Earth)typ. 2.2 nF
Resistance per path≤ 100 mΩ
Surge protection fault messagenone
Max. required back-up fuse500 mA (FF)
Impulse durability (line-line)C1 - 1 kV / 500 A
C3 - 100 A
Impulse durability (line-earth)C1 - 1 kV / 500 A
C2 - 10 kV / 5 kA
C3 - 100 A
D1 - 500 A
Pulse reset time (line-earth)≤ 1 s
Additional technical data
Max. total discharge current Itotal max(8/20) µs20 kA (1x)

Environmental and real-life conditions
Ambient conditions
Degree of protectionIP20
Ambient temperature (operation)-40 °C ... 85 °C
Ambient temperature (storage/transport)-40 °C ... 85 °C
Altitude≤ 4000 m (amsl)
Permissible humidity (operation)5 % ... 95 %

Standards and regulations
Standards/specificationsIEC 61643-21
Note2000 + corrigendum 2001 + A1:2008, modified + A2:2012
EN 61643-21
Standards/specificationsEN 61643-21
Note2001 + A1:2009 + A2:2013

Mounting
Mounting typeDIN rail: TH 35 - 7.5 mm

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.