CB TM1 16A F1 P 2800867 PHOENIX CONTACT Thermomagnetic device circuit breaker
CB TM1 16A F1 P
2800867
PHOENIX CONTACT
1 Pcs.
Automation > Device circuit breaker
Over Current Protection
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Pluggable modular protection is delivered by the Phoenix Contact CB TM1 16A F1 P 2800867 PHOENIX CONTACT Thermomagnetic device circuit breaker within modern control cabinets. Pluggable circuit breakers streamline maintenance routines by allowing technicians to swap out protection modules quickly without disrupting adjacent wiring or structural terminal assemblies.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Number of poles (EF001391): 1
- Construction type (EF000767): Plug
- Width (EF000008): 12.3 mm
- Height (EF000040): 45 mm
- Depth (EF000049): 52 mm
- Operating voltage (EF000111): 50 V
- Nominal current (EF000001): 16 A
- Active current limitation x IN (EF011922): 0
- With remote signalling contact (EF000422): No
- Ambient temperature during operating (EF007515): -30 °C
More info
▲Key Commercial Data
| Orderkey | 2800867 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 330 (C-4-2017) |
| GTIN | 4046356690195 |
| Weight per Piece (excluding packing) | 42.320 g |
| Custom tariff number | 85362010 |
| Country of origin | ID (Indonesia) |
Dimensions
| Height | 45 mm |
|---|---|
| Width | 12.3 mm |
| Depth | 52 mm |
| Complete module height | 90 mm |
| Complete module width | 12.3 mm |
| Complete module depth | 77.3 mm |
Ambient conditions
| Ambient temperature (operation) | -30 °C ... 60 °C |
|---|---|
| Ambient temperature (storage/transport) | -40 °C ... 80 °C |
| Humidity test | 240 h, 95 % RH, 40 °C |
| Shock (operation) | 15g (IEC 60068-2-27, Test Ea) |
| Vibration (operation) | 5g (IEC 60068-2-6, Test Fc) |
| Degree of protection | IP30 (Actuation area) |
General
| Installation instructions | When mounted in rows, the nominal device current can be limited to just 80% or must be overdimensioned accordingly. |
|---|---|
| Flammability rating according to UL 94 | V0 |
| Mounting type | on base element |
| Color | gray |
| Number of positions | 1 |
| Insulating material group | II |
| Degree of pollution | 2 |
| Type | Male |
Electrical data
| Fuse type | fast blow |
|---|---|
| Rated surge voltage | 2.5 kV (Increased insulation in actuation area) |
| Rated voltage | 50 V DC (IEC 60934) |
| 50 V DC (UL 1077) | |
| 50 V DC (UL 508 - with plug-in base) | |
| Rated current IN | 16 A (IEC 60934) |
| inductive load according to UL 1077 | |
| 16 A DC (low-induction load according to UL 1077) | |
| 16 A DC (low-induction load according to UL 508 - with plug-in base) | |
| 16 A | |
| Rated insulation voltage Ui | 277 V AC (UL 1077) |
| 250 V AC (IEC 60934) | |
| Power dissipation | 5.12 W (in nominal operation per channel) |
| Device resistance | 8 mΩ |
| Insulation resistance Riso | > 100 MΩ (500 V DC) |
| Type of actuation | S type |
| Tripping method | TM (thermomagnetic) |
| Tripping level | Trip-free mechanism (positive) |
| Rated short-circuit switching capacity Icn | |
| 600 A (50 V DC) | |
| Required backup fuse | 64 A (I > Icn) |
| Short-circuit switching capacity Ik | 1000 A AC (277 V AC) |
| 1000 A DC (50 V DC) | |
| Dielectric strength | 3000 V AC (Actuation area) |
| 1500 V AC (Main to auxiliary circuit) | |
| 1500 V AC (Open main circuit) | |
| 1000 V AC (Open auxiliary circuit) | |
| Voltage drop | 0.13 V (at 1 x In) |
| Switching cycles, max. | 6000 (at 1 x In) |
| Auxiliary circuit | 277 V AC / 0.5 A (Low-induction) |
| 277 V AC / 1 A (Low-induction, maximum of 2000 cycles) | |
| 50 V DC / 1 A (Low-induction) | |
| Minimum auxiliary contact operating voltage | 10 V |
| Maximum auxiliary contact operating voltage | 240 V |
| 240 V | |
| Minimum auxiliary contact operating current | 10 mA |
| Maximum auxiliary contact operating current | 1 A |
Standards and Regulations
| Standards/specifications | EN 60934 |
|---|---|
| UL 1077 UL/C-UL recognized | |
| UL 508 UL/C - UL listed | |
| CSA 22.2 No. 235-04 |