View larger
TRIO-PS-IP67/1AC/24DC/20 1039830 PHOENIX CONTACT TRIO POWER primary-switched power supply in IP67 die-cast h..
TRIO-PS-IP67/1AC/24DC/20
1039830
PHOENIX CONTACT
1 Pcs.
Automation > DC-power supply
Power Supplies (PS)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Phoenix Contact TRIO-PS-IP67/1AC/24DC/20 primary-switched power supply features a robust IP67 die-cast housing designed for decentralized power supply deployment. It operates reliably in harsh industrial environments exposed to moisture, dust, and temperature extremes. Pricing, availability, and lead time are confirmed per enquiry through an RFQ.
- Orderkey: 1039830
- Packing unit: 1
- Catalog page: Page 264 (C-4-2019)
- GTIN: 4055626598703
- Custom tariff number: 85044030
- Width: 151 mm
- Height: 304 mm
- Depth: 120 mm
- Degree of protection: IP67
- Ambient temperature (operation): -25 °C ... 85 °C (Derating >60°C: 2.5 %/K)
- Ambient temperature (start-up type tested): -40 °C
- Ambient temperature (storage/transport): -40 °C ... 85 °C
- Max. permissible relative humidity (operation): ≤ 95 % (at 25 °C, non-condensing)
- Climatic class: 3K3 (in acc. with EN 60721)
- Degree of pollution: 4
- Installation height: ≤ 4000 m (> 2000 m, Derating: 10 %/1000 m)
More info
▲Key Commercial Data
| Orderkey | 1039830 |
|---|---|
| Packing unit | 1 |
| Catalog page | Page 264 (C-4-2019) |
| GTIN | 4055626598703 |
| Custom tariff number | 85044030 |
Ambient conditions
| Degree of protection | IP67 |
|---|---|
| Ambient temperature (operation) | -25 °C ... 85 °C (Derating >60°C: 2.5 %/K) |
| Ambient temperature (start-up type tested) | -40 °C |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Max. permissible relative humidity (operation) | ≤ 95 % (at 25 °C, non-condensing) |
| Climatic class | 3K3 (in acc. with EN 60721) |
| Degree of pollution | 4 |
| Installation height | ≤ 4000 m (> 2000 m, Derating: 10 %/1000 m) |
Input data
| Nominal input voltage range | 100 V AC ... 240 V AC |
|---|---|
| 110 V DC ... 250 V DC | |
| Input voltage range | 100 V AC ... 240 V AC 10 % |
| 110 V DC ... 250 V DC 10 % | |
| Dielectric strength maximum | ≤ 300 V AC 15 s |
| AC frequency range | 50 Hz ... 60 Hz |
| Discharge current to PE | < 3.5 mA |
| Current consumption | 5.6 A (100 V AC) |
| 2.4 A (240 V AC) | |
| Nominal power consumption | 36.8 W |
| Inrush current | typ. 20 A (at 25 °C) |
| Mains buffering time | typ. 10 ms (120 V AC) |
| typ. 15 ms (230 V AC) | |
| Input fuse | 10 A (internal (device protection)) |
| Recommended breaker for input protection | 10 A ... 16 A (Characteristics B, C, D, K) |
| Type of protection | Transient surge protection |
| Protective circuit/component | Varistor |
Output data
| Nominal output voltage | 24 V DC ±1 % |
|---|---|
| Nominal output current (IN) | 20 A |
| Dynamic Boost (IDyn.Boost) | 30 A (5 s) |
| Derating | > 60 °C ... 70 °C (2.5%/K) |
| Protection against overvoltage at the output (OVP) | ≤ 30 V DC |
| Control deviation | < 1 % (change in load, static 10 % ... 90 %) |
| < 3 % (Dynamic load change 10 % ... 90 %, 10 Hz) | |
| < 0.1 % (change in input voltage ±10 %) | |
| Residual ripple | ≤ 30 mVPP |
| Output power | 480 W |
| Typical response time | < 1 s |
| Maximum power dissipation in no-load condition | < 3 W (120 V AC) |
| < 2.5 W (230 V AC) | |
| Power loss nominal load max. | < 48 W (120 V AC) |
| < 36 W (230 V AC) |
General
| Net weight | 3.7 kg |
