Request QuoteProduct Overview
Phoenix Contact IB IL 24 DI 8/T2-PAC Inline terminal components function as modular input interfaces designed to collect discrete signals within automated control architectures. This specific unit processes multiple digital input channels to relay field-level sensor data directly back to the main processing system. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Supply voltage DC (EF007534): 19.2 V
- Voltage type (supply voltage) (EF002991): DC
- Number of digital inputs (EF001992): 8
- Number of digital outputs (EF001993): 0
- Digital inputs configurable (EF008516): No
- Digital outputs configurable (EF008520): No
- Input current at signal 1 (EF001428): 0.006 mA
- Permitted voltage at input (EF007554): -3 V
- Type of voltage (input voltage) (EF003033): DC
- Short-circuit protection, outputs available (EF003203): No
- Number of HW-interfaces industrial Ethernet (EF003020): 0
- Number of interfaces PROFINET (EF006932): 0
- Number of HW-interfaces RS-232 (EF003021): 0
- Number of HW-interfaces RS-422 (EF003022): 0
- Number of HW-interfaces RS-485 (EF003023): 0
- Number of HW-interfaces serial TTY (EF003024): 0
More info
▲Key Commercial Data
| Orderkey | 2862204 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 149 (C-6-2017) |
| GTIN | 4017918894689 |
| Weight per Piece (excluding packing) | 118.000 g |
| Custom tariff number | 85389091 |
| Country of origin | DE (Germany) |
Ambient conditions
| Ambient temperature (operation) | -25 °C ... 55 °C |
|---|---|
| Ambient temperature (storage/transport) | -25 °C ... 85 °C |
| Permissible humidity (operation) | 10 % ... 95 % (according to DIN EN 61131-2) |
| Permissible humidity (storage/transport) | 10 % ... 95 % (according to DIN EN 61131-2) |
| Air pressure (operation) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Air pressure (storage/transport) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Degree of protection | IP20 |
Interfaces
| Designation | Inline local bus |
|---|---|
| No. of channels | 2 |
| Connection method | Inline data jumper |
| Transmission speed | 500 kbps |
Inline potentials
| Designation | Communications power (UL) |
|---|---|
| Supply voltage | 7.5 V DC (via voltage jumper) |
| Current consumption | max. 50 mA |
| Designation | Segment circuit supply (US) |
| Supply voltage | 24 V DC (via voltage jumper) |
| Supply voltage range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
| Current consumption | max. 2 A |
| 0 A |
Digital inputs
| Input name | Digital inputs |
|---|---|
| Description of the input | IEC 61131-2 Type 2 |
| Connection method | Spring-cage connection |
| Connection technology | 4-wire |
| Number of inputs | 8 |
| Typical response time | < 1 ms |
| Type of protection | Short-circuit and overload protection |
| Input voltage | 24 V DC |
| Input voltage range "0" signal | -3 V DC ... 5 V DC |
| Input voltage range "1" signal | 15 V DC ... 30 V DC |
| Nominal input current at UIN | min. 6 mA (at nominal voltage) |
Electrical isolation
| Test section | 5 V supply, incoming remote bus/7.5 V supply (bus logics) 500 V AC 50 Hz 1 min. |
|---|---|
| 5 V supply, outgoing remote bus/7.5 V supply (bus logics) 500 V AC 50 Hz 1 min. | |
| 7.5 V supply (bus logics)/24 V supply (I/O) 500 V AC 50 Hz 1 min. | |
| 24 V supply (I/O) / functional earth ground 500 V AC 50 Hz 1 min. |
Standards and Regulations
| Connection in acc. with standard | CUL |
|---|---|
| Protection class | III, IEC 61140, EN 61140, VDE 0140-1 |
Environmental Product Compliance
| China RoHS | Environmentally friendly use period: unlimited = EFUP-e |
|---|---|
| No hazardous substances above threshold values |