View larger
PT 2-TELE-ST 2838733 PHOENIX CONTACT Surge protection plug
PT 2-TELE-ST
2838733
PHOENIX CONTACT
1 Pcs.
Automation > Surge protection device for data networks/MCR-technology
Trabtech (TT)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Serving as a surge protection plug, the Phoenix Contact PT 2-TELE-ST 2838733 protects telecommunication and signal interfaces from destructive voltage surges. Systems engineers use these pluggable modules to safeguard communication lines against lightning strikes and operational switching transients. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Nominal voltage AC (EF008798): 185 V
More info
▲Key Commercial Data
| Orderkey | 2838733 |
|---|---|
| Packing unit | 10 pc |
| Catalog page | Page 164 (C-4-2017) |
| GTIN | 4046356044677 |
| Weight per Piece (excluding packing) | 28.940 g |
| Custom tariff number | 85363010 |
| Country of origin | DE (Germany) |
Dimensions
| Height | 45 mm |
|---|---|
| Width | 17.7 mm |
| Depth | 52 mm |
| Horizontal pitch | 1 Div. |
| Complete module height | 90 mm |
| Complete module width | 17.7 mm |
| Complete module depth | 65.5 mm |
Ambient conditions
| Ambient temperature (operation) | -40 °C ... 85 °C |
|---|---|
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Degree of protection | IP20 |
General
| Housing material | PA 6.6 |
|---|---|
| Flammability rating according to UL 94 | V-0 |
| Color | jet black RAL 9005 |
| Mounting type | on base element |
| Type | Male |
| Number of positions | 2 |
| Direction of action | Line-Line & Line-Earth Ground |
Protective circuit
| IEC test classification | B2 |
|---|---|
| C1 | |
| C2 | |
| C3 | |
| D1 | |
| Nominal voltage UN | 185 V DC |
| 130 V AC | |
| Maximum continuous voltage UC | 185 V DC |
| 130 V AC | |
| Rated current | 450 mA AC (45°C) |
| 130 mA DC (45°C) | |
| Operating effective current ICat UC | ≤ 10 µA |
| Residual current IPE | ≤ 10 µA |
| Nominal discharge current In(8/20) µs (line-line) | 10 kA |
| Nominal discharge current In(8/20) µs (line-earth) | 10 kA |
| Pulse discharge current Iimp(10/350) µs (line-line) | 1 kA |
| Pulse discharge current Iimp(10/350) µs (line-earth) | 1 kA |
| Total discharge current Itotal(8/20) µs | 18 kA |
| Max. discharge current Imax(8/20) µs maximum (line-earth) | 18 kA |
| Nominal pulse current Ian (10/700) µs (line-line) | 100 A |
| Nominal pulse current Ian (10/700) µs (line-earth) | 100 A |
| Output voltage limitation at 1 kV/µs (line-line) spike | ≤ 300 V |
| Output voltage limitation at 1 kV/µs (line-earth) spike | ≤ 300 V |
| Output voltage limitation at 1 kV/µs (line-line) static | ≤ 300 V |
| Output voltage limitation at 1 kV/µs (line-earth) static | ≤ 300 V |
| Residual voltage at In(line-line) | ≤ 160 V (C2 - 10 kV / 5 kA) |
| Residual voltage at In(line-earth) | ≤ 200 V (C2 - 10 kV / 5 kA) |
| Voltage protection level Up(line-line) | ≤ 250 V (B2 - 1 kV / 25 A) |
| ≤ 300 V (B2 - 4 kV / 100 A) | |
| ≤ 270 V (C1 - 1 kV/500 A) | |
| ≤ 300 V (C2 - 2 kV/1 kA) | |
| ≤ 320 V (C2 - 4 kV / 2 kA) | |
| ≤ 330 V (C2 - 10 kV / 5 kA) | |
| Voltage protection level Up(line-earth) | ≤ 250 V (B2 - 1 kV / 25 A) |
| ≤ 300 V (B2 - 4 kV / 100 A) | |
| ≤ 270 V (C1 - 1 kV/500 A) | |
| ≤ 300 V (C2 - 2 kV/1 kA) | |
| ≤ 320 V (C2 - 4 kV / 2 kA) | |
| ≤ 330 V (C2 - 10 kV / 5 kA) | |
| Response time tA(line-line) | ≤ 500 ns |
| Response time tA(line-earth) | ≤ 500 ns |
| Input attenuation aE, sym. | typ. 0.4 dB (≤ 5 MHz / 100 Ω) |
| Cut-off frequency fg (3 dB), sym. in 100 Ohm system | typ. 20 MHz |
| Capacity (line-line) | typ. 30 pF (f=1 MHz / VR= 0 V) |
| Capacity (line-earth) | typ. 30 pF (f=1 MHz / VR= 0 V) |
| Surge protection fault message | none |
| Impulse durability (line-line) | B2 - 4 kV/100 A |
| C1 - 1 kV/500 A | |
| C2 - 10 kV/5 kA | |
| C3 - 25 A | |
| D1 - 1 kA | |
| Impulse durability (line-earth) | B2 - 4 kV/100 A |
| C1 - 1 kV/500 A | |
| C2 - 10 kV/5 kA | |
| C3 - 25 A | |
| D1 - 1 kA |
Environmental Product Compliance
| China RoHS | Environmentally friendly use period: unlimited = EFUP-e |
|---|---|
| No hazardous substances above threshold values |