PHOENIX CONTACT UT 6-TMC M 8A UT 6-TMC M 8A 0916609 PHOENIX CONTACT Thermomagnetic device circuit breaker View larger
Images are for illustrative purposes only. Please refer to data sheet for details

UT 6-TMC M 8A 0916609 PHOENIX CONTACT Thermomagnetic device circuit breaker

UT 6-TMC M 8A

0916609

PHOENIX CONTACT

6 Pcs.

Thermomagnetic device circuit breaker Thermomagnetic protection switch, 1 pole, for symmetrical rail mounting Circuit breaker, 1 pole, for DIN rail mounting

Automation > Device circuit breaker
Over Current Protection

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

Safeguarding industrial machinery from excess current loads, the Phoenix Contact UT 6-TMC M 8A thermomagnetic device circuit breaker provides dual-action protection against short circuits and thermal overloads. This hardware is a staple in control cabinet builds where reliable circuit segmentation is required.

Pricing, availability and lead time are confirmed per enquiry through an RFQ.

  • Orderkey: 0916609
  • Packing unit: 6 pc
  • Catalog page: Page 332 (C-4-2017)
  • GTIN: 4046356449052
  • Weight per Piece (excluding packing): 63.000 g
  • Custom tariff number: 85362010
  • Country of origin: CZ (Czech Republic)
  • Number of levels: 1
  • Number of connections: 2
  • Mounting type: DIN rail: 35 mm
  • Color: gray
  • Number of positions: 1
  • Overvoltage category_GRP: II
  • Insulating material: PA66
  • Flammability rating according to UL 94: V0
  • Fuse type: Automatic device

More info

▲

Key Commercial Data

Orderkey0916609
Packing unit6 pc
Catalog pagePage 332 (C-4-2017)
GTIN4046356449052
Weight per Piece (excluding packing)63.000 g
Custom tariff number85362010
Country of originCZ (Czech Republic)

General

Number of levels1
Number of connections2
Mounting typeDIN rail: 35 mm
Colorgray
Number of positions1
Overvoltage category_GRPII
Insulating materialPA66
Flammability rating according to UL 94V0

Electrical data

Fuse typeAutomatic device
Rated surge voltage2.8 kV
Rated voltage240 V AC (50/60 Hz)
28 V DC
240 V AC (50/60 Hz)
28 V DC
Operating voltage50 V AC ... 264 V AC (48 - 62 Hz)
5 V DC ... 30.8 V DC
Rated current IN8 A
Rated insulation voltage Ui440 V AC
Insulation resistance Riso> 100 MΩ (main contact)
Required backup fuse25 A
Rated short-circuit switching capacity Icn200 A (240 V AC)
400 A (28 V DC)
Dielectric strength2000 V
Switching cycles, max.6000 (at 1 x In)
50 (at 1.5 x In)
40 (at 6 x In)
Degree of pollution2
Overvoltage category_GRPII

Dimensions

Height85.5 mm
Width12.3 mm
Depth89.5 mm

Ambient conditions

Ambient temperature (operation)-30 °C ... 60 °C
Altitude2000 m (acc. to EN 60934)
Degree of protectionIP40 (Actuation area)
IP20 (Connection area)

Connection data

Conductor cross section solid min.0.2 mm²
Conductor cross section solid max.10 mm²
Conductor cross section flexible min.0.2 mm²
Conductor cross section flexible max.10 mm²
Conductor cross section AWG min.24
Conductor cross section AWG max.8
Conductor cross section flexible, with ferrule without plastic sleeve min.0.25 mm²
Conductor cross section flexible, with ferrule without plastic sleeve max.6 mm²
Conductor cross section flexible, with ferrule with plastic sleeve min.0.25 mm²
Conductor cross section flexible, with ferrule with plastic sleeve max.6 mm²
2 conductors with same cross section, solid min.0.2 mm²
2 conductors with same cross section, solid max.2.5 mm²
2 conductors with same cross section, stranded min.0.2 mm²
2 conductors with same cross section, stranded max.2.5 mm²
2 conductors with same cross section, stranded, ferrules without plastic sleeve, min.0.25 mm²
2 conductors with same cross section, stranded, ferrules without plastic sleeve, max.1.5 mm²
2 conductors with same cross section, stranded, TWIN ferrules with plastic sleeve, min.0.5 mm²
2 conductors with same cross section, stranded, TWIN ferrules with plastic sleeve, max.4 mm²
Connection methodScrew connection
Stripping length10 mm
Screw threadM4
Tightening torque, min1.5 Nm
Tightening torque max1.8 Nm

Standards and Regulations

Standards/specificationsEN 60934
UL 1077
CSA 22.2 No. 235
EAC

Environmental Product Compliance

REACh SVHCLead 7439-92-1
China RoHSEnvironmentally Friendly Use Period = 50
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”

Classifications


Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.