View larger
PT 3-PB-ST 2858030 PHOENIX CONTACT Surge protection plug
PT 3-PB-ST
2858030
PHOENIX CONTACT
1 Pcs.
Automation > Surge protection device for data networks/MCR-technology
Trabtech (TT)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Designed for easy replacement, the Phoenix Contact PT 3-PB-ST surge protection plug helps maintain continuous operation in automation networks by absorbing harmful electrical surges. Modular plug-in suppressors are commonly integrated into multi-tier terminal setups to protect low-voltage communication lines and field devices from destructive transient events. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Nominal voltage AC (EF008798): 5 V
More info
▲Key Commercial Data
| Orderkey | 2858030 |
|---|---|
| Packing unit | 10 pc |
| Catalog page | Page 154 (C-4-2017) |
| GTIN | 4017918878030 |
| Weight per Piece (excluding packing) | 20.530 g |
| Custom tariff number | 85363090 |
| Country of origin | DE (Germany) |
Dimensions
| Height | 45 mm |
|---|---|
| Width | 17.7 mm |
| Depth | 52 mm |
| Horizontal pitch | 1 Div. |
| Complete module height | 90 mm |
| Complete module width | 17.7 mm |
| Complete module depth | 65.5 mm |
Ambient conditions
| Ambient temperature (operation) | -40 °C ... 85 °C |
|---|---|
| Altitude | max. 2000 m |
| Degree of protection | IP20 |
General
| Housing material | PA |
|---|---|
| Flammability rating according to UL 94 | V-0 |
| Color | black |
| Standards for cearances and creepage distances | DIN EN 61664-1 |
| IEC 60664-1 | |
| Mounting type | on base element |
| Type | Male |
| Number of positions | 2 |
| Direction of action | Line-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-Earth Ground |
| Arrester can be tested with CHECKMASTER from software version: | From SW rev. 1.10 |
Protective circuit
| IEC test classification | C1 |
|---|---|
| C2 | |
| C3 | |
| D1 | |
| VDE requirement class | C1 |
| C2 | |
| C3 | |
| D1 | |
| Nominal voltage UN | 5 V DC |
| Maximum continuous voltage UC | 5.2 V DC |
| 3.6 V AC | |
| Rated current | 450 mA (45°C) |
| Operating effective current ICat UC | ≤ 300 µA |
| Residual current IPE | ≤ 300 µA (with PT 1X2-BE) |
| ≤ 1 µA (with PT 1X2+F-BE) | |
| Nominal discharge current In(8/20) µs (line-line) | 10 kA |
| Nominal discharge current In(8/20) µs (line-earth) | 10 kA |
| Pulse discharge current Iimp(10/350) µs | 2.5 kA |
| Total discharge current Itotal(8/20) µs | 20 kA |
| Max. discharge current Imax(8/20) µs maximum (line-line) | 10 kA |
| Max. discharge current Imax(8/20) µs maximum (line-earth) | 10 kA |
| Nominal pulse current Ian (10/1000) µs (line-line) | 90 A |
| Output voltage limitation at 1 kV/µs (line-line) spike | ≤ 55 V |
| Output voltage limitation at 1 kV/µs (line-earth) spike | ≤ 55 V (with PT 1X2-BE) |
| ≤ 700 V (with PT 1X2+F-BE) | |
| Output voltage limitation at 1 kV/µs (line-line) static | ≤ 15 V |
| Output voltage limitation at 1 kV/µs (line-earth) static | ≤ 15 V |
| ≤ 30 V (with PT 1X2+F-BE) | |
| Residual voltage at In(line-line) | ≤ 15 V |
| Residual voltage at In(line-earth) | ≤ 30 V (with PT 1X2-BE) |
| Residual voltage at In(line-signalground) | ≤ 15 V (with PT 1X2-BE) |
| Residual voltage with Ian (10/1000) µs (line-line) | ≤ 15 V |
| Residual voltage with Ian (10/1000) µs (line-signalground) | ≤ 15 V |
| Voltage protection level Up(line-line) | ≤ 70 V (C1 - 1 kV/500 A) |
| ≤ 45 V (C3 - 25 A) | |
| ≤ 100 V (C2 - 10 kV / 5 kA) | |
| ≤ 70 V (6 kV / 3 kA) | |
| Voltage protection level Up(line-earth) | ≤ 80 V (C1 - 1 kV/500 A) |
| ≤ 110 V (C2 - 10 kV / 5 kA) | |
| ≤ 100 V (6 kV / 3 kA) | |
| ≤ 45 V (C3 - 25 A) | |
| Voltage protection level Up(line-signalground) | ≤ 45 V (C3 - 25 A) |
| Response time tA(line-line) | ≤ 500 ns |
| Response time tA (line-signalground) | ≤ 500 ns |
| Response time tA(line-earth) | ≤ 500 ns |
| Input attenuation aE, sym. | typ. 0.3 dB (≤ 5 MHz / 100 Ω) |
| Cut-off frequency fg (3 dB), sym. in 100 Ohm system | typ. 60 MHz |
| Capacity (line-line) | typ. 30 pF |
| Resistance in series | 2.2 Ω ±10 % (7-8/11-12) |
| Max. required back-up fuse | 500 mA (T) |
| Impulse durability (line-line) | C2 - 10 kV/5 kA |
| C3 - 90 A | |
| Impulse durability (line-earth) | C2 - 10 kV/5 kA |
| C3 - 90 A | |
| D1 - 2.5 kA |
Connection data
| Connection method | Screw connection (in connection with the base element) |
|---|---|
| Screw thread | M3 |
| Tightening torque | 0.8 Nm |
| Stripping length | 8 mm |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross section solid | 0.2 mm² ... 4 mm² |
| Conductor cross section AWG | 24 ... 12 |
Connection, equipotential bonding
| Stripping length | 8 mm |
|---|---|
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 2.5 mm² |
| Conductor cross section solid min. | 0.2 mm² |
| Conductor cross section solid max. | 4 mm² |
| Conductor cross section AWG min. | 24 |
| Conductor cross section AWG max. | 12 |