View larger
TT-SLKK5/ 24DC 2794903 PHOENIX CONTACT Surge protection device
TT-SLKK5/ 24DC
2794903
PHOENIX CONTACT
1 Pcs.
Automation > Surge protection device for data networks/MCR-technology
Trabtech (TT)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
The Phoenix Contact TT-SLKK5/ 24DC surge protection device is a specialized component designed to safeguard sensitive industrial electrical equipment from transient voltage spikes and surges. Units of this type are typically integrated into control cabinets and signal circuits to divert harmful electrical surges safely to ground, protecting downstream instruments from damage. Pricing, availability, and lead time are confirmed per enquiry through an RFQ.
- Orderkey: 2794903
- Packing unit: 50 pc
- Catalog page: Page 99 (C-6-2013)
- GTIN: 4017918072971
- Weight per Piece (excluding packing): 21.940 g
- Custom tariff number: 85363030
- Country of origin: DE (Germany)
- Height: 69.5 mm
- Width: 6.2 mm
- Length: 66.5 mm
- Ambient temperature (operation): -40 °C ... 85 °C
- Degree of protection: IP20
- Housing material: PA
- Flammability rating according to UL 94: V-2
- Color: black
- Mounting type: DIN rail: 35 mm
More info
▲Key Commercial Data
| Orderkey | 2794903 |
|---|---|
| Packing unit | 50 pc |
| Catalog page | Page 99 (C-6-2013) |
| GTIN | 4017918072971 |
| Weight per Piece (excluding packing) | 21.940 g |
| Custom tariff number | 85363030 |
| Country of origin | DE (Germany) |
General
| Housing material | PA |
|---|---|
| Flammability rating according to UL 94 | V-2 |
| Color | black |
| Mounting type | DIN rail: 35 mm |
| Type | Single-level terminal block – separate PE connection |
| Direction of action | Line-Earth Ground |
Protective circuit
| IEC test classification | C1 |
|---|---|
| C2 | |
| C3 | |
| VDE requirement class | C1 |
| C2 | |
| C3 | |
| Nominal voltage UN | 24 V DC |
| Maximum continuous voltage UC | 31 V DC |
| 25 V AC | |
| Rated current | 32 A (50 °C) |
| Operating effective current ICat UC | ≤ 30 µA |
| Residual current IPE | ≤ 30 µA |
| Nominal discharge current In(8/20) µs (line-earth) | 700 A |
| Total discharge current Itotal(8/20) µs | 2 kA |
| Max. discharge current Imax(8/20) µs maximum (line-earth) | 2 kA |
| Nominal pulse current Ian (10/1000) µs (line-earth) | 70 A |
| Output voltage limitation at 1 kV/µs (line-earth) spike | ≤ 90 V |
| Output voltage limitation at 1 kV/µs (line-earth) static | ≤ 80 V |
| Residual voltage at In(line-earth) | ≤ 125 V |
| Response time tA(line-earth) | ≤ 25 ns |
| Cut-off frequency fg (3 dB), asym. (PE) in 150 Ohm system | typ. 300 kHz |
| Surge protection fault message | none |
Connection data
| Connection method | Screw connection |
|---|---|
| Connection method IN | Screw terminal blocks |
| Connection method OUT | Screw terminal blocks |
| Screw thread | M3 |
| Tightening torque | 0.8 Nm |
| Stripping length | 8 mm |
| Conductor cross section flexible | 0.2 mm² ... 4 mm² |
| Conductor cross section solid | 0.2 mm² ... 4 mm² |
| Conductor cross section AWG | 24 ... 12 |
Environmental Product Compliance
| REACh SVHC | 4-Nonylphenol, ethoxylated |
|---|---|
| Lead 7439-92-1 | |
| China RoHS | Environmentally Friendly Use Period = 50 |
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |