View larger
Images are for illustrative purposes only. Please refer to data sheet for details
MINI MCR-SL-PT100-LP-NC 2810308 PHOENIX CONTACT Temperature measuring transducer
MINI MCR-SL-PT100-LP-NC
2810308
PHOENIX CONTACT
1 Pcs.
Temperature measuring transducer
Configurable Loop-powered temperature converter for Pt 100 temperature sensors, configurable via DIP switch, with screw connection, without presetting
Configurable Loop Powered Converter for Pt 100 Temperature Sensors, DIP Switch Configurable, with Screw Connection, Not Preconfigured
Automation > Temperature transformer
INTERFACE Components (IF)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Phoenix Contact MINI MCR-SL-PT100-LP-NC temperature measuring transducer transforms Pt100 sensor resistances into stable analog signals, facilitating precise thermal control and data acquisition. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Measuring range (EF001836): -150 °C
- Analogue output 0 mA ... 20 mA (EF006808): No
- Analogue output 4 mA ... 20 mA (EF006810): Yes
- Analogue output 0 V ... 2 V (EF009886): No
- Analogue output 0 V ... 5 V (EF009887): No
- Analogue output 0 V ... 10 V (EF006807): No
- Analogue output 2 V ... 10 V (EF009888): No
- With switching output (EF005225): No
- Modular version (EF001126): Yes
- Integrated configuration function (EF003064): Yes
- EMC-version (EF001062): Yes
- Ambient temperature (EF002386): 65 °C
- Weight (EF000167): 0.0684 kg
More info
▲Key Commercial Data
| Orderkey | 2810308 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 106 (C-7-2015) |
| GTIN | 4046356134668 |
| Weight per Piece (excluding packing) | 68.400 g |
| Custom tariff number | 85437090 |
| Country of origin | DE (Germany) |
Note
| Utilization restriction | EMC: class A product, see manufacturer's declaration in the download area |
|---|
Ambient conditions
| Ambient temperature (operation) | -20 °C ... 65 °C |
|---|---|
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Maximum altitude | ≤ 2000 m |
Input data
| Configurable/programmable | Yes, unconfigured |
|---|---|
| Sensor types (RTD) that can be used | Pt 100 (IEC 60751/EN 60751) |
| Sensor input current | 1 mA (constant) |
| Connection technology | 2, 3, 4-wire |
Output data
| Number of outputs | 1 |
|---|---|
| Configurable/programmable | Yes, unconfigured |
| Current output signal | 4 mA ... 20 mA |
| 20 mA ... 4 mA | |
| Max. output current | 23 mA (output limit) |
| Load/output load current output | (Usupply- 12 V) / 22 mA |
| Ripple | < 20 mVPP(at 500 Ω) |
Power supply
| Designation | Loop-powered |
|---|---|
| Supply voltage range | 12 V DC ... 30 V DC |
| Max. current consumption | < 4.5 mA (without signal current) |
| Power consumption | < 150 mW (without signal current) |
Connection data
| Connection method | Screw connection |
|---|---|
| Conductor cross section solid min. | 0.2 mm² |
| Conductor cross section solid max. | 2.5 mm² |
| Conductor cross section AWG min. | 26 |
| Conductor cross section AWG max. | 12 |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 2.5 mm² |
| Stripping length | 12 mm |
| Screw thread | M3 |
General
| Transmission error in the set measuring range | ((90 K / set measuring range [K]) + 0.05)% |
|---|---|
| Transmission error in the full measuring range | ≤ 0,25 % |
| Maximum temperature coefficient | < 0.02 %/K |
| Linearity error | < 0.05 % (for full measuring range) |
| Electrical isolation | Basic insulation according to EN 61010 |
| Overvoltage category | II |
| Degree of pollution | 2 |
| Rated insulation voltage | 30 V AC |
| Test voltage, input/output/supply | 1.5 kV (50 Hz, 1 min.) |
| Electromagnetic compatibility | Conformance with EMC directive |
| Noise emission | EN 61000-6-4 |
| Noise immunity | EN 61000-6-2 When being exposed to interference, there may be minimal deviations. |
| Color | green |
| Housing material | PBT |
| Mounting position | any |
| Conformance | CE-compliant |
| ATEX | II 3 G Ex nA IIC T4 Gc X |
| UL, USA/Canada | UL 508 Recognized |
| Class I, Div. 2, Groups A, B, C, D T4 | |
| Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 - HL 2 |
| Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 - HL 2 |
| Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 - HL 2 |
EMC data
| Designation | Electromagnetic RF field |
|---|---|
| Standards/regulations | EN 61000-4-3 |
| Typical deviation from the measuring range final value | 5 % |
| Designation | Fast transients (burst) |
| Standards/regulations | EN 61000-4-4 |
| Typical deviation from the measuring range final value | 5 % |
| Designation | Conducted interferences |
| Standards/regulations | EN 61000-4-6 |
| Typical deviation from the measuring range final value | 5 % |
Standards and Regulations
| Electromagnetic compatibility | Conformance with EMC directive |
|---|---|
| Noise emission | EN 61000-6-4 |
| Connection in acc. with standard | CUL |
| Standards/regulations | EN 61000-4-2 |
| Designation | Electromagnetic RF field |
| Standards/regulations | EN 61000-4-3 |
| EN 61000-4-4 | |
| EN 61000-4-5 | |
| Designation | Conducted interferences |
| Standards/regulations | EN 61000-4-6 |
| Electrical isolation | Basic insulation according to EN 61010 |
| Conformance | CE-compliant |
| ATEX | II 3 G Ex nA IIC T4 Gc X |
| UL, USA/Canada | UL 508 Recognized |
| Class I, Div. 2, Groups A, B, C, D T4 | |
| Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 - HL 2 |
| Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 - HL 2 |
| Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 - HL 2 |
Environmental Product Compliance
| China RoHS | Environmentally Friendly Use Period = 50 |
|---|---|
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |