View larger
CB TM1 6A F1 P 2800863 PHOENIX CONTACT Thermomagnetic device circuit breaker
CB TM1 6A F1 P
2800863
PHOENIX CONTACT
1 Pcs.
Automation > Device circuit breaker
Over Current Protection
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
A CB TM1 6A F1 P PHOENIX CONTACT thermomagnetic device circuit breaker serves as a critical protective element in electrical panels, disconnecting power when current thresholds are exceeded. It utilizes dual tripping technologies to safely interrupt both sustained overloads and sudden short circuits. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Product type: Thermomagnetic device circuit breakers
- Product family: CB TM
- Type: Male
- Number of positions: 1
- No. of channels: 1
- Data management status Article revision: 06
- Insulation characteristics Degree of pollution: 2
- Fuse type: Automatic device
- General Rated voltage: 50 V DC (IEC 60934)
- Rated insulation voltage U i: 277 V AC (UL 1077)
- Rated current I N: 6 A (IEC 60934)
- Rated surge voltage: 2.5 kV (Increased insulation in actuation area)
- Insulation resistance R iso: > 100 MΩ (500 V DC)
- Auxiliary circuit: 277 V AC / 0.5 A (Low-induction)
- Type of actuation: S type
- Tripping method: TM (thermomagnetic)
More info
▲| General | When mounted in rows, the nominal device current can be limited to just 80% or must be overdimensioned accordingly. |
| Product type | Thermomagnetic device circuit breakers |
| Product family | CB TM |
| Type | Male |
| Number of positions | 1 |
| No. of channels | 1 |
| Data management status | |
| Article revision | 06 |
| Insulation characteristics | |
| Degree of pollution | 2 |
| Fuse type | Automatic device |
| General | |
| Rated voltage | 50 V DC (IEC 60934) |
| 50 V DC (UL 1077) | |
| 50 V DC (UL 508 - with plug-in base) | |
| Rated insulation voltage Ui | 277 V AC (UL 1077) |
| 250 V AC (IEC 60934) | |
| Rated current IN | 6 A (IEC 60934) |
| inductive load according to UL 1077 | |
| 6 A DC (low-induction load according to UL 1077) | |
| 6 A DC (inductive load according to UL 508 - with plug-in base) | |
| 6 A DC (low-induction load according to UL 508 - with plug-in base) | |
| Rated surge voltage | 2.5 kV (Increased insulation in actuation area) |
| Insulation resistance Riso | > 100 MΩ (500 V DC) |
| Auxiliary circuit | 277 V AC / 0.5 A (Low-induction) |
| 277 V AC / 1 A (Low-induction, maximum of 2000 cycles) | |
| 50 V DC / 1 A (Low-induction) | |
| Type of actuation | S type |
| Tripping method | TM (thermomagnetic) |
| Tripping level | Trip-free mechanism (positive) |
| Device resistance | 50 mΩ |
| Switch-on delay | typ. 2 ms |
| Required backup fuse | 24 A (I > Icn) |
| Rated short-circuit switching capacity Icn | 600 A (50 V DC) |
| Short-circuit switching capacity | 1000 A AC (277 V AC) |
| 1000 A DC (50 V DC) | |
| Dielectric strength | 3000 V AC (Actuation area) |
| 1500 V AC (Main to auxiliary circuit) | |
| 1500 V AC (Open main circuit) | |
| 1000 V AC (Open auxiliary circuit) | |
| Switching cycles, max. | 6000 (at 1 x In) |
| Fuse | F1 (fast blow) |
| Power dissipation | 1.8 W (in nominal operation per channel) |
| Voltage drop | 0.29 V (at 1 x In) |
| Auxiliary contact | |
| Minimum operating voltage UminDC | 10 V |
| Maximum operating voltage UmaxDC | 240 V |
| Maximum operating voltage Umax.AC | 240 V |
| Minimum operating current Imin | 10 mA |
| Max. operating current Imax | 1 A |
| Connection method | pluggable |
| Connection method | pluggable |
| Dimensional drawing | |
| Width | 12.3 mm |
| Height | 45 mm |
| Depth | 52 mm |
| Complete module width | 12.3 mm |
| Complete module height | 90 mm |
| Complete module depth | 77.3 mm |
| Color | gray (RAL 7042) |
| black (RAL 9005) | |
| Flammability rating according to UL 94 | V-0 |
| Insulating material group | II |
| Mechanical data | |
| Open side panel | No |
| Ambient conditions | |
| Degree of protection | IP30 (Actuation area) |
| Ambient temperature (operation) | -30 °C ... 60 °C |
| Ambient temperature (storage/transport) | -40 °C ... 80 °C |
| Humidity test | 240 h, 95 % RH, 40 °C |
| Shock (operation) | 15g (IEC 60068-2-27, Test Ea) |
| Vibration (operation) | 5g (IEC 60068-2-6, Test Fc) |
| UL approval | |
| Identification | UL Listed UL 508 |
| UL/C-UL Recognized UL 1077 | |
| CSA | |
| Identification | CSA CAN/CSA-C22.2 No. 235-04 |
| Shipbuilding approval | |
| Identification | DNV GL |
| Standards/specifications | EN 60934 |
| Mounting type | on base element |