Double-level terminal block Double-deck terminal block, The operating voltage is determined by the indicator light variant. Characteristic data LED 12 V DC ... 30 V DC, 0.7 mA ... 2.4 mA, rated voltage: 500 V, rated current: 20 A, connection type: Push-in connection, Sizing cross-section: 2.5 mm², cross-section: 0.14 mm² - 4 mm², mounting: NS 35/7.5, NS 35/15, color: gray

Automation > Component terminal block
Modular TBs

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

Phoenix Contact PTTB 2,5-LA 24 RD is a double-level terminal block utilized in industrial automation systems for multi-conductor pass-through connections and integrated optical status indication. Pricing, availability and lead time are confirmed per enquiry through an RFQ.

  • Connectable conductor cross section solid-core (EF007337): 0.14 mm²
  • Rated current In (EF008250): 20 A
  • Rated voltage (EF000228): 500 V
  • Number of levels (EF002659): 2
  • Number of clamp positions per level (EF002660): 2
  • Internally connected stages (EF002661): No
  • Mounting method (EF000003): DIN rail (top hat rail) 35 mm
  • Width (EF000008): 5.2 mm
  • Height (EF000040): 68.2 mm
  • Depth (EF000049): 45.9 mm
  • Closing plate required (EF002525): Yes
  • Colour (EF000007): Grey

More info

▲

Key Commercial Data

Orderkey3211456
Packing unit50 pc
Minimum order quantity50 pc
Catalog pagePage 80 (C-1-2017)
GTIN4046356433792
Weight per Piece (excluding packing)13.420 g
Custom tariff number85369010
Country of originPL (Poland)

General

NoteThe operating voltage is determined by the LED display version. Key data LED 12 V DC - 30 V DC, 0.7 mA - 2.4 mA
Number of levels2
Number of connections4
Nominal cross section2.5 mm²
Colorgray
Insulating materialPA
Flammability rating according to UL 94V0
Rated surge voltage4 kV
Degree of pollution3
Overvoltage categoryIII
Insulating material groupI
Maximum power dissipation for nominal condition0.77 W (the value is multiplied when connecting multiple levels)
Ambient temperature (operation)-40 °C ... 130 °C
Connection in acc. with standardIEC 60947-7-1
Nominal current IN20 A
Maximum load current24 A (with 4 mm² conductor cross section)
Nominal voltage UN500 V (the operating voltage is determined by the selected LED version)
Open side panelYes
Shock protection test specificationDIN EN 50274 (VDE 0660-514):2002-11
Back of the hand protectionguaranteed
Finger protectionguaranteed
Result of surge voltage testTest passed
Surge voltage test setpoint4.8 kV
Result of power-frequency withstand voltage testTest passed
Power frequency withstand voltage setpoint1.5 kV
Checking the mechanical stability of terminal points (5 x conductor connection)Test passed
Result of bending testTest passed
Bending test rotation speed10 rpm
Bending test turns135
Bending test conductor cross section/weight0.14 mm² / 0.2 kg
2.5 mm² / 0.7 kg
4 mm² / 0.9 kg
Tensile test resultTest passed
Conductor cross section tensile test0.14 mm²
Tractive force setpoint10 N
Conductor cross section tensile test2.5 mm²
Tractive force setpoint50 N
Conductor cross section tensile test4 mm²
Tractive force setpoint60 N
Result of tight fit on supportTest passed
Tight fit on carrierNS 35
Setpoint1 N
Result of voltage-drop testTest passed
Requirements, voltage drop≤ 3.2 mV
Result of temperature-rise testTest passed
Short circuit stability resultTest passed
Conductor cross section short circuit testing2.5 mm²
Short-time current0.3 kA
Conductor cross section short circuit testing4 mm²
Short-time current0.48 kA
Result of aging testTest passed
Ageing test for screwless modular terminal block temperature cycles192
Result of thermal testTest passed
Proof of thermal characteristics (needle flame) effective duration30 s
Oscillation, broadband noise test resultTest passed
Test specification, oscillation, broadband noiseDIN EN 50155 (VDE 0115-200):2008-03
Test spectrumService life test category 1, class B, body mounted
Test frequencyf1= 5 Hz to f2= 150 Hz
ASD level1.857 (m/s2)2/Hz
Acceleration0,8 g
Test duration per axis5 h
Test directionsX-, Y- and Z-axis
Shock test resultTest passed
Test specification, shock testDIN EN 50155 (VDE 0115-200):2008-03
Shock formHalf-sine
Acceleration5 g
Shock duration30 ms
Number of shocks per direction3
Test directionsX-, Y- and Z-axis (pos. and neg.)
Relative insulation material temperature index (Elec.; UL 746 B)130 °C
Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21))130 °C
Static insulating material application in cold-60 °C
Behavior in fire for rail vehicles (DIN 5510-2)Test passed
Flame test method (DIN EN 60695-11-10)V0
Oxygen index (DIN EN ISO 4589-2)>32 %
NF F16-101, NF F10-102 Class I2
NF F16-101, NF F10-102 Class F2
Surface flammability NFPA 130 (ASTM E 162)passed
Specific optical density of smoke NFPA 130 (ASTM E 662)passed
Smoke gas toxicity NFPA 130 (SMP 800C)passed
Calorimetric heat release NFPA 130 (ASTM E 1354)28 MJ/kg
Fire protection for rail vehicles (DIN EN 45545-2) R22HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R23HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R24HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R26HL 1 - HL 3

Dimensions

Width5.2 mm
Length68 mm
Height NS 35/7,547.5 mm
Height NS 35/1555 mm

Connection data

Connection methodPush-in connection
Conductor cross section solid min.0.14 mm²
Conductor cross section solid max.4 mm²
Conductor cross section flexible min.0.14 mm²
Conductor cross section flexible max.2.5 mm²
Conductor cross section AWG min.26
Conductor cross section AWG max.12
Conductor cross section flexible, with ferrule without plastic sleeve min.0.14 mm²
Conductor cross section flexible, with ferrule without plastic sleeve max.2.5 mm²
Conductor cross section flexible, with ferrule with plastic sleeve min.0.14 mm²
Conductor cross section flexible, with ferrule with plastic sleeve max.2.5 mm²
2 conductors with same cross section, stranded, TWIN ferrules with plastic sleeve, max.0.5 mm²
Stripping length8 mm ... 10 mm
Internal cylindrical gageA3
Stripping length8 mm ... 10 mm

Standards and Regulations

Connection in acc. with standardCSA
IEC 60947-7-1
Flammability rating according to UL 94V0
Fire protection for rail vehicles (DIN EN 45545-2) R22HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R23HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R24HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R26HL 1 - HL 3

Environmental Product Compliance

China RoHSEnvironmentally friendly use period: unlimited = EFUP-e
No hazardous substances above threshold values

Classifications


Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.