View larger
TRIO-PS-2G/1AC/48DC/5 2903159 PHOENIX CONTACT Power supply unit
TRIO-PS-2G/1AC/48DC/5
2903159
PHOENIX CONTACT
1 Pcs.
Automation > DC-power supply
Power Supplies (PS)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Designed as a Power supply unit, the Phoenix Contact TRIO-PS-2G/1AC/48DC/5 component delivers conversion of electrical input into regulated DC voltage levels for industrial systems. Power supply units are essential for feeding reliable operating power to automated production equipment and control electronics.
Pricing, availability, and lead time are confirmed per enquiry through an RFQ.
- Voltage type (supply voltage) (EF002991): AC/DC
- 1st secondary output voltage (EF006792): 36 V
- Max. output current 1 (EF008284): 7.5 A
- Secondary voltage adjustable (EF007002): Yes
- Nominal value output voltage 1 (EF009393): 48 V
- Nominal value output current 1 (EF009396): 5 A
- Short-circuit-proof (EF007332): Yes
- Rated supply voltage AC 50 Hz (EF007076): 100 V
- Rated supply voltage AC 60 Hz (EF007077): 100 V
- Rated supply voltage DC (EF007078): 110 V
- Output voltage stabilized (EF003092): Yes
- Power consumption (EF000346): 285.7 VA
- Power output (EF003034): 240 W
- Stabilized (EF005302): Yes
- Suitable for rail mounting (EF003972): Yes
- Wall mounting possible (EF003973): No
More info
▲Key Commercial Data
| Orderkey | 2903159 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 225 (C-4-2017) |
| GTIN | 4055626255422 |
| Weight per Piece (excluding packing) | 1,120.000 g |
| Custom tariff number | 85044030 |
| Country of origin | CN (China) |
Ambient conditions
| Degree of protection | IP20 |
|---|---|
| Ambient temperature (operation) | -25 °C ... 70 °C (> 60 °C Derating: 2.5 %/K) |
| Ambient temperature (start-up type tested) | -40 °C |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Max. permissible relative humidity (operation) | ≤ 95 % (at 25 °C, non-condensing) |
| Climatic class | 3K3 (in acc. with EN 60721) |
| Degree of pollution | 2 |
| Installation height | ≤ 5000 m (> 2000 m, Derating: 10 %/1000 m) |
Input data
| Nominal input voltage range | 100 V AC ... 240 V AC |
|---|---|
| 110 V DC ... 250 V DC | |
| Input voltage range | 100 V AC ... 240 V AC -15 % ... +10 % |
| 110 V DC ... 250 V DC ±10 % | |
| Dielectric strength maximum | ≤ 300 V AC 15 s |
| AC frequency range | 50 Hz ... 60 Hz ±10 % |
| Discharge current to PE | < 3.5 mA |
| Current consumption | 2.9 A (100 V AC) |
| 2.3 A (120 V AC) | |
| 1.2 A (230 V AC) | |
| 1.2 A (240 V AC) | |
| Nominal power consumption | 285.7 VA |
| Mains buffering | typ. 15 ms (120 V AC) |
| typ. 15 ms (230 V AC) | |
| Input fuse | 6.3 A (internal (device protection)) |
| Choice of suitable circuit breakers | 6 A ... 16 A (Characteristics B, C, D, K) |
| Power factor (cos phi) | 0.91 |
Output data
| Nominal output voltage | 48 V DC ±1 % |
|---|---|
| Setting range of the output voltage (USet) | 36 V DC ... 55 V DC (> 48 V DC, constant capacity restricted) |
| Nominal output current (IN) | 5 A |
| Dynamic Boost (IDyn.Boost) | 7.5 A (5 s) |
| Derating | > 60 °C ... 70 °C (2.5%/K) |
| Connection in parallel | Yes, for redundancy and increased capacity |
| Connection in series | yes |
| Feedback resistance | ≤ 60 V DC |
| Output overvoltage protection | ≤ 60 V DC |
| Control deviation | < 1 % (change in load, static 10 % ... 90 %) |
| < 3 % (Dynamic load change 10 % ... 90 %, 10 Hz) | |
| < 0.1 % (change in input voltage ±10 %) | |
| Residual ripple | < 20 mVPP(with nominal values) |
| Output power | 240 W |
| Peak switching voltages nominal load | < 15 mVPP |
| Maximum power dissipation in no-load condition | typ. 4 W (120 V AC) |
| typ. 4.1 W (230 V AC) | |
| Power loss nominal load max. | typ. 24.5 W (120 V AC) |
| typ. 20.1 W (230 V AC) | |
| Short-circuit current | < 7 A DC (Permanent) |
General
| Net weight | 0.9 kg |
|---|---|
| Efficiency | typ. 90.5 % (120 V AC) |
| typ. 91 % (230 V AC) | |
| Insulation voltage input/output | 3 kV AC (type test) |
| 1.5 kV AC (routine test) | |
| Protection class | I (in closed control cabinet) |
| Degree of protection | IP20 |
| MTBF (IEC 61709, SN 29500) | > 2000000 h (25 °C) |
| > 1200000 h (40 °C) | |
| > 620000 h (60 °C) | |
| Mounting position | horizontal DIN rail NS 35, EN 60715 |
| Assembly instructions | alignable: horizontally 0 mm (≤ 40 °C) 10 mm (≤ 70 °C), vertically 50 mm |
Connection data, input
| Connection method | Push-in connection |
|---|---|
| Conductor cross section solid min. | 0.2 mm² |
| Conductor cross section solid max. | 4 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 2.5 mm² |
| Conductor cross section AWG min. | 24 |
| Conductor cross section AWG max. | 12 |
| Stripping length | 10 mm |
Connection data, output
| Connection method | Push-in connection |
|---|---|
| Conductor cross section solid min. | 0.2 mm² |
| Conductor cross section solid max. | 4 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 2.5 mm² |
| Conductor cross section AWG min. | 24 |
| Conductor cross section AWG max. | 12 |
| Stripping length | 8 mm |
Connection data for signaling
| Connection method | Push-in connection |
|---|---|
| Conductor cross section solid min. | 0.2 mm² |
| Conductor cross section solid max. | 1.5 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 1.5 mm² |
| Conductor cross section AWG min. | 24 |
| Conductor cross section AWG max. | 16 |
| Stripping length | 8 mm |
Standards and Regulations
| Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
|---|---|
| Noise emission | EN 55011 (EN 55022) |
| Noise immunity | Immunity according to EN 61000-6-1 (residential), EN 61000-6-2 (industrial) |
| Standards/regulations | EN 61000-4-2 |
| Contact discharge | 4 kV (Test Level 2) |
| Standards/regulations | EN 61000-4-3 |
| Frequency range | 80 MHz ... 1 GHz |
| Test field strength | 10 V/m (Test Level 3) |
| Frequency range | 1.4 GHz ... 2 GHz |
| Test field strength | 3 V/m (Test Level 2) |
| Standards/regulations | EN 61000-4-4 |
| Comments | Criterion B |
| Standards/regulations | EN 61000-6-3 |
| EN 61000-4-6 | |
| Frequency range | 0.15 MHz ... 80 MHz |
| Voltage | 10 V (Test Level 3) |
| Conducted noise emission | EN 55016 EN 61000-6-4 (Class A) |
| Standards/regulations | EN 61000-4-11 |
| Low Voltage Directive | Conformance with Low Voltage Directive 2014/35/EC |
| Standard - Electrical safety | IEC 60950-1/VDE 0805 (SELV) |
| Standard – Safety extra-low voltage | IEC 60950-1 (SELV) and EN 60204-1 (PELV) |
| Standard - Safe isolation | DIN VDE 0100-410 |
| Standard – Limitation of mains harmonic currents | EN 61000-3-2 |
| UL approvals | UL Listed UL 508 |
| UL/C-UL Recognized UL 60950-1 | |
| Shock | 18 ms, 30g, in each space direction (according to IEC 60068-2-27) |
| Vibration (operation) | DNV GL CG-0339 / Class B 2 Hz - 100 Hz resonance search, 90 min. in resonance, 2 Hz - 25 Hz, ±1.6 mm amplitude, 25 Hz - 100 Hz, 4g acceleration |
| Rail applications | EN 50121-4 |
| Overvoltage category (EN 60950-1) | II |
| Overvoltage category (EN 62477-1) | III |
Environmental Product Compliance
| China RoHS | Environmentally Friendly Use Period = 25; |
|---|---|
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |