View larger
HC-D 64-A-TWIN-PEL-M 1580192 PHOENIX CONTACT Terminal adapter
HC-D 64-A-TWIN-PEL-M
1580192
PHOENIX CONTACT
1 Pcs.
Connectors > Contact insert for rectangular connectors
Industrial plug-in connectors/interfaces
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
The Phoenix Contact HC-D 64-A-TWIN-PEL-M terminal adapter provides a high-capacity branching and termination interface for extensive control wiring arrays. Industrial terminal adapters help organize massive wire counts, allowing clean transitions between internal cabinet runs and heavy plug connectors.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Contact type (EF001587): Pin
- Number of poles (EF001391): 64
- Ambient temperature (EF002386): 125 °C
- Operating temperature (EF002393): -40 °C
- Rated voltage (EF000228): 250 V
- Over voltage category (EF006785): III
- With wire protection (EF000550): No
- Connectable conductor cross section multi-wired (EF007343): 0.5 mm²
- With protective conductor (EF007468): Yes
- Width (EF000008): 34 mm
- Height (EF000040): 139.3 mm
- Depth (EF000049): 110 mm
More info
▲Key Commercial Data
| Orderkey | 1580192 |
|---|---|
| Packing unit | 4 pc |
| Note | Made to Order (non-returnable) |
| Catalog page | Page 531 (C-2-2017) |
| GTIN | 4046356154529 |
| Weight per Piece (excluding packing) | 441.380 g |
| Custom tariff number | 85366990 |
| Country of origin | PL (Poland) |
Electrical characteristics
| Number of positions | 64 |
|---|---|
| Rated voltage (III/3) | 250 V |
| Rated surge voltage | 6 kV |
| Rated current | 10 A |
Mechanical characteristics
| Type | B24 |
|---|---|
| Connection method | Push-in connection |
| Stripping length of the individual wire | 10 mm |
| Conductor cross section | 0.5 mm² ... 2.5 mm² |
| Connection cross section AWG | 22 ... 12 |
General
| Note | For HEAVYCON-ADVANCE mounting flange and HEAVYCON panel mounting base of B24 type |
|---|---|
| Connectors may be operated only when there is no load/voltage. | |
| Contact material | Copper alloy |
| Contact surface material | Ag |
| Contact carrier material | PA |
| Standards/regulations | PA: Fire protection in rail vehicles - requirement sets R22 and R23 acc. to DIN EN 45545-2 (Risk level HL1 - HL2) |
| PA: Fire protection in rail vehicles - requirement set R24 acc. to DIN EN 45545-2 (Risk level HL1 - HL3) | |
| Degree of pollution | 3 |
| Overvoltage category | III |
| Flammability rating according to UL 94 | V0 |
| Assembly instructions | To ensure correct use, installation in housing with IP54 protection or better is required |
| Not for HC-EVO panel mounting bases | |
| Not for HC-EVO panel mounting bases | |
| Installation instructions | Connectors may be plugged in only when there is no load/voltage. Not for HC-B 24-AMQ-EMV housings |
Standards and Regulations
| Constructional and testing regulations | DIN EN 61984 |
|---|---|
| DIN EN 60664 | |
| IEC 60352 | |
| Flammability rating according to UL 94 | V0 |
Environmental Product Compliance
| REACh SVHC | Lead 7439-92-1 |
|---|---|
| China RoHS | Environmentally Friendly Use Period = 50 |
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |