View larger
VAL-MS 500 ST 2807609 PHOENIX CONTACT Type 2 surge protection plug
VAL-MS 500 ST
2807609
PHOENIX CONTACT
1 Pcs.
Automation > Accessories/spare parts for surge protection power supply systems
Trabtech (TT)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Designed to handle severe voltage transients, the VAL-MS 500 ST 2807609 PHOENIX CONTACT Type 2 surge protection plug provides robust overvoltage protection for industrial power systems. Pluggable surge arresters are commonly installed within primary distribution boards to safeguard critical electrical loads from grid anomalies. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Orderkey: 2807609
- Packing unit: 10 pc
- Catalog page: Page 61 (C-4-2017)
- GTIN: 4017918075293
- Weight per Piece (excluding packing): 60.340 g
- Custom tariff number: 85363010
- Country of origin: DE (Germany)
- Height: 52.4 mm
- Width: 17.5 mm
- Depth: 55.3 mm
- Horizontal pitch: 1 Div.
- Degree of protection: IP20
- Ambient temperature (operation): -40 °C ... 80 °C
- Ambient temperature (storage/transport): -40 °C ... 80 °C
- Altitude: ≤ 2000 m (amsl (above mean sea level))
- Permissible humidity (operation): 5 % ... 95 %
More info
▲Key Commercial Data
| Orderkey | 2807609 |
|---|---|
| Packing unit | 10 pc |
| Catalog page | Page 61 (C-4-2017) |
| GTIN | 4017918075293 |
| Weight per Piece (excluding packing) | 60.340 g |
| Custom tariff number | 85363010 |
| Country of origin | DE (Germany) |
Ambient conditions
| Degree of protection | IP20 |
|---|---|
| Ambient temperature (operation) | -40 °C ... 80 °C |
| Ambient temperature (storage/transport) | -40 °C ... 80 °C |
| Altitude | ≤ 2000 m (amsl (above mean sea level)) |
| Permissible humidity (operation) | 5 % ... 95 % |
| Shock (operation) | 25g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z) |
| Vibration (operation) | 5g (10 ... 500 Hz / 2.5 h / X, Y, Z) |
General
| IEC test classification | II |
|---|---|
| T2 | |
| EN type | T2 |
| IEC power supply system | TN |
| IT | |
| Mode of protection | L-PE |
| L-PEN | |
| Mounting type | on base element |
| Color | jet black RAL 9005 |
| Housing material | PA 6.6 |
| Degree of pollution | 2 |
| Distance between live and grounded parts | 5 mm |
| Flammability rating according to UL 94 | V-0 |
| Type | DIN rail module, two-section, divisible |
| Number of positions | 1 |
| Arrester can be tested with CHECKMASTER from software version: | From SW rev. 1.10 |
| Surge protection fault message | optical |
Additional descriptions
| Note | Usable in all low-voltage systems between L-N or L-PEN. Only usable in IT Systems between L-PE, if the exposed-conductive-parts (bodies) of the equipment of the low-voltage installation is connected to the earthing arrangement of the transformer substation. (interconnected earthing arrangement of the HV-transformer substation with the bodies of the LV-installation. RE= RAaccordance to IEC 60364-4-442 / VDE 0100-442 Fig. 44D / Example a) |
|---|
Protective circuit
| Nominal voltage UN | 400/690 V AC (TN) |
|---|---|
| 500 V AC (IT) | |
| Nominal frequency fN | 50 Hz (60 Hz) |
| Maximum continuous voltage UC | 600 V AC |
| Residual current IPE | ≤ 0.45 mA |
| Standby power consumption PC | ≤ 250 mVA |
| Nominal discharge current In(8/20) µs | 15 kA |
| Maximum discharge current Imax(8/20) µs | 30 kA |
| Short-circuit current rating ISCCR | 25 kA |
| Voltage protection level Up | ≤ 2.7 kV |
| Residual voltage Ures | ≤ 2.7 kV (at In) |
| ≤ 2.5 kV (at 10 kA) | |
| ≤ 2.3 kV (at 5 kA) | |
| ≤ 2.2 kV (at 3 kA) | |
| TOV behavior at UT | 690 V AC (5 s / withstand mode) |
| 762 V AC (120 min / withstand mode) | |
| Response time tA | ≤ 25 ns |
| Max. backup fuse with branch wiring | 125 A (gG) |
UL specifications
| SPD Type | 4CA |
|---|---|
| Maximum continuous operating voltage MCOV (L-N) | 600 V AC |
| Nom. voltage | 500 V AC |
| Mode of protection | L-N |
| Power distribution system | Single phase |
| Nominal frequency | 50/60 Hz |
| Measured limiting voltage MLV (L-N) | 2370 V |
| Nominal discharge current In(L-N) | 10 kA |