PHOENIX CONTACT TC-XC96-DI32-2EX-PR-HIMAX01 TC-XC96-DI32-2EX-PR-HIMAX01 2908749 PHOENIX CONTACT Termination Carrier for connecting 32 MACX Analog Ex i s.. View larger
Images are for illustrative purposes only. Please refer to data sheet for details

TC-XC96-DI32-2EX-PR-HIMAX01 2908749 PHOENIX CONTACT Termination Carrier for connecting 32 MACX Analog Ex i s..

TC-XC96-DI32-2EX-PR-HIMAX01

2908749

PHOENIX CONTACT

1 Pcs.

Termination Carrier for connecting 32 MACX Analog Ex i signal conditioners to digital input cards of the HIMA HIMax controller, via one C96 connector, 96-pos. Suitable for the HIMax X-DI 32 01 card Termination Carrier for the connection of 32 MACX Analog Ex-i separation amplifiers to digital input cards of the HIMA-HIMax control system, via a C96, 96-pole connector. Suitable for HIMax X-DI 32 01 card

Automation > Interface module
INTERFACE Components (IF)

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

The TC-XC96-DI32-2EX-PR-HIMAX01 2908749 PHOENIX CONTACT Termination Carrier is a specialized hardware component engineered for connecting signal circuits in complex control and automation architectures. Termination carriers serve as streamlined marshalling interfaces, bridging field-level signals with system-specific I/O cards while maintaining organized cable management and signal integrity. Pricing, availability, and lead time are confirmed per enquiry through an RFQ.

  • Utilization restriction EMC note: EMC: class A product, see manufacturer's declaration in the download area
  • Product type: Module carrier
  • Data management status Article revision: 05
  • Overvoltage category: II
  • Pollution degree: 2
  • Max. permissible current: 1 A (Signal/channel)
  • Nominal voltage U N: < 50 V DC (Per signal/channel)
  • Rated surge voltage: 0.5 kV
  • Supported controller HIMA HIMax Suitable I/O card: X-DI 32 01
  • Supply Designation: Device supply
  • Fuse: 2x 2.5 A Slow-blow (exchangeable)
  • Input voltage: 24 V DC
  • Input voltage range: 19.2 V DC ... 30 V DC
  • Input current: ≤ 2 A
  • Redundant supply: yes, decoupled from diodes
  • Polarization and surge protection: Yes

More info

▲
Technical data

Notes
Notes on operationFor proper use, the specifications of the installation directive (see Downloads) must be observed. For applications or use with third-party products, the specifications, and the safety and warning instructions of the respective third-party manufacturer must also be met.
Utilization restriction
EMC noteEMC: class A product, see manufacturer's declaration in the download area

Product properties
Product typeModule carrier
Data management status
Article revision05
Insulation characteristics: Air clearances and creepage distances
InsulationBasic insulation
Overvoltage categoryII
Pollution degree2

Electrical properties
Max. permissible current1 A (Signal/channel)
Nominal voltage UN< 50 V DC (Per signal/channel)
Air clearances and creepage distances
Rated insulation voltage30 V
Rated surge voltage0.5 kV
Supported controller HIMA HIMax
Suitable I/O cardX-DI 32 01
Supply
DesignationDevice supply
Fuse2x 2.5 A Slow-blow (exchangeable)
Input voltage24 V DC
Input voltage range19.2 V DC ... 30 V DC
Input current≤ 2 A
Redundant supplyyes, decoupled from diodes
Polarization and surge protectionYes
Output nameSwitching output
Contact switching type1 N/C contact (alarm = open)
Maximum switching voltage30 V DC (2 A)

Connection data
Power supply
Connection methodScrew connection
Stripping length7 mm
Number of connections1
Number of positions6
Conductor cross section rigid0.75 mm² ... 2.5 mm²
Conductor cross section flexible0.75 mm² ... 2.5 mm²
Conductor cross section AWG18 ... 14
Controller level
Connection in acc. with standardIEC 60603-2
Connection methodPin strip
TypeC
Number of connections1
Number of positions96

Signaling
Status display2x green LEDs (PWR1 and PWR2)

Dimensions
Width242 mm
Height170 mm
Depth159.5 mm

Environmental and real-life conditions
Ambient conditions
Degree of protectionIP20
Ambient temperature (operation)-20 °C ... 60 °C
Ambient temperature (storage/transport)-40 °C ... 80 °C
Altitude≤ 2000 m
Permissible humidity (operation)5 % ... 95 % (non-condensing)
Shock15g, according to IEC 60068-2-27
Vibration (operation)2g, according to IEC 60068-2-6

Approvals
ATEX
Identification II 3 G Ex ec IIC T4 Gc X
UKCA Ex (UKEX)
Identification II 3 G Ex ec IIC T4 Gc
CertificatePxCIF21UKEX2908750X
UL, USA/Canada
IdentificationUL 61010 Listed
Class I, Div. 2, Groups A, B, C, D T4
Class I, Zone 2, Group IIC

Standards and regulations
Air clearances and creepage distances
Standards/regulationsEN 60664-1
Directive 2014/35/EU (EMV)
Standards/regulationsEN 6100-6-2
EN 6100-6-4
Directive 2014/34/EU (ATEX)
Standards/regulationsEN 60079-0
EN 60079-7
EN 60079-11

Mounting
Mounting typeDIN rail mounting
Assembly noteNo end clamp
Mounting positionvertical, horizontal

Product Datasheet