Ensuring reliable signal transmission in automated processes, the Phoenix Contact S-PT-1X2-24DC 2880668 PHOENIX CONTACT Surge protection device offers dependable defense against unexpected electrical transients. Automation engineers rely on dedicated surge suppressors to extend the lifespan of valuable field devices and controllers.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Nominal voltage DC (EF008799): 24 V
More info
▲Key Commercial Data
| Orderkey | 2880668 |
|---|---|
| Packing unit | 1 pc |
| Note | Made to Order (non-returnable) |
| Catalog page | Page 101 (C-4-2017) |
| GTIN | 4046356049009 |
| Weight per Piece (excluding packing) | 352.520 g |
| Custom tariff number | 85363010 |
| Country of origin | DE (Germany) |
Ambient conditions
| Ambient temperature (operation) | -40 °C ... 85 °C |
|---|---|
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Altitude | ≤ 2000 m (amsl (above mean sea level)) |
| Degree of protection | IP67 |
General
| Housing material | Zinc die-cast, surface bronzed and nickel-plated |
|---|---|
| Color | silver |
| Standards for cearances and creepage distances | IEC 60664-1 |
| VDE 0110-1 | |
| Mounting type | direct screw connection |
| Type | Screw-in module |
| Number of positions | 3 |
| Direction of action | Line-Line & Line-Earth Ground |
Protective circuit
| IEC test classification | C1 |
|---|---|
| C2 | |
| C3 | |
| D1 | |
| Nominal voltage UN | 24 V DC |
| Maximum continuous voltage UC | 40 V DC |
| 28 V AC | |
| Rated current | 450 mA (55 °C) |
| Operating effective current ICat UC | ≤ 10 µA |
| Residual current IPE | ≤ 2 µA |
| Nominal discharge current In(8/20) µs (line-line) | 10 kA |
| Nominal discharge current In(8/20) µs (line-earth) | 10 kA (per path) |
| Nominal discharge current In(8/20) µs (shield-earth) | 10 kA (optional) |
| Pulse discharge current Iimp(10/350) µs | 1 kA |
| Total discharge current Itotal(8/20) µs | 20 kA |
| Total discharge current Itotal(10/350) µs | 2 kA |
| Max. discharge current Imax(8/20) µs maximum (line-line) | 10 kA |
| Max. discharge current Imax(8/20) µs maximum (line-earth) | 10 kA (per path) |
| Max. discharge current Imax(8/20) µs maximum (shield-earth) | 10 kA |
| Nominal pulse current Ian (10/1000) µs (line-line) | 23 A |
| Nominal pulse current Ian (10/1000) µs (line-earth) | 100 A |
| Nominal pulse current Ian (10/1000) µs (Shield-Earth) | 100 A |
| Output voltage limitation at 1 kV/µs (line-line) spike | ≤ 55 V |
| Output voltage limitation at 1 kV/µs (line-earth) spike | ≤ 450 V (Direct grounding) |
| Output voltage limitation at 1 kV/µs (shield-earth) spike | ≤ 600 V (optional) |
| Output voltage limitation at 1 kV/µs (line-line) static | ≤ 55 V |
| Output voltage limitation at 1 kV/µs (line-earth) static | ≤ 450 V (Direct grounding) |
| Residual voltage at In(line-line) | ≤ 55 V |
| Residual voltage with Ian (10/1000) µs (line-line) | ≤ 65 V |
| Voltage protection level Up(line-line) | ≤ 80 V (C2 - 10 kV / 5 kA) |
| Voltage protection level Up(line-earth) | ≤ 450 V (C2 - 10 kV / 5 kA) |
| Voltage protection level Up(shield-ground) | ≤ 600 V (C2 - 10 kV / 5 kA) |
| Voltage protection level Upstatic (line-line) | ≤ 50 V (C2 - 10 kV / 5 kA) |
| Response time tA(line-line) | ≤ 1 ns |
| Response time tA(line-earth) | ≤ 100 ns |
| Response time tA (shield-earth) | ≤ 100 ns |
| Input attenuation aE, sym. | typ. 0.5 dB (≤ 1.5 MHz / 50 Ω) |
| typ. 0.2 dB (≤ 300 kHz / 150 Ω) | |
| Cut-off frequency fg (3 dB), sym. in 50 Ohm system | typ. 6 MHz |
| Cut-off frequency fg (3 dB), sym. in 150 Ohm system | typ. 2 MHz |
| Resistance in series | 2.2 Ω ±10 % |
| Surge protection fault message | none |
| Max. required back-up fuse | 500 mA (T) |
| Impulse durability (line-line) | C2 - 10 kV/5 kA |
| D1 - 1 kA | |
| Impulse durability (line-earth) | C2 - 10 kV/5 kA |
| D1 - 1 kA | |
| Impulse durability (shield-earth) | C2 - 10 kV / 5 kA |
| D1 - 1 kA |
Connection data
| Connection method | Screw connection |
|---|---|
| Connection method IN | Screw terminal blocks |
| Connection method OUT | Connection line |
| Connection technology | Screw connection |
| Screw thread | M3 |
| Tightening torque | 0.6 Nm |
| Stripping length | 6 mm |
| Conductor cross section flexible | 0.14 mm² ... 1.5 mm² |
| Conductor cross section solid | 0.14 mm² ... 1.5 mm² |
| Conductor cross section AWG | 26 ... 16 |
Environmental Product Compliance
| China RoHS | Environmentally Friendly Use Period = 50 |
|---|---|
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |