View larger
MACX MCR-T-UI-UP-SP 2811860 PHOENIX CONTACT Temperature measuring transducer
MACX MCR-T-UI-UP-SP
2811860
PHOENIX CONTACT
1 Pcs.
Automation > Temperature transformer
INTERFACE Components (IF)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
The MACX MCR-T-UI-UP-SP 2811860 PHOENIX CONTACT Temperature measuring transducer functions as a core interface module for converting thermal signals into standardized electrical outputs for control panels. Industrial setups utilize temperature transducers to ensure accurate thermal management, protecting sensitive equipment and maintaining stable process conditions.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Measuring range (EF001836): -250 °C
- Analogue output 4 mA ... 20 mA (EF006810): Yes
- With switching output (EF005225): Yes
- EMC-version (EF001062): Yes
- Ambient temperature (EF002386): 65 °C
- Weight (EF000167): 0.15 kg
More info
▲Key Commercial Data
| Orderkey | 2811860 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 128 (C-5-2017) |
| GTIN | 4046356629119 |
| Weight per Piece (excluding packing) | 150.000 g |
| Custom tariff number | 85437090 |
| Country of origin | DE (Germany) |
Ambient conditions
| Ambient temperature (operation) | -20 °C ... 65 °C |
|---|---|
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Maximum altitude | ≤ 2000 m |
| Permissible humidity (operation) | typ. 5 % ... 95 % (non-condensing) |
| Noise immunity | EN 61000-6-2 When being exposed to interference, there may be minimal deviations. |
Input data
| Sensor types (RTD) that can be used | Pt, Ni, Cu sensors: 2, 3, 4-wire |
|---|---|
| Sensor types that can be used (TC) | B, E, J, K, N, R, S, T, L, U, CA, DA, A1G, A2G, A3G, MG, LG |
| Temperature measuring range | -250 °C ... 2500 °C (Range depending on the sensor type) |
| Input signal range | 0 Ω ... 50 kΩ |
| Potentiometer resistance range | 0 Ω ... 50 kΩ |
| Input signal range | -1000 mV ... 1000 mV |
Output data
| Configurable/programmable | Yes |
|---|---|
| Max. voltage output signal | ± 11 V |
| Current output signal | 4 mA ... 20 mA (in the case of SIL; further free configuration without SIL) |
| Max. current output signal | 22 mA |
| Load/output load voltage output | ≥ 10 kΩ |
| Load/output load current output | ≤ 600 Ω (at 20 mA) |
| Behavior in the event of a sensor error | according to NE 43 or freely configurable |
| Output name | Relay output |
| Configurable/programmable | no |
| Contact type | 1 PDT |
| Contact material | AgSnO2, hard gold-plated |
| Maximum switching voltage | 30 V AC (30 V DC) |
| Maximum inrush current | 0.5 A (30 V AC) |
| 1 A (30 V DC) |
Power supply
| Supply voltage range | 24 V ... 230 V AC/DC (-20 %/+10 %, 50/60 Hz) |
|---|---|
| Power consumption | < 1.5 W |
Connection data
| Conductor cross section solid min. | 0.2 mm² |
|---|---|
| Conductor cross section solid max. | 1.5 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 1.5 mm² |
| Conductor cross section AWG min. | 24 |
| Conductor cross section AWG max. | 16 |
| Stripping length | 8 mm |
| Connection method | Push-in connection |
General
| Maximum temperature coefficient | 0.01 %/K |
|---|---|
| Flammability rating according to UL 94 | V0 |
| Degree of pollution | 2 |
| Overvoltage category | II |
| Electromagnetic compatibility | Conformance with EMC directive |
| Housing material | PA 6.6-FR |
| Color | gray |
| Designation | Input/output/power supply |
| Electrical isolation | 300 Vrms(Rated insulation voltage (overvoltage category II; degree of pollution 2, safe isolation as per EN 61010-1)) |
| 2.5 kV (50 Hz, 1 min., test voltage) | |
| Designation | Input/output |
| Electrical isolation | 375 V (Peak value in accordance with EN 60079-11) |
| Designation | Input/power supply |
| Electrical isolation | 375 V (Peak value in accordance with EN 60079-11) |
| Designation | Input/switching output |
| Electrical isolation | 375 V (Peak value in accordance with EN 60079-11) |
| Conformance | CE-compliant |
| ATEX | II 3 G Ex nA nC ic IIC T4 Gc X |
| IECEx | Ex nA nC ic IIC T4 Gc X |
| UL, USA/Canada | UL 508 Listed |
| Class I, Div. 2, Groups A, B, C, D T6 | |
| Class I, Zone 2, Group IIC T6 | |
| SIL | 2 |
Standards and Regulations
| Electromagnetic compatibility | Conformance with EMC directive |
|---|---|
| Electrical isolation | 4-way, between input/output/power supply/switching output |
| Flammability rating according to UL 94 | V0 |
| Conformance | CE-compliant |
| ATEX | II 3 G Ex nA nC ic IIC T4 Gc X |
| IECEx | Ex nA nC ic IIC T4 Gc X |
| UL, USA/Canada | UL 508 Listed |
| Class I, Div. 2, Groups A, B, C, D T6 | |
| Class I, Zone 2, Group IIC T6 | |
| DNV GL-Temperature | B |
| DNV GL-Humidity | B |
| DNV GL-Vibration | A |
| DNV GL-EMC | A |
| DNV GL-Enclosure | Required protection according to the Rules shall be provided upon installation on board |
Environmental Product Compliance
| REACh SVHC | Lead 7439-92-1 |
|---|---|
| China RoHS | Environmentally Friendly Use Period = 50 |
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |