View larger
MCR-SL-S-200-U 2813460 PHOENIX CONTACT Current transducers
MCR-SL-S-200-U
2813460
PHOENIX CONTACT
1 Pcs.
Automation > Current value transformer
INTERFACE Components (IF)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Current transducer model MCR-SL-S-200-U from Phoenix Contact processes electrical input signals to generate proportional voltage outputs for industrial monitoring applications. Such devices protect sensitive control electronics by providing galvanic isolation between primary power circuits and secondary instrumentation. Pricing, availability, and lead time are confirmed per enquiry through an RFQ.
- Product type: Current transducer
- Data management status Article revision: 03
- Insulation characteristics Overvoltage category: III
- Pollution degree: 2
- Maximum power dissipation for nominal condition: 1 W
- Test voltage input/output: 4.13 kV AC (50 Hz, 60 s)
- Step response (10-90%): < 340 ms
- Maximum temperature coefficient: < 0.035 %/K
- Maximum transmission error: < 1 % (of final value)
- Rated insulation voltage: 300 V AC (to earth)
- Supply Nominal supply voltage: 24 V DC
- Supply voltage range: 20 V DC ... 30 V DC
- Max. current consumption: < 30 mA
- Signal Configurable/programmable: Yes
- Current input signal: 0 A ... 200 A
- Measurement Input current range: 0 A AC ... 100 A AC
More info
▲| Product type | Current transducer |
| Data management status | |
| Article revision | 03 |
| Insulation characteristics | |
| Overvoltage category | III |
| Pollution degree | 2 |
| Maximum power dissipation for nominal condition | 1 W |
| Test voltage input/output | 4.13 kV AC (50 Hz, 60 s) |
| Step response (10-90%) | < 340 ms |
| Maximum temperature coefficient | < 0.035 %/K |
| Maximum transmission error | < 1 % (of final value) |
| Rated insulation voltage | 300 V AC (to earth) |
| Supply | |
| Nominal supply voltage | 24 V DC |
| Supply voltage range | 20 V DC ... 30 V DC |
| Max. current consumption | < 30 mA |
| Signal | |
| Configurable/programmable | Yes |
| Current input signal | 0 A ... 200 A |
| Measurement | |
| Input current range | 0 A AC ... 100 A AC |
| 0 A AC ... 150 A AC | |
| 0 A AC ... 200 A AC | |
| Setting range for min. input current | 0 A AC ... 100 A AC |
| Setting range for max. input current | 0 A AC ... 200 A AC |
| Overload capacity | Depending on laid conductor |
| Surge strength | Depending on through connected conductor |
| Frequency measuring range | 30 Hz ... 6000 Hz |
| Curve type | Sinusoidal and non-sinusoidal |
| Operate threshold | 1 % (of final value) |
| Signal: Voltage | |
| Voltage output signal | 0 V ... 5 V |
| 0 V ... 10 V | |
| Max. voltage output signal | (0 V ... 10 V) 14 V, (0 V ... 5 V) 7 V |
| Load/output load voltage output | ≥ 10 kΩ |
| Connection method | Screw connection |
| Stripping length | 8 mm |
| Screw thread | M3 |
| Conductor cross section rigid | 0.2 mm² ... 2.5 mm² |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross section AWG | 24 ... 14 |
| Tightening torque | 0.5 Nm ... 0.6 Nm (4,4 ... 5,31 lbf-in.) |
| Connection method | Through connection |
| Item dimensions | |
| Width | 55 mm |
| Height | 85 mm |
| Depth | 70.5 mm |
| Circular conductor | |
| Diameter | ≤ 18.5 mm |
| Color | green (RAL 6021) |
| Housing material | Polyamide PA non-reinforced |
| Ambient conditions | |
| Degree of protection | IP20 |
| Ambient temperature (operation) | -20 °C ... 60 °C |
| CE | |
| Certificate | CE-compliant |
| UKCA | |
| Certificate | UKCA-compliant |
| UL, USA/Canada | |
| Identification | UL/C-UL Listed UL 508 |
| Class I, Div. 2, Groups A, B, C, D T4A | |
| Class I, Zone 2, Group IIC T4A | |
| Or Non-Hazardous Locations only | |
| Mounting type | DIN rail mounting |
| Mounting position | any |