Power supply unit from Phoenix Contact, model TRIO-PS-2G/1AC/24DC/20, designed to convert incoming electrical mains into a stable low-voltage output for industrial control architectures. Units of this type supply reliable, continuous direct current to sensitive automation instrumentation, PLCs, and associated field devices mounted within control cabinets. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Voltage type (supply voltage) (EF002991): AC/DC
- 1st secondary output voltage (EF006792): 24 V
- Max. output current 1 (EF008284): 30 A
- Secondary voltage adjustable (EF007002): Yes
- Nominal value output voltage 1 (EF009393): 24 V
- Nominal value output current 1 (EF009396): 20 A
- Short-circuit-proof (EF007332): Yes
- Rated supply voltage AC 50 Hz (EF007076): 100 V
- Rated supply voltage AC 60 Hz (EF007077): 100 V
- Rated supply voltage DC (EF007078): 110 V
- Output voltage stabilized (EF003092): Yes
- Power consumption (EF000346): 534.7 VA
- Power output (EF003034): 480 W
- Stabilized (EF005302): Yes
- Suitable for rail mounting (EF003972): Yes
- Wall mounting possible (EF003973): No
More info
▲Key Commercial Data
| Orderkey | 2903151 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 221 (C-4-2017) |
| GTIN | 4046356960939 |
| Weight per Piece (excluding packing) | 1,675.800 g |
| Custom tariff number | 85044030 |
| Country of origin | CN (China) |
Ambient conditions
| Degree of protection | IP20 |
|---|---|
| Ambient temperature (operation) | -25 °C ... 70 °C (> 60 °C Derating: 2.5 %/K) |
| Ambient temperature (start-up type tested) | -40 °C |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Max. permissible relative humidity (operation) | ≤ 95 % (at 25 °C, non-condensing) |
| Climatic class | 3K3 (in acc. with EN 60721) |
| Degree of pollution | 2 |
| Installation height | ≤ 4000 m (> 2000 m, Derating: 10 %/1000 m) |
Input data
| Nominal input voltage range | 100 V AC ... 240 V AC |
|---|---|
| 110 V DC ... 250 V DC | |
| Input voltage range | 100 V AC ... 240 V AC -15 % ... +10 % |
| 99 V DC ... 275 V DC | |
| Dielectric strength maximum | ≤ 300 V AC 15 s |
| AC frequency range | 50 Hz ... 60 Hz ±10 % |
| Discharge current to PE | < 3.5 mA |
| Current consumption | 5.6 A (100 V AC) |
| 4.3 A (120 V AC) | |
| 2.4 A (230 V AC) | |
| 2.4 A (240 V AC) | |
| Nominal power consumption | 534.7 VA |
| Inrush surge current | ≤ 20 A (typical) |
| Mains buffering | typ. 10 ms (120 V AC) |
| typ. 15 ms (230 V AC) | |
| Input fuse | 10 A (internal (device protection)) |
| Choice of suitable circuit breakers | 10 A ... 16 A (Characteristics B, C, D, K) |
| Power factor (cos phi) | 0.98 |
| Type of protection | Transient surge protection |
| Protective circuit/component | Varistor |
Output data
| Nominal output voltage | 24 V DC ±1 % |
|---|---|
| Setting range of the output voltage (USet) | 24 V DC ... 28 V DC (> 24 V DC, constant capacity restricted) |
| Nominal output current (IN) | 20 A |
| Dynamic Boost (IDyn.Boost) | 30 A (5 s) |
| Derating | > 60 °C ... 70 °C (2.5%/K) |
| Connection in parallel | Yes, for redundancy and increased capacity |
| Connection in series | yes |
| Feedback resistance | ≤ 35 V DC |
| Protection against surge voltage on the output | ≤ 30 V DC |
| Control deviation | < 1 % (change in load, static 10 % ... 90 %) |
| < 3 % (Dynamic load change 10 % ... 90 %, 10 Hz) | |
| < 0.1 % (change in input voltage ±10 %) | |
| Residual ripple | < 30 mVPP(with nominal values) |
| Output power | 480 W |
| Typical response time | < 1 s |
| Maximum power dissipation in no-load condition | < 5.7 W |
| Power loss nominal load max. | < 44 W |
General
| Net weight | 1.5 kg |
|---|---|
| Efficiency | > 93 % (for 230 V AC and nominal values) |
| Insulation voltage input/output | 3 kV AC (type test) |
| 1.5 kV AC (routine test) | |
| Protection class | I (in closed control cabinet) |
| Degree of protection | IP20 |
| MTBF (IEC 61709, SN 29500) | > 1800000 h (25 °C) |
| > 1000000 h (40 °C) | |
| > 480000 h (60 °C) | |
| Mounting position | horizontal DIN rail NS 35, EN 60715 |
| Assembly instructions | alignable: horizontally 0 mm (≤ 40 °C) 10 mm (≤ 70 °C), vertically 50 mm |
Connection data, input
| Connection method | Push-in connection |
|---|---|
| Conductor cross section solid min. | 0.2 mm² |
| Conductor cross section solid max. | 4 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 2.5 mm² |
| Conductor cross section AWG min. | 24 |
| Conductor cross section AWG max. | 12 |
| Stripping length | 10 mm |
Connection data, output
| Connection method | Push-in connection |
|---|---|
| Conductor cross section solid min. | 0.2 mm² |
| Conductor cross section solid max. | 10 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 6 mm² |
| Conductor cross section AWG min. | 24 |
| Conductor cross section AWG max. | 8 |
| Stripping length | 15 mm |
Connection data for signaling
| Connection method | Push-in connection |
|---|---|
| Conductor cross section solid min. | 0.2 mm² |
| Conductor cross section solid max. | 1.5 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 1.5 mm² |
| Conductor cross section AWG min. | 24 |
| Conductor cross section AWG max. | 16 |
| Stripping length | 8 mm |
Standards and Regulations
| Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
|---|---|
| Noise emission | EN 55011 (EN 55022) |
| Noise immunity | EN 61000-6-2:2005 |
| Standards/regulations | EN 61000-4-2 |
| Contact discharge | 4 kV (Test Level 2) |
| Standards/regulations | EN 61000-4-3 |
| Frequency range | 80 MHz ... 1 GHz |
| Test field strength | 10 V/m (Test Level 3) |
| Frequency range | 1.4 GHz ... 2 GHz |
| Test field strength | 3 V/m (Test Level 2) |
| Standards/regulations | EN 61000-4-4 |
| Comments | Criterion B |
| Standards/regulations | EN 61000-6-3 |
| EN 61000-4-6 | |
| Frequency range | 0.15 MHz ... 80 MHz |
| Voltage | 10 V (Test Level 3) |
| Low Voltage Directive | Conformance with LV directive 2006/95/EC |
| Standard - Safety of transformers | EN 61558-2-16 (air clearances and creepage distances only) |
| Standard - Electrical safety | IEC 60950-1/VDE 0805 (SELV) |
| Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations | EN 50178/VDE 0160 (PELV) |
| Standard – Safety extra-low voltage | IEC 60950-1 (SELV) and EN 60204-1 (PELV) |
| Standard - Safe isolation | DIN VDE 0100-410 |
| Standard – Limitation of mains harmonic currents | EN 61000-3-2 |
| UL approvals | UL Listed UL 508 |
| UL/C-UL Recognized UL 60950-1 | |
| Shock | 18 ms, 30g, in each space direction (according to IEC 60068-2-27) |
| Vibration (operation) | < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6) |
| 15 Hz ... 150 Hz, 4g, 90 min. | |
| Rail applications | EN 50121-4 |
| GL | GL applied for |
Environmental Product Compliance
| REACh SVHC | Lead 7439-92-1 |
|---|---|
| China RoHS | Environmentally Friendly Use Period = 25; |