View larger
VAL-MS 750/30-ST 2920256 PHOENIX CONTACT Type 2 surge protection plug
VAL-MS 750/30-ST
2920256
PHOENIX CONTACT
1 Pcs.
Automation > Accessories/spare parts for surge protection power supply systems
Trabtech (TT)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
The VAL-MS 750/30-ST type 2 surge protection plug by Phoenix Contact intercepts transient overvoltages to protect sensitive industrial electronics and distribution grids. Surge protective plugs are deployed in main control panels to safeguard downstream equipment against lightning and switching surges.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Orderkey: 2920256
- Packing unit: 10 pc
- Catalog page: Page 56 (C-4-2017)
- GTIN: 4046356157308
- Weight per Piece (excluding packing): 62.000 g
- Custom tariff number: 85363030
- Country of origin: DE (Germany)
- Height: 52.4 mm
- Width: 17.5 mm
- Depth: 55.3 mm
- Horizontal pitch: 1 Div.
- Degree of protection: IP20
- Ambient temperature (operation): -40 °C ... 80 °C
- Ambient temperature (storage/transport): -40 °C ... 80 °C
- Altitude: ≤ 2000 m (amsl (above mean sea level))
- Permissible humidity (operation): 5 % ... 95 %
More info
▲Key Commercial Data
| Orderkey | 2920256 |
|---|---|
| Packing unit | 10 pc |
| Catalog page | Page 56 (C-4-2017) |
| GTIN | 4046356157308 |
| Weight per Piece (excluding packing) | 62.000 g |
| Custom tariff number | 85363030 |
| Country of origin | DE (Germany) |
Ambient conditions
| Degree of protection | IP20 |
|---|---|
| Ambient temperature (operation) | -40 °C ... 80 °C |
| Ambient temperature (storage/transport) | -40 °C ... 80 °C |
| Altitude | ≤ 2000 m (amsl (above mean sea level)) |
| Permissible humidity (operation) | 5 % ... 95 % |
| Shock (operation) | 25g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z) |
| Vibration (operation) | 5g (10 ... 500 Hz / 2.5 h / X, Y, Z) |
General
| IEC test classification | II |
|---|---|
| T2 | |
| EN type | T2 |
| IEC power supply system | TN |
| TT | |
| Mode of protection | L-PE |
| L-PEN | |
| Mounting type | on base element |
| Color | jet black RAL 9005 |
| Housing material | PA 6.6 |
| Degree of pollution | 2 |
| Distance between live and grounded parts | 8 mm |
| Flammability rating according to UL 94 | V-0 |
| Type | Male |
| Number of positions | 1 |
| Surge protection fault message | optical |
Additional descriptions
| Note | For use in all low-voltage systems between L-PEN. Only for use in IT systems between L-PE if the bodies of the equipment in the low-voltage system are connected to the grounding system of the transformer station. (common grounding of the HV transformer station and the bodies of the LV consumer's installation. RE= RAaccording to IEC 60364-4-442/VDE 0100-442 Figure 44D/example a) |
|---|
Protective circuit
| Nominal voltage UN | 554/960 V AC (TN) |
|---|---|
| 690 V AC (IT) | |
| Nominal frequency fN | 50 Hz (60 Hz) |
| Maximum continuous voltage UC | 760 V AC |
| Residual current IPE | ≤ 0.5 mA |
| Standby power consumption PC | ≤ 400 mVA |
| Nominal discharge current In(8/20) µs | 15 kA |
| Maximum discharge current Imax(8/20) µs | 30 kA |
| Short-circuit current rating ISCCR | 25 kA |
| Voltage protection level Up | ≤ 2.9 kV |
| Residual voltage Ures | ≤ 2.9 kV (at In) |
| ≤ 2.7 kV (at 10 kA) | |
| ≤ 2.5 kV (at 5 kA) | |
| ≤ 2.3 kV (at 3 kA) | |
| TOV behavior at UT | 1000 V AC (5 s / withstand mode) |
| 1056 V AC (120 min / safe failure mode) | |
| Response time tA | ≤ 25 ns |
| Max. backup fuse with branch wiring | 100 A (gG) |
UL specifications
| SPD Type | 4CA |
|---|---|
| Maximum continuous operating voltage MCOV (L-N) | 750 V AC |
| Nom. voltage | 690 V AC |
| Mode of protection | L-N |
| Power distribution system | Single phase |
| Nominal frequency | 50/60 Hz |
| Measured limiting voltage MLV (L-N) | 2700 V |
| Nominal discharge current In(L-N) | 10 kA |
Environmental Product Compliance
| China RoHS | Environmentally friendly use period: unlimited = EFUP-e |
|---|---|
| No hazardous substances above threshold values |