View larger
TRIO-UPS-2G/1AC/24DC/10 2907161 PHOENIX CONTACT Uninterruptible power supply with integrated power supply un..
TRIO-UPS-2G/1AC/24DC/10
2907161
PHOENIX CONTACT
1 Pcs.
Automation > UPS
Power Supplies (PS)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Phoenix Contact TRIO-UPS-2G/1AC/24DC/10 is an uninterruptible power supply with integrated power supply unit designed to maintain continuous power delivery to sensitive DC loads during primary grid interruptions. These systems protect industrial control panels, automation hardware, and instrumentation against unexpected voltage drops or complete outages.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Input voltage (EF003840): 85 V
- Output voltage (EF003933): 24 V
- USB interface (EF002039): No
- With communication interface RS-232 (EF007312): No
- SNMP (EF005284): No
- Voltage type (EF000187): AC
- Height (EF000040): 130 mm
- Width (EF000008): 68 mm
- Depth (EF000049): 68 mm
- Weight (EF000167): 1.36666 kg
More info
▲Key Commercial Data
| Orderkey | 2907161 |
|---|---|
| Packing unit | 1 pc |
| GTIN | 4055626166582 |
| Weight per Piece (excluding packing) | 1,700.000 g |
| Custom tariff number | 85044030 |
| Country of origin | CN (China) |
Dimensions
| Width | 68 mm |
|---|---|
| Height | 130 mm |
| Depth | 160 mm |
| Width with alternative assembly | 160 mm |
| Height with alternative assembly | 130 mm |
| Depth with alternative assembly | 68 mm |
Ambient conditions
| Degree of protection | IP20 |
|---|---|
| Ambient temperature (operation) | -25 °C ... 70 °C (> 60 °C Derating: 2.5 %/K) |
| Ambient temperature (start-up type tested) | -40 °C |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Max. permissible relative humidity (operation) | ≤ 93 % (At +25°C, non-condensing) |
| Climatic class | 3K3 (in acc. with EN 60721) |
| Degree of pollution | 2 |
| Installation height | ≤ 4000 m (> 2000 m, observe derating) |
Input data
| AC input voltage range | 100 V AC ... 240 V AC -15 % ... +10 % |
|---|---|
| Inrush current limiting/I²t | < 0.2 A2s |
| Mains buffering | ≥ 25 ms (120 V AC) |
| Typical response time | 200 ms |
| Input fuse, integrated | 6.3 A (slow-blow, internal) |
Output data
| Nominal output voltage | 24 V DC |
|---|---|
| Setting range of the output voltage (USet) | 24 V DC ... 28 V DC (> 24 V constant capacity) |
| Nominal output current (IN) | 10 A |
| Dynamic Boost (IDyn.Boost) | 15 A |
| Derating | > 60 °C (2.5%/K of POutnom.) |
| Control deviation | < 0.55 % (Static load change 10 % ... 90 %) |
| Maximum power dissipation in no-load condition | < 3 W (230 V AC) |
| Efficiency | typ. 90 % (120 V AC) |
| typ. 91 % (230 V AC) | |
| typ. 96 % (Battery operation) | |
| Residual ripple | < 20 mV |
| Connection in parallel | yes, with diode module uncoupled |
| Surge protection against internal surge voltages | < 30 V DC |
| Feedback resistance | ≤ 35 V DC |
General
| Net weight | 1.34 kg |
|---|---|
| Insulation voltage input/output | 4 kV AC (type test) |
| 2 kV AC (routine test) | |
| Protection class | I |
| MTBF (IEC 61709, SN 29500) | > 2007013 h (230 V AC, at 25 °C) |
| > 1210518 h (230 V AC, at 40 °C) | |
| > 575978 h (230 V AC, at 60 °C) | |
| Mounting position | horizontal DIN rail NS 35, EN 60715 |
| Assembly instructions | alignable: horizontally 0 mm, vertically 50 mm |
Connection data, input
| Connection method | Push-in connection |
|---|---|
| Conductor cross section solid min. | 0.2 mm² |
| Conductor cross section solid max. | 4 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 2.5 mm² |
| Conductor cross section AWG min. | 24 |
| Conductor cross section AWG max. | 12 |
| Stripping length | 10 mm |
Connection data, output
| Connection method | Push-in connection |
|---|---|
| Conductor cross section solid min. | 0.2 mm² |
| Conductor cross section solid max. | 4 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 2.5 mm² |
| Conductor cross section AWG min. | 24 |
| Conductor cross section AWG max. | 12 |
| Stripping length | 10 mm |
Connection data for signaling
| Connection method | Push-in connection |
|---|---|
| Conductor cross section solid min. | 0.2 mm² |
| Conductor cross section solid max. | 1.5 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 1.5 mm² |
| Conductor cross section AWG min. | 24 |
| Conductor cross section AWG max. | 16 |
| Stripping length | 8 mm |
Standards and Regulations
| Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
|---|---|
| Standards/regulations | EN 61000-4-2 |
| Contact discharge | 4 kV (Test Level 2) |
| Standards/regulations | EN 61000-4-3 |
| Frequency range | 80 MHz ... 1 GHz |
| Test field strength | 10 V/m (Test Level 3) |
| Standards/regulations | EN 61000-4-4 |
| Comments | Criterion B |
| Standards/regulations | EN 61000-4-6 |
| Frequency range | 0.15 MHz ... 80 MHz |
| Voltage | 10 V (Test Level 3) |
| Conducted noise emission | EN 61000-6-4 (Class A) |
| Standards/regulations | EN 61000-4-12 |
| Low Voltage Directive | Conformance with Low Voltage Directive 2014/35/EC |
| Standard - power supply devices for low voltage with DC output | EN 61204-3 |
| Standard – Safety extra-low voltage | IEC 61010 (SELV) / (PELV) |
| Standard - Safe isolation | DIN VDE 0100-410 |
| UL approvals | UL Listed UL 61010 |
| UL/C-UL Listed ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C | |
| Shock | 30g, 18 ms according to IEC 60068-2-27 |
| Vibration (operation) | in accordance with IEC 60068-2-6 |
| Overvoltage category (EN 61010-1) | II |