View larger
S-PT-EX(I)-24DC-1/2" 2882572 PHOENIX CONTACT Surge protection device
S-PT-EX(I)-24DC-1/2"
2882572
PHOENIX CONTACT
1 Pcs.
Automation > Combined arrester for data networks/MCR-technology
Trabtech (TT)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Engineered for measurement and control applications, the Phoenix Contact S-PT-EX(I)-24DC-1/2" surge protection device provides critical defense for sensitive instrumentation loops against electrical disturbances. Units of this type protect field devices in industrial networks by safely diverting harmful voltage spikes to ground. Pricing, availability, and lead time are confirmed per enquiry through an RFQ.
- Product type: Surge protection for MCR technology
- Product family: SURGETRAB
- IEC test classification: C1
- Type: Screw-in module
- Number of positions: 3
- Wire pairs per module: 1
- Data management status Article revision: 17
- Insulation characteristics Overvoltage category: III
- Pollution degree: 2
- Nominal voltage U N: 24 V DC
- Connection method: Screw connection
- Screw thread: M3
- Tightening torque: 0.6 Nm
- Conductor cross section flexible: 0.14 mm² ... 1.5 mm²
- Conductor cross section rigid: 0.14 mm² ... 1.5 mm²
- Conductor cross section AWG: 26 ... 16
More info
▲| Notes on operation | When the bridge is disconnected, the shield connection is indirectly connected to the housing or reference potential. |
| Product type | Surge protection for MCR technology |
| Product family | SURGETRAB |
| IEC test classification | C1 |
| C2 | |
| C3 | |
| D1 | |
| Type | Screw-in module |
| Number of positions | 3 |
| Surge protection fault message | none |
| Wire pairs per module | 1 |
| Data management status | |
| Article revision | 17 |
| Insulation characteristics | |
| Overvoltage category | III |
| Pollution degree | 2 |
| Nominal voltage UN | 24 V DC |
| Connection method | Screw connection |
| Screw thread | M3 |
| Tightening torque | 0.6 Nm |
| Conductor cross section flexible | 0.14 mm² ... 1.5 mm² |
| Conductor cross section rigid | 0.14 mm² ... 1.5 mm² |
| Conductor cross section AWG | 26 ... 16 |
| Maximum inner capacitance Ci | 2 nF |
| Max. internal inductance Li | 1 µH |
| Max. input current Ii | 350 mA (T4 / ≤ 50 °C) |
| 350 mA (T5 / ≤ 50 °C) | |
| 350 mA (T6 / ≤ 50 °C) | |
| Max. input voltage Ui | 30 V |
| max. input power Pi | 3.00 W |
| Insulation voltage to ground | 500 V AC |
| Ambient temperature (operation) | -40 °C ... 50 °C |
| Max. surface temperature | 135 °C (T4) |
| 100 °C (T5) | |
| 85 °C (T6) |
| Dimensional drawing | |
| Width | 33.5 mm |
| Height | 33.5 mm |
| Depth | 148 mm |
| Color | Steel/stainless steel color |
| Housing material | Zinc die-cast, surface bronzed and nickel-plated |
| Housing surface material | nickel-plated |
| Mechanical data | |
| Open side panel | No |
| Direction of action | Line-Line & Line-Earth Ground |
| Maximum continuous voltage UC | 30 V DC |
| 21 V AC | |
| Rated current | 350 mA (50 °C) |
| Operating effective current ICat UC | ≤ 10 µA |
| Residual current IPE | ≤ 2 µA |
| Nominal discharge current In(8/20) µs (line-line) | 10 kA |
| Nominal discharge current In(8/20) µs (line-ground) | 10 kA (per path) |
| Nominal discharge current In(8/20) µs (shield-ground) | 10 kA (optional) |
| Pulse discharge current Iimp(10/350) µs | 1 kA |
| Max. discharge current Imax(8/20) µs maximum (line-line) | 10 kA |
| Max. discharge current Imax(8/20) µs maximum (line-earth) | 10 kA (per path) |
| Discharge surge current Imax(8/20) µs maximum (shield-ground) | 10 kA |
| Nominal pulse current Ian (10/1000) µs (line-line) | 30 A |
| Nominal pulse current Ian (10/1000) µs (line-earth) | 100 A (per path) |
| Nominal pulse current Ian (10/1000) µs (shield-ground) | 100 A |
| Output voltage limitation at 1 kV/µs (line-line) spike | ≤ 50 V |
| Output voltage limitation at 1 kV/µs (line-earth) spike | ≤ 1.4 kV (Direct grounding) |
| Output voltage limitation at 1 kV/µs (shield-ground) spike | ≤ 600 V (optional) |
| Output voltage limitation at 1 kV/µs (line-line) static | ≤ 50 V |
| Output voltage limitation at 1 kV/µs (line-earth) static | ≤ 1.4 kV (Direct grounding) |
| Residual voltage at In(conductor-conductor) | ≤ 50 V |
| Residual voltage with Ian (10/1000) µs (line-line) | ≤ 50 V |
| Voltage protection level Up(line-line) | ≤ 50 V (C1 - 0.5 kV / 250 A) |
| ≤ 55 V (C1 - 1 kV / 500 A) | |
| ≤ 55 V (C2 - 2 kV/1 kA) | |
| ≤ 55 V (C2 - 10 kV / 5 kA) | |
| ≤ 50 V (C3 - 10 A) | |
| ≤ 50 V (C3 - 25 A) | |
| ≤ 80 V (D1 - 1 kA) | |
| Voltage protection level Up(line-earth) | ≤ 1.4 kV (C1 - 1 kV / 500 A) |
| ≤ 1.4 kV (C2 - 2 kV/1 kA) | |
| ≤ 1.4 kV (C2 - 10 kV / 5 kA) | |
| ≤ 1.4 kV (C3 - 25 A) | |
| ≤ 1.4 kV (C3 - 100 A) | |
| ≤ 1.4 kV (D1 - 1 kA) | |
| Voltage protection level Up(shield-ground) | ≤ 600 V (C1 - 0.5 kV / 250 A) |
| ≤ 650 V (C1 - 1 kV / 500 A) | |
| ≤ 650 V (C2 - 2 kV/1 kA) | |
| ≤ 650 V (C2 - 10 kV / 5 kA) | |
| ≤ 650 V (C3 - 10 A) | |
| ≤ 750 V (C3 - 25 A) | |
| ≤ 750 V (C3 - 100 A) | |
| ≤ 650 V (D1 - 1 kA) | |
| Response time tA(line-line) | ≤ 1 ns |
| Response time tA(line-earth) | ≤ 100 ns |
| Response time tA (shield-ground) | ≤ 100 ns |
| Input attenuation aE, sym. | typ. 0.5 dB (≤ 1 MHz / 50 Ω) |
| typ. 0.2 dB (≤ 400 kHz / 150 Ω) | |
| Cut-off frequency fg (3 dB), sym. in 50 Ω system | typ. 6 MHz |
| Cut-off frequency fg (3 dB), sym. in 150 Ω system | typ. 2.5 MHz |
| Resistance per path | 2.2 Ω ±10 % |
| Surge protection fault message | none |
| Impulse durability (line-line) | C1 - 1 kV / 500 A |
| C2 - 10 kV / 5 kA | |
| C3 - 25 A | |
| D1 - 1 kA | |
| Impulse durability (line-earth) | C1 - 1 kV / 500 A |
| C2 - 10 kV / 5 kA | |
| C3 - 100 A | |
| D1 - 1 kA | |
| Impulse durability (shield-ground) | C1 - 1 kV/500 A |
| C2 - 10 kV/5 kA | |
| C3 - 100 A | |
| D1 - 1 kA | |
| Alternating current carrying capacity (line-earth) | 10 A - 1 s |
| Alternating current carrying capacity (shield-ground) | 10 A - 1 s |
| Ambient conditions | |
| Degree of protection | IP67 |
| Ambient temperature (operation) | -40 °C ... 50 °C |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Altitude | ≤ 2000 m (amsl) |
| Conformity/Approvals | |
| ATEX | II 1G Ex ia IIC T4...T6 Ga |
| IECEx | Ex ia IIC T4...T6 Ga |
| Air clearances and creepage distances | |
| Standards/regulations | IEC 60664-1 / EN 60079-0 / EN 60079-11 |
| Standards/specifications | EN 61643-21 |
| Note | A2:2013 |
| Standards/specifications | EN 60079-0 |
| Note | 2018 |
| Standards/specifications | EN 60079-11 |
| Note | 2012 |
| Standards/specifications | IEC 60079-0 |
| Note | 2017 |
| Standards/specifications | IEC 60079-11 |
| Note | 2011 |
| Mounting type | direct screw connection |