|---|---|
| Efficiency | 91 % (100 V AC) |
| 93 % (230 V AC) | |
| Insulation voltage input/output | 4 kV AC (type test) |
| 1.5 kV AC (routine test) | |
| Protection class | I |
| Degree of protection | IP67 |
| MTBF (IEC 61709, SN 29500) | > 1400000 h (25 °C) |
| > 800000 h (40 °C) | |
| > 400000 h (60 °C) | |
| Assembly instructions | Alignable: 20 mm horizontally, 50 mm vertically above, 100 mm vertically below |
Connection data, input
| Connection method | Circular connector |
|---|---|
| Type of locking | M12 screw locking |
| Coding | S-coded |
| Number of positions | 3 |
Connection data, output
| Connection method | Circular connector |
|---|---|
| Type of locking | M17 standard and SPEEDCON locking |
| Coding | N-coded |
| Number of positions | 4 |
Connection data for signaling
| Connection method | Circular connector |
|---|---|
| Type of locking | SPEEDCON M12 |
| Coding | A-coded |
| Number of positions | 5 |
Standards
| Standard - Electrical safety | IEC 61010-2-201 (SELV) |
|---|---|
| Standard – Safety extra-low voltage | EN 60204-1 (PELV) |
| Standard - Safe isolation | DIN VDE 0100-410 |
| Standard – Limitation of mains harmonic currents | EN 61000-3-2 |
EMC data
| Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
|---|---|
| Low Voltage Directive | Conformance with Low Voltage Directive 2014/35/EC |
| Conducted noise emission | EN 55016 |
| EN 61000-6-3 (Class B) | |
| Noise emission | EN 55016 |
| EN 61000-6-3 (Class B) | |
| Flicker | EN 61000-3-3 |
| Electrostatic discharge | EN 61000-4-2 |
| Contact discharge | 6 kV (Test Level 4) |
| Discharge in air | 8 kV (Test Level 4) |
| Electromagnetic HF field | EN 61000-4-3 |
| Frequency range | 80 MHz ... 1 GHz |
| Test field strength | 10 V/m (Test Level 3) |
| Frequency range | 1 GHz ... 2 GHz |
| Test field strength | 10 V/m (Test Level 3) |
| Frequency range | 2 GHz ... 3 GHz |
| Test field strength | 10 V/m (Test Level 3) |
| Comments | Criterion A |
| Fast transients (burst) | EN 61000-4-4 |
| Input | 4 kV (Test Level 4 - asymmetrical) |
| Output | 2 kV (Test Level 3 - asymmetrical) |
| Signal | 2 kV (Test Level 2 - asymmetrical) |
| Comments | Criterion A |
| Surge voltage load (surge) | EN 61000-4-5 |
| Input | 3 kV (Test Level 3 - symmetrical) |
| 4 kV (Test Level 4 - asymmetrical) | |
| Output | 1 kV (Test Level 2 - symmetrical) |
| 2 kV (Test Level 1 - asymmetrical) | |
| Signal | 1 kV (Test Level 2 - asymmetrical) |
| Comments | Criterion B |
| Conducted interference | EN 61000-4-6 |
| Frequency range | 0.15 MHz ... 80 MHz |
| Voltage | 10 V (Test Level 3) |
| Comments | Criterion A |
| Voltage dips | EN 61000-4-11 |
| Voltage | 230 V AC |
| Frequency | 50 Hz |
| Voltage dip | 70 % |
| Number of periods | 25 periods |
| Additional text | Test Level 2 |
| Comments | Criterion A |
| Voltage dip | 40 % |
| Number of periods | 10 periods |
| Additional text | Test Level 2 |
| Comments | Criterion B |
| Voltage dip | 0 % |
| Number of periods | 1 period |
| Additional text | Test Level 2 |
| Comments | Criterion B |
| Criterion A | Normal operating behavior within the specified limits. |
| Criterion B | Temporary impairment to operational behavior that is corrected by the device itself. |
| Criterion C | Temporary adverse effects on the operating behavior, which the device corrects automatically or which can be restored by actuating the operating elements. |