PHOENIX CONTACT F-MS 12 ST F-MS 12 ST 2817990 PHOENIX CONTACT Type 2 surge protection plug View larger
Images are for illustrative purposes only. Please refer to data sheet for details

F-MS 12 ST 2817990 PHOENIX CONTACT Type 2 surge protection plug

F-MS 12 ST

2817990

PHOENIX CONTACT

1 Pcs.

Type 2 surge protection plug Plug-in protection against type 2 surges, with N-PE sum current arc arrester, for base element.

Automation > Accessories/spare parts for surge protection power supply systems
Trabtech (TT)

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

The Phoenix Contact F-MS 12 ST (2817990) functions as a Type 2 surge protection plug utilized in electrical distribution setups to limit transient overvoltages and protect downstream machinery. These replaceable suppression plugs serve as a frontline defense within industrial control panels, maintaining system uptime by absorbing high-energy electrical disturbances. Pricing, availability and lead time are confirmed per enquiry through an RFQ.

  • Orderkey: 2817990
  • Packing unit: 10 pc
  • Catalog page: Page 63 (C-4-2017)
  • GTIN: 4017918163648
  • Weight per Piece (excluding packing): 35.560 g
  • Custom tariff number: 85363010
  • Country of origin: DE (Germany)
  • Height: 52.4 mm
  • Width: 17.5 mm
  • Depth: 55.3 mm
  • Horizontal pitch: 1 Div.
  • Degree of protection: IP20
  • Ambient temperature (operation): -40 °C ... 80 °C
  • Ambient temperature (storage/transport): -40 °C ... 80 °C
  • Altitude: ≤ 2000 m (amsl (above mean sea level))
  • Permissible humidity (operation): 5 % ... 95 %

More info

▲

Key Commercial Data

Orderkey2817990
Packing unit10 pc
Catalog pagePage 63 (C-4-2017)
GTIN4017918163648
Weight per Piece (excluding packing)35.560 g
Custom tariff number85363010
Country of originDE (Germany)

Dimensions

Height52.4 mm
Width17.5 mm
Depth55.3 mm
Horizontal pitch1 Div.

Ambient conditions

Degree of protectionIP20
Ambient temperature (operation)-40 °C ... 80 °C
Ambient temperature (storage/transport)-40 °C ... 80 °C
Altitude≤ 2000 m (amsl (above mean sea level))
Permissible humidity (operation)5 % ... 95 %
Shock (operation)25g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
Vibration (operation)5g (10 ... 500 Hz / 2.5 h / X, Y, Z)

General

IEC test classificationII
T2
EN typeT2
IEC power supply systemTN
TT
Mode of protectionN-PE
Mounting typeon base element
Colorjet black RAL 9005
Housing materialPA 6.6
Degree of pollution2
Flammability rating according to UL 94V-0
TypeMale
Number of positions1
Arrester can be tested with CHECKMASTER from software version:From SW rev. 1.10
Surge protection fault messageoptical

Protective circuit

Nominal voltage UN240/415 V AC (TN - only N-PE)
240/415 V AC (TT - only N-PE)
Nominal frequency fN50 Hz (60 Hz)
Maximum continuous voltage UC260 V AC
Residual current IPE≤ 5 µA
Standby power consumption PC≤ 1.5 mVA
Nominal discharge current In(8/20) µs20 kA
Maximum discharge current Imax(8/20) µs40 kA
Follow current interrupt rating Ifi100 A (260 V)
Voltage protection level Up≤ 1.5 kV
Residual voltage Ures≤ 0.4 kV (at In)
≤ 0.25 kV (at 10 kA)
≤ 0.15 kV (at 5 kA)
≤ 0.1 kV (at 3 kA)
Front of wave sparkover voltage at 6 kV (1.2/50) µs≤ 1.5 kV
TOV behavior at UT1200 V AC (200 ms / withstand mode)
Response time tA≤ 100 ns

Connection data

Connection methodpluggable

UL specifications

SPD Type4CA
Maximum continuous operating voltage MCOV (N-G)260 V AC
Mode of protectionN-G
Power distribution systemSingle phase
Nominal frequency50/60 Hz
Measured limiting voltage MLV (N-G)1490 V
Nominal discharge current In(N-G)20 kA

Standards and Regulations

Standards/regulationsIEC 61643-11 2011
EN 61643-11 2012

Classifications


Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.