View larger
TAE-TRAB FM-NFN-AP 2749628 PHOENIX CONTACT Surge protection device
TAE-TRAB FM-NFN-AP
2749628
PHOENIX CONTACT
1 Pcs.
Automation > Surge protection device for data networks/MCR-technology
Trabtech (TT)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
The Phoenix Contact TAE-TRAB FM-NFN-AP surge protection device safeguards telecommunication and data networks from damaging voltage transients. These specialized barriers are widely integrated into communication infrastructure to preserve signal integrity and hardware lifespan. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Nominal voltage AC (EF008798): 60 V
More info
▲Key Commercial Data
| Orderkey | 2749628 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 165 (C-4-2017) |
| GTIN | 4017918108199 |
| Weight per Piece (excluding packing) | 79.600 g |
| Custom tariff number | 85363010 |
| Country of origin | DE (Germany) |
General
| Housing material | ABS |
|---|---|
| Color | cream white |
| Standards for cearances and creepage distances | VDE 0110-1 |
| IEC 60664-1 | |
| For country-specific use in | D |
| Mounting type | Surface/Wall mounting |
| Type | Socket for surface mounting |
| Direction of action | Line-Line & Line-Earth Ground |
Protective circuit
| IEC test classification | B2 |
|---|---|
| C1 | |
| C2 | |
| C3 | |
| D1 | |
| VDE requirement class | B2 |
| C1 | |
| C2 | |
| C3 | |
| D1 | |
| Nominal voltage UN | 60 V DC |
| Maximum continuous voltage UC | 185 V DC |
| Rated current | 450 mA (≤ 40°C) |
| Operating effective current ICat UC | ≤ 10 µA |
| Residual current IPE | ≤ 6 µA |
| Nominal discharge current In(8/20) µs (line-line) | 5 kA |
| Nominal discharge current In(8/20) µs (line-earth) | 5 kA |
| Total discharge current Itotal(8/20) µs | 10 kA |
| Total discharge current Itotal(10/350) µs | 5 kA |
| Max. discharge current Imax(8/20) µs maximum (line-line) | 5 kA |
| Max. discharge current Imax(8/20) µs maximum (line-earth) | 5 kA |
| Nominal pulse current Ian (10/1000) µs (line-line) | 100 A |
| Nominal pulse current Ian (10/1000) µs (line-earth) | 100 A |
| Nominal pulse current Ian (10/700) µs (line-line) | 150 A |
| Nominal pulse current Ian (10/700) µs (line-earth) | 150 A |
| Output voltage limitation at 1 kV/µs (line-line) spike | ≤ 250 V |
| Output voltage limitation at 1 kV/µs (line-earth) spike | ≤ 450 V |
| Output voltage limitation at 1 kV/µs (line-line) static | ≤ 250 V |
| Output voltage limitation at 1 kV/µs (line-earth) static | ≤ 450 V |
| Voltage protection level Up(line-line) | ≤ 250 V (C2 - 10 kV / 5 kA) |
| ≤ 250 V (C1 - 1 kV/500 A) | |
| ≤ 250 V (B2 - 4 kV / 100 A) | |
| Voltage protection level Up(line-earth) | ≤ 500 V (C2 - 10 kV / 5 kA) |
| ≤ 450 V (C1 - 1 kV/500 A) | |
| ≤ 400 V (B2 - 4 kV / 100 A) | |
| Response time tA(line-line) | ≤ 1 ns |
| Response time tA(line-earth) | ≤ 100 ns |
| Input attenuation aE, sym. | 0.3 dB (≤ 1 MHz / 150 Ω) |
| 0.3 dB (≤ 400 kHz / 600 Ω) | |
| Input attenuation aE, asym. | 0.3 dB (≤ 400 kHz / 600 Ω) |
| Cut-off frequency fg (3 dB), sym. in 150 Ohm system | typ. 8 MHz |
| Cut-off frequency fg (3 dB), sym. in 600 Ohm system | typ. 2 MHz |
| Capacity (line-line) | typ. 200 pF (f = 1 MHz / VR = 0 V) |
| Capacity (line-earth) | typ. 15 pF (f = 1 MHz / VR = 0 V) |
| Resistance in series | 2.2 Ω 10 % |
| Short-circuit current self-quenching | 150 mA |
| Surge protection fault message | none |
| Impulse durability (line-line) | C2 - 10 kV/5 kA |
| C1 - 1 kV/500 A | |
| B2 - 4 kV/100 A | |
| Impulse durability (line-earth) | C2 - 10 kV/5 kA |
| C1 - 1 kV/500 A | |
| B2 - 4 kV/100 A | |
| D1 - 2.5 kA | |
| Alternating current carrying capacity (line-earth) | 5 A - 1 s |
Connection data
| Connection method | Screw connection & TAE 6 |
|---|---|
| Connection method IN | Screw terminal blocks |
| Connection method OUT | 3x TAE-NFN |
| Connection technology | Screw connection |
| Screw thread | M3 |
| Tightening torque | 0.5 Nm |
| Stripping length | 6 mm |
| Conductor cross section flexible | 0.14 mm² ... 1.5 mm² |
| Conductor cross section solid | 0.14 mm² ... 1.5 mm² |
| Conductor cross section AWG | 26 ... 16 |
Connection, equipotential bonding
| Connection method | Screw terminal block |
|---|---|
| Stripping length | 6 mm |
| Tightening torque, min | 0.5 Nm |
| Conductor cross section flexible min. | 0.14 mm² |
| Conductor cross section flexible max. | 1.5 mm² |
| Conductor cross section solid min. | 0.14 mm² |
| Conductor cross section solid max. | 1.5 mm² |
| Conductor cross section AWG min. | 26 |
| Conductor cross section AWG max. | 16 |
Standards and Regulations
| Standards/regulations | IEC 61643-21 |
|---|---|
| Standards/specifications | DIN EN 61643-21 2002 |
| IEC 61643-21 2000 |