View larger
VAL-MS 320/3+1 2859178 PHOENIX CONTACT Type 2 surge arrester
VAL-MS 320/3+1
2859178
PHOENIX CONTACT
1 Pcs.
Automation > Surge protection device for power supply systems
Trabtech (TT)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Engineered by Phoenix Contact under part number 2859178, this type 2 surge arrester is designed to protect industrial electrical networks from transient overvoltages and switching surges. Units of this classification are typically deployed in low-voltage distribution switchboards to preserve operational continuity.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- System configuration DC: No
- System configuration IT: No
- System configuration TN: No
- System configuration TN-C: No
- System configuration TN-C-S: No
- System configuration TN-S: Yes
- System configuration TT: No
- System configuration other: No
- Nominal discharge surge current (8/20): 20 kA
- Max. discharge surge current (8/20): 40 kA
- Max. continuous voltage AC: 335 V
- Voltage protection level: 1.9 kV
- Voltage protection level L-N: 1.5 kV
- Voltage protection level N-PE: 1.5 kV
- Short-circuit breaking capacity (Isccr): 25 kA
- Integrated backup fuse: Yes
More info
▲Key Commercial Data
| Orderkey | 2859178 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 52 (C-4-2017) |
| GTIN | 4017918911225 |
| Weight per Piece (excluding packing) | 386.120 g |
| Custom tariff number | 85363030 |
| Country of origin | DE (Germany) |
Ambient conditions
| Degree of protection | IP20 (only when all terminal points are used) |
|---|---|
| Ambient temperature (operation) | -40 °C ... 80 °C |
| Ambient temperature (storage/transport) | -40 °C ... 80 °C |
| Altitude | ≤ 2000 m (amsl (above mean sea level)) |
| Permissible humidity (operation) | 5 % ... 95 % |
| Shock (operation) | 25g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z) |
| Vibration (operation) | 5g (10 ... 500 Hz / 2.5 h / X, Y, Z) |
General
| IEC test classification | II |
|---|---|
| T2 | |
| EN type | T2 |
| IEC power supply system | TN-S |
| TT | |
| Mode of protection | L-N |
| L-PE | |
| N-PE | |
| Mounting type | DIN rail: 35 mm |
| Color | jet black RAL 9005 |
| Housing material | PA 6.6 |
| PBT | |
| Degree of pollution | 2 |
| Flammability rating according to UL 94 | V-0 |
| Type | DIN rail module, two-section, divisible |
| Number of positions | 4 |
| Surge protection fault message | optical |
Protective circuit
| Nominal voltage UN | 240/415 V AC (TN-S) |
|---|---|
| 240/415 V AC (TT) | |
| Nominal frequency fN | 50 Hz (60 Hz) |
| Maximum continuous operating voltage UC(L-N) | 335 V AC |
| Maximum continuous operating voltage UC(L-PE) | 335 V AC |
| Maximum continuous voltage UC(N-PE) | 260 V AC |
| Rated load current IL | 80 A |
| Residual current IPE | ≤ 5 µA |
| Standby power consumption PC | ≤ 450 mVA |
| Nominal discharge current In(8/20) µs | 20 kA |
| Maximum discharge current Imax(8/20) µs | 40 kA |
| Follow current interrupt rating Ifi(N-PE) | 100 A |
| Short-circuit current rating ISCCR | 25 kA |
| Voltage protection level Up(L-N) | ≤ 1.5 kV |
| Voltage protection level Up(L-PE) | ≤ 1.9 kV |
| Voltage protection level Up(N-PE) | ≤ 1.5 kV |
| Residual voltage Ures(L-N) | ≤ 1.5 kV (at In) |
| ≤ 1.3 kV (at 10 kA) | |
| ≤ 1.2 kV (at 5 kA) | |
| ≤ 1.1 kV (at 3 kA) | |
| Residual voltage Ures(L-PE) | ≤ 1.9 kV (at In) |
| ≤ 1.5 kV (at 10 kA) | |
| ≤ 1.3 kV (at 5 kA) | |
| ≤ 1.2 kV (at 3 kA) | |
| Residual voltage Ures(N-PE) | ≤ 0.4 kV (at In) |
| ≤ 0.25 kV (at 10 kA) | |
| ≤ 0.15 kV (at 5 kA) | |
| ≤ 0.1 kV (at 3 kA) | |
| TOV behavior at UT(L-N) | 415 V AC (5 s / withstand mode) |
| 440 V AC (120 min / safe failure mode) | |
| TOV behavior at UT(N-PE) | 1200 V AC (200 ms / withstand mode) |
| Response time tA(L-N) | ≤ 25 ns |
| Response time tA(L-PE) | ≤ 100 ns |
| Response time tA(N-PE) | ≤ 100 ns |
| Max. backup fuse with V-type through wiring | 80 A (gG) |
| Max. backup fuse with branch wiring | 125 A (gG) |
Connection data
| Connection method | Screw connection |
|---|---|
| Screw thread | M5 |
| Tightening torque | 3 Nm (1,5 mm² ... 16 mm²) |
| 4.5 Nm (25 mm² ... 35 mm²) | |
| Stripping length | 16 mm |
| Conductor cross section flexible | 1.5 mm² ... 25 mm² |
| Conductor cross section solid | 1.5 mm² ... 35 mm² |
| Conductor cross section AWG | 15 ... 2 |
| Connection method | Fork-type cable lug |
| Conductor cross section flexible | 1.5 mm² ... 16 mm² |
UL specifications
| SPD Type | 4CA |
|---|---|
| Maximum continuous operating voltage MCOV (L-L) | 640 V AC |
| Maximum continuous operating voltage MCOV (L-N) | 320 V AC |
| Maximum continuous operating voltage MCOV (L-G) | 320 V AC |
| Maximum continuous operating voltage MCOV (N-G) | 260 V AC |
| Nom. voltage | 240/415 V AC |
| Mode of protection | L-L |
| L-N | |
| L-G | |
| N-G | |
| Power distribution system | Wye |
| Nominal frequency | 50/60 Hz |
| Measured limiting voltage MLV (L-L) | 2900 V |
| Measured limiting voltage MLV (L-N) | 2030 V |
| Measured limiting voltage MLV (L-G) | 2720 V |
| Measured limiting voltage MLV (N-G) | 1370 V |
| Nominal discharge current In(L-L) | 20 kA |
| Nominal discharge current In(L-N) | 20 kA |
| Nominal discharge current In(L-G) | 20 kA |
| Nominal discharge current In(N-G) | 20 kA |