Phoenix Contact unit MCR-S10-50-UI-DCI-NC acts as a dependable Current transducers module used to monitor electrical loads and protect automated industrial systems. Transducers convert primary current variables into standardized, proportional output signals compatible with PLCs and data acquisition systems. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Orderkey: 2814728
- Packing unit: 1 pc
- Catalog page: Page 243 (C-5-2017)
- GTIN: 4017918169305
- Weight per Piece (excluding packing): 119.480 g
- Custom tariff number: 85437090
- Country of origin: DE (Germany)
- Utilization restriction: EMC: class A product, see manufacturer's declaration in the download area
- Width: 22.5 mm
- Height: 99 mm
- Depth: 114.5 mm
- Ambient temperature (operation): -20 °C ... 60 °C
- Ambient temperature (storage/transport): -40 °C ... 85 °C
- Maximum altitude: < 2000 m
- Input: Current measuring input
- Configurable/programmable: Yes, unconfigured
More info
▲Key Commercial Data
| Orderkey | 2814728 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 243 (C-5-2017) |
| GTIN | 4017918169305 |
| Weight per Piece (excluding packing) | 119.480 g |
| Custom tariff number | 85437090 |
| Country of origin | DE (Germany) |
Note
| Utilization restriction | EMC: class A product, see manufacturer's declaration in the download area |
|---|
Ambient conditions
| Ambient temperature (operation) | -20 °C ... 60 °C |
|---|---|
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Maximum altitude | < 2000 m |
Input data
| Input | Current measuring input |
|---|---|
| Configurable/programmable | Yes, unconfigured |
| Input current range | 0 A ... 55 A (AC/DC) |
| Operate threshold | 0.8 % (of measuring range nominal value 50 A) |
| Setting range for min. input current | 0 A ... 9.5 A |
| Setting range for max. input current | 0 A ... 55 A |
| Impulse form | AC, DC or distorted currents |
| Overload capacity | Depending on through connected conductor |
| Surge strength | Depending on through connected conductor |
| Frequency measuring range | 15 Hz ... 400 Hz |
| Connection method | Through connection, diameter 10.5 mm |
Output data
| Output name | Voltage output / current output |
|---|---|
| Configurable/programmable | Yes, unconfigured |
| Voltage output signal | 0 V ... 10 V |
| 5 V ... 1 V | |
| 5 V ... -5 V | |
| 2 V ... 10 V | |
| -10 V ... 10 V | |
| 0 V ... 5 V | |
| 1 V ... 5 V | |
| -5 V ... 5 V | |
| 10 V ... 0 V | |
| 10 V ... 2 V | |
| 10 V ... -10 V | |
| 5 V ... 0 V | |
| Current output signal | 0 mA ... 20 mA |
| 4 mA ... 20 mA | |
| 20 mA ... 0 mA | |
| 20 mA ... 4 mA | |
| Load/output load voltage output | > 10 kΩ |
| Load/output load current output | < 500 Ω |
Connection data
| Connection method | Screw connection |
|---|---|
| Conductor cross section solid min. | 0.2 mm² |
| Conductor cross section solid max. | 2.5 mm² |
| Conductor cross section AWG min. | 24 |
| Conductor cross section AWG max. | 14 |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 2.5 mm² |
| Stripping length | 8 mm |
| Screw thread | M3 |
General
| Maximum transmission error | < 0.5 % (of nominal range value under nominal conditions) |
|---|---|
| Temperature coefficient, typical | < 0.025 %/K |
| Step response (10-90%) | 330 ms (with AC) |
| 40 ms (with DC) | |
| Status display | Green LED |
| Overvoltage category | III |
| Degree of pollution | 2 |
| Rated insulation voltage | 300 V AC (to earth) |
| Test voltage input/output | 4 kV (50 Hz, 1 min.) |
| Test voltage input/power supply | 4 kV (50 Hz, 1 min.) |
| Test voltage output/power supply | 500 V (50 Hz, 1 min.) |
| Electromagnetic compatibility | Conformance with EMC directive |
| Noise emission | EN 61000-6-4 |
| Noise immunity | EN 61000-6-2 |
| Color | green |
| Housing material | Polyamide PA non-reinforced |
| Mounting position | any |
| Conformance | CE-compliant |
| UL, USA/Canada | Class I, Zone 2, AEx nA nC IIC T4, Ex nA nC IIC T4 Gc X |
| Class I, Div. 2, Groups A, B, C and D or Non-Hazardous Locations Only |
Standards and Regulations
| Electromagnetic compatibility | Conformance with EMC directive |
|---|---|
| Noise emission | EN 61000-6-4 |
| Noise immunity | EN 61000-6-2 |
| Connection in acc. with standard | CUL |
| Low Voltage Directive | Conformance with Low Voltage Directive |
| Conformance | CE-compliant |
| UL, USA/Canada | Class I, Zone 2, AEx nA nC IIC T4, Ex nA nC IIC T4 Gc X |
| Class I, Div. 2, Groups A, B, C and D or Non-Hazardous Locations Only |