View larger
VAL-MS 60 ST 2807573 PHOENIX CONTACT Type 2 surge protection plug
VAL-MS 60 ST
2807573
PHOENIX CONTACT
1 Pcs.
Automation > Accessories/spare parts for surge protection power supply systems
Trabtech (TT)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Designed for low-voltage circuits, the VAL-MS 60 ST 2807573 PHOENIX CONTACT Type 2 surge protection plug limits transient overvoltages to protect sensitive industrial electronics. These modular protection plugs are commonly deployed across control automation layouts to maintain system reliability. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Orderkey: 2807573
- Packing unit: 10 pc
- Catalog page: Page 58 (C-4-2017)
- GTIN: 4017918075262
- Weight per Piece (excluding packing): 30.500 g
- Custom tariff number: 85363010
- Country of origin: DE (Germany)
- Height: 52.4 mm
- Width: 17.5 mm
- Depth: 55.3 mm
- Horizontal pitch: 1 Div.
- Degree of protection: IP20
- Ambient temperature (operation): -40 °C ... 80 °C
- Ambient temperature (storage/transport): -40 °C ... 80 °C
- Altitude: ≤ 2000 m (amsl (above mean sea level))
- Permissible humidity (operation): 5 % ... 95 %
More info
▲Key Commercial Data
| Orderkey | 2807573 |
|---|---|
| Packing unit | 10 pc |
| Catalog page | Page 58 (C-4-2017) |
| GTIN | 4017918075262 |
| Weight per Piece (excluding packing) | 30.500 g |
| Custom tariff number | 85363010 |
| Country of origin | DE (Germany) |
Ambient conditions
| Degree of protection | IP20 |
|---|---|
| Ambient temperature (operation) | -40 °C ... 80 °C |
| Ambient temperature (storage/transport) | -40 °C ... 80 °C |
| Altitude | ≤ 2000 m (amsl (above mean sea level)) |
| Permissible humidity (operation) | 5 % ... 95 % |
| Shock (operation) | 25g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z) |
| Vibration (operation) | 5g (10 ... 500 Hz / 2.5 h / X, Y, Z) |
General
| IEC test classification | II |
|---|---|
| T2 | |
| EN type | T2 |
| IEC power supply system | TN |
| Mode of protection | L-PEN |
| Mounting type | on base element |
| Color | jet black RAL 9005 |
| Housing material | PA 6.6 |
| Degree of pollution | 2 |
| Flammability rating according to UL 94 | V-0 |
| Type | Male |
| Number of positions | 1 |
| Arrester can be tested with CHECKMASTER from software version: | From SW rev. 1.10 |
| Surge protection fault message | optical |
Protective circuit
| Nominal voltage UN | 60 V AC (TN) |
|---|---|
| 60 V DC | |
| -48 V DC (RRH) | |
| Nominal frequency fN | 50 Hz (60 Hz) |
| Maximum continuous voltage UC | 75 V AC |
| 100 V DC | |
| Residual current IPE | ≤ 0.45 mA |
| Standby power consumption PC | ≤ 35 mVA |
| Nominal discharge current In(8/20) µs | 15 kA |
| Maximum discharge current Imax(8/20) µs | 40 kA |
| Short-circuit current rating ISCCR | 25 kA |
| Voltage protection level Up | ≤ 0.55 kV |
| Residual voltage Ures | ≤ 0.55 kV (at In) |
| ≤ 0.425 kV (at 10 kA) | |
| ≤ 0.325 kV (at 5 kA) | |
| ≤ 0.275 kV (at 3 kA) | |
| TOV behavior at UT | 100 V AC (5 s / withstand mode) |
| Response time tA | ≤ 25 ns |
| Max. backup fuse with branch wiring | 125 A AC (gG) |
| 50 A DC (gG) |
UL specifications
| SPD Type | 4CA |
|---|---|
| Maximum continuous operating voltage MCOV (L-N) | 75 V AC |
| Maximum continuous operating voltage MCOV (L+) - (L-) | 100 V DC |
| Nom. voltage | 60 V AC |
| Nominal voltage | 60 V DC |
| Mode of protection | L-N |
| (L+) - (L-) | |
| Power distribution system | Single phase |
| Nominal frequency | 50/60 Hz |
| Measured limiting voltage MLV (L-N) | 630 V |
| Measured limiting voltage MLV (L+) - (L-) | 810 V |
| Nominal discharge current In(L-N) | 10 kA |
| Nominal discharge current In(L+) - (L-) | 10 kA |