PHOENIX CONTACT SRTK 6 SRTK 6 3029952 PHOENIX CONTACT Test disconnect terminal block View larger
Images are for illustrative purposes only. Please refer to data sheet for details

SRTK 6 3029952 PHOENIX CONTACT Test disconnect terminal block

SRTK 6

3029952

PHOENIX CONTACT

1 Pcs.

Test disconnect terminal block Borne interrupts. for circ. Size, Rated Voltage: 400 V, Rated Current: 41 A, Connection Type: Spring Connection, 1st Floor, Sizing Section: 6 mm², Section: 0.2 mm² - 10 mm², Color: Gray

Automation > (Knife) disconnect terminal block
Modular TBs

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

A test disconnect terminal block provides a secure method for isolating electrical signals and taking measurements in control systems without disturbing permanent field wiring. The Phoenix Contact SRTK 6 3029952 PHOENIX CONTACT Test disconnect terminal block utilizes spring clamp connections to facilitate fast and vibration-resistant installation within electrical enclosures.

Pricing, availability and lead time are confirmed per enquiry through an RFQ.

  • Connectable conductor cross section solid-core (EF007337): 0.2 mm²
  • Rated current In (EF008250): 41 A
  • Rated voltage (EF000228): 400 V
  • Type of electrical connection 1 (EF002526): Spring clamp connection
  • Type of electrical connection 2 (EF002527): Spring clamp connection
  • Number of clamp positions per level (EF002660): 2
  • Internally connected stages (EF002661): Yes
  • Mounting method (EF000003): DIN rail (top hat rail) 35 mm
  • Width (EF000008): 8.2 mm
  • Height (EF000040): 113 mm
  • Depth (EF000049): 49 mm
  • Closing plate required (EF002525): Yes
  • Colour (EF000007): Grey

More info

▲

Key Commercial Data

Orderkey3029952
Packing unit50 pc
Catalog pagePage 186 (C-1-2017)
GTIN4046356169981
Weight per Piece (excluding packing)34.260 g
Custom tariff number85369010
Country of originPL (Poland)

General

Number of levels1
Number of connections2
Potentials1
Nominal cross section6 mm²
Colorgray
Insulating materialPA
Flammability rating according to UL 94V0
Rated surge voltage6 kV
Degree of pollution3
Overvoltage categoryIII
Insulating material groupI
Maximum power dissipation for nominal condition1.31 W
Maximum load current45 A (with 10 mm² conductor cross section)
Nominal current IN41 A
Nominal voltage UN400 V
Open side panelYes
Shock protection test specificationIEC 60529:2001-02
Back of the hand protectionguaranteed
Finger protectionguaranteed
Result of surge voltage testTest passed
Surge voltage test setpoint7.3 kV
Result of power-frequency withstand voltage testTest passed
Power frequency withstand voltage setpoint1.89 kV
Result of the test for mechanical stability of terminal points (5 x conductor connection)Test passed
Result of bending testTest passed
Bending test rotation speed10 rpm
Bending test turns135
Bending test conductor cross section/weight1 mm² / 0.4 kg
6 mm2/ 1.4 kg
10 mm² / 2 kg
Tensile test resultTest passed
Conductor cross section tensile test1 mm²
Tractive force setpoint35 N
Conductor cross section tensile test6 mm²
Tractive force setpoint80 N
Conductor cross section tensile test10 mm²
Tractive force setpoint90 N
Result of tight fit on supportTest passed
Tight fit on carrierNS 32/NS 35
Setpoint5 N
Result of voltage-drop testTest passed
Requirements, voltage drop≤ 6,4 mV
Result of temperature-rise testTest passed
Short circuit stability resultTest passed
Conductor cross section short circuit testing6 mm²
Short-time current0.72 kA
Conductor cross section short circuit testing10 mm²
Short-time current1.2 kA
Result of thermal testTest passed
Ageing test for screwless modular terminal block temperature cycles192
Proof of thermal characteristics (needle flame) effective duration30 s
Result of aging testTest passed
Oscillation, broadband noise test resultTest passed
Test specification, oscillation, broadband noiseDIN EN 50155 (VDE 0115-200):2008-03
Test spectrumService life test category 1, class B, body mounted
Test frequencyf1= 5 Hz to f2= 150 Hz
ASD level1.857 (m/s2)2/Hz
Acceleration0,8 g
Test duration per axis5 h
Test directionsX-, Y- and Z-axis
Shock test resultTest passed
Test specification, shock testDIN EN 50155 (VDE 0115-200):2008-03
Shock formHalf-sine
Acceleration5 g
Shock duration30 ms
Number of shocks per direction3
Test directionsX-, Y- and Z-axis (pos. and neg.)
Relative insulation material temperature index (Elec., UL 746 B)130 °C
Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21))130 °C
Static insulating material application in cold-60 °C
Behavior in fire for rail vehicles (DIN 5510-2)Test passed
Flame test method (DIN EN 60695-11-10)V0
Oxygen index (DIN EN ISO 4589-2)>32 %
NF F16-101, NF F10-102 Class I2
NF F16-101, NF F10-102 Class F2
Surface flammability NFPA 130 (ASTM E 162)passed
Specific optical density of smoke NFPA 130 (ASTM E 662)passed
Smoke gas toxicity NFPA 130 (SMP 800C)passed
Calorimetric heat release NFPA 130 (ASTM E 1354)28 MJ/kg
Fire protection for rail vehicles (DIN EN 45545-2) R22HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R23HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R24HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R26HL 1 - HL 3

Dimensions

Width8.2 mm
End cover width2 mm
Length113 mm
Height NS 35/7,549 mm
Height NS 35/1556.5 mm

Connection data

Connection methodSpring-cage connection
Stripping length12 mm
Connection in acc. with standardIEC 60947-7-1
Conductor cross section solid min.0.2 mm²
Conductor cross section solid max.10 mm²
Conductor cross section AWG min.24
Conductor cross section AWG max.8
Conductor cross section flexible min.0.2 mm²
Conductor cross section flexible max.6 mm²
Min. AWG conductor cross section, flexible24
Max. AWG conductor cross section, flexible10
Conductor cross section flexible, with ferrule without plastic sleeve min.0.25 mm²
Conductor cross section flexible, with ferrule without plastic sleeve max.6 mm²
Conductor cross section flexible, with ferrule with plastic sleeve min.0.25 mm²
Conductor cross section flexible, with ferrule with plastic sleeve max.6 mm²
2 conductors with same cross section, stranded, TWIN ferrules with plastic sleeve, min.0.5 mm²
2 conductors with same cross section, stranded, TWIN ferrules with plastic sleeve, max.1.5 mm²
Internal cylindrical gageA4

Standards and Regulations

Connection in acc. with standardCUL
IEC 60947-7-1
Flammability rating according to UL 94V0
Fire protection for rail vehicles (DIN EN 45545-2) R22HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R23HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R24HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R26HL 1 - HL 3

Environmental Product Compliance

China RoHSEnvironmentally friendly use period: unlimited = EFUP-e
No hazardous substances above threshold values

Classifications


Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.