View larger
IB IL AO 2/U/BP-PAC 2861467 PHOENIX CONTACT Inline terminal
IB IL AO 2/U/BP-PAC
2861467
PHOENIX CONTACT
1 Pcs.
Automation > Fieldbus, decentr. periphery - analogue I/O module
I/O
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
An Inline terminal from Phoenix Contact, identified by part number IB IL AO 2/U/BP-PAC 2861467, is utilized in industrial automation networks to process modular input and output signals for decentralized machine control. These terminal blocks integrate into backplane systems to route data seamlessly across a facility. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Supply voltage DC (EF007534): 19.2 V
- Voltage type (supply voltage) (EF002991): DC
- Input, current (EF003204): No
- Input, voltage (EF003205): No
- Input, resistor (EF003206): No
- Input, resistance thermometer (EF003207): No
- Input, thermocouple (EF003208): No
- Input signal, configurable (EF003209): No
- Output, current (EF003212): No
- Output, voltage (EF003213): Yes
- Output signal configurable (EF003214): Yes
- Number of analogue inputs (EF001994): 0
- Number of analogue outputs (EF001995): 2
- Analogue inputs configurable (EF008518): No
- Analogue outputs configurable (EF008519): Yes
- Number of HW-interfaces industrial Ethernet (EF003020): 0
More info
▲Key Commercial Data
| Orderkey | 2861467 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 167 (C-6-2017) |
| GTIN | 4017918894382 |
| Weight per Piece (excluding packing) | 48.000 g |
| Custom tariff number | 85389091 |
| Country of origin | DE (Germany) |
Note
| Utilization restriction | EMC: class A product, see manufacturer's declaration in the download area |
|---|
Ambient conditions
| Ambient temperature (operation) | -25 °C ... 55 °C |
|---|---|
| Ambient temperature (storage/transport) | -25 °C ... 85 °C |
| Permissible humidity (operation) | 10 % ... 95 % (non-condensing) |
| Permissible humidity (storage/transport) | 10 % ... 95 % (non-condensing) |
| Air pressure (operation) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Air pressure (storage/transport) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Degree of protection | IP20 |
General
| Mounting type | DIN rail |
|---|---|
| Net weight | 48 g |
| Note on weight specifications | with connector |
| Diagnostics messages | Failure of or insufficient communications power ULI/O error message sent to the bus coupler |
Interfaces
| Designation | Inline local bus |
|---|---|
| No. of channels | 2 |
| Connection method | Inline data jumper |
| Transmission speed | 500 kbps |
| Transmission physics | Copper |
Inline potentials
| Designation | Communications power (UL) |
|---|---|
| Supply voltage | 7.5 V DC (via voltage jumper) |
| Current consumption | typ. 33 mA |
| max. 40 mA | |
| Designation | Supply of analog modules (UANA) |
| Supply voltage | 24 V DC (via voltage jumper) |
| Supply voltage range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
| Current consumption | typ. 18 mA (No-load) |
| max. 28 mA (No-load) | |
| typ. 25 mA (Full load (RL= 2 kΩ)) | |
| max. 35 mA (Full load (RL= 2 kΩ)) | |
| Power consumption | typ. 0.68 W (No-load) |
Analog outputs
| Number of outputs | 2 |
|---|---|
| Connection technology | 2-wire |
| Note regarding the connection technology | shielded |
| Output name | Analog outputs |
| D/A conversion time | < 100 ns |
| Type of protection | Transient protection of outputs |
| Data formats | IB IL, IB ST |
| Representation of output values | 16 bits (15 bits + sign) |
| DAC resolution | 13 Bit |
| Process data update | < 1 ms |
| Voltage output signal | 0 V ... 10 V |
| -10 V ... 10 V | |
| Load/output load voltage output | > 2 kΩ |
| Precision | typ. 0.02 % (of output range final value) |
| Permissible cable length | max. 500 m (The specifications refer to nominal operation after complying with installation instructions. The specifications refer to the following reference cable type: Shielded power station cable: LiYCY; 2 x 2 x 0,5 mm²; VDE0812) |
Electrical isolation
| Test section | 7.5 V supply (bus logic), 24 V supply UANA/ I/O 500 V AC 50 Hz 1 min. |
|---|---|
| 7.5 V supply (bus logic), 24 V supply UANA/functional earth ground 500 V AC 50 Hz 1 min. | |
| 24 V supply (I/O) / functional earth ground 500 V AC 50 Hz 1 min. |
Standards and Regulations
| Connection in acc. with standard | CUL |
|---|---|
| Protection class | III, IEC 61140, EN 61140, VDE 0140-1 |
Environmental Product Compliance
| China RoHS | Environmentally friendly use period: unlimited = EFUP-e |
|---|---|
| No hazardous substances above threshold values |