View larger
TMCP 1 M1 300 12,0A 0915849 PHOENIX CONTACT Thermomagnetic device circuit breaker
TMCP 1 M1 300 12,0A
0915849
PHOENIX CONTACT
6 Pcs.
Automation > Device circuit breaker
Over Current Protection
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
The Phoenix Contact TMCP 1 M1 300 12,0A 0915849 PHOENIX CONTACT Thermomagnetic device circuit breaker acts as a dedicated safeguard for industrial machinery and distribution boards. Panel builders utilize these devices to protect individual electrical loops from the damaging effects of excessive current flow, ensuring operational uptime across automated processes.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Product type: Thermomagnetic device circuit breakers
- Product family: TMCP
- Type: Male
- Number of positions: 1
- No. of channels: 1
- Insulation characteristics Overvoltage category: II
- Degree of pollution: 2
- Fuse type: Automatic device
- General Rated voltage: 250 V AC
- Rated current I N: 12 A
- Rated surge voltage: 2.5 kV
- Insulation resistance R iso: > 100 MΩ (500 V DC)
- Auxiliary circuit: 240 V AC / 1 A (Low-induction)
- Tripping method: TM (thermomagnetic)
- Device resistance: 0.02 Ω
- Rated short-circuit switching capacity I cn: 800 A
More info
▲| Product type | Thermomagnetic device circuit breakers |
| Product family | TMCP |
| Type | Male |
| Number of positions | 1 |
| No. of channels | 1 |
| Insulation characteristics | |
| Overvoltage category | II |
| Degree of pollution | 2 |
| Fuse type | Automatic device |
| General | |
| Rated voltage | 250 V AC |
| 65 V DC | |
| Rated current IN | 12 A |
| Rated surge voltage | 2.5 kV |
| Insulation resistance Riso | > 100 MΩ (500 V DC) |
| Auxiliary circuit | 240 V AC / 1 A (Low-induction) |
| 65 V AC / 1 A (Low-induction) | |
| Tripping method | TM (thermomagnetic) |
| Device resistance | 0.02 Ω |
| Rated short-circuit switching capacity Icn | 800 A |
| 2500 A (32 V DC) | |
| Short-circuit switching capacity | 5000 A (UL 1077: 277 V AC) |
| 2000 A (UL 1077: 65 V DC) | |
| Dielectric strength | 3000 V AC (Actuation area) |
| 1500 V AC (Main to auxiliary circuit) | |
| 1000 V AC (Auxiliary circuit 11 - 12 to 23 - 24) | |
| Switching cycles, max. | 10000 (At 1 x In, inductive) |
| Fuse | M1 (normal blow) |
| Connection method | pluggable |
| Connection method | pluggable |
| Width | 12.5 mm |
| Height | 50 mm |
| Depth | 78.5 mm |
| Complete module width | 38 mm |
| Complete module height | 115 mm |
| Complete module depth | 121 mm |
| Color | black (RAL 9005) |
| Flammability rating according to UL 94 | V-2 |
| Insulating material group | II |
| Insulating material | PA66 |
| Mechanical data | |
| Open side panel | No |
| Ambient conditions | |
| Degree of protection | IP30 (Actuation area) |
| IP00 (Connection area) | |
| Ambient temperature (operation) | -30 °C ... 60 °C |
| Humidity test | 240 h, 95 % RH, 40 °C |
| Standards/specifications | EN 60934 |
| Standards/specifications | UL 1077 |
| Mounting type | on base element |