View larger
VAL-CP-MCB-3S-350/40/FM 2882750 PHOENIX CONTACT Type 2 surge arrester
VAL-CP-MCB-3S-350/40/FM
2882750
PHOENIX CONTACT
1 Pcs.
Automation > Surge protection device for power supply systems
Trabtech (TT)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Phoenix Contact produces the VAL-CP-MCB-3S-350/40/FM Type 2 surge arrester to provide comprehensive overvoltage protection and integrated switching capabilities in power distribution setups. Installers rely on these modular components inside primary or secondary distribution panels to safeguard installations against voltage surges. Pricing, availability, and lead time are confirmed per enquiry through an RFQ.
- Product type: Surge arrester
- Product family: SEC Family
- IEC test classification: II
- EN type: T2
- IEC power supply system: TN-S
- Type: DIN rail module, two-section, divisible
- Number of positions: 4
- Surge protection fault message: Optical, remote indicator contact
- Data management status Article revision: 12
- Insulation characteristics Overvoltage category: III
- Pollution degree: 2
- Nominal frequency f N: 50 Hz (60 Hz)
- Indicator/remote signaling Connection name: Remote fault indicator contact
- Switching function: Changeover contact
- Operating voltage: 250 V AC
- Operating current: 1 mA AC ... 2 A AC
More info
▲| Product type | Surge arrester |
| Product family | SEC Family |
| IEC test classification | II |
| T2 | |
| EN type | T2 |
| IEC power supply system | TN-S |
| TT | |
| Type | DIN rail module, two-section, divisible |
| Number of positions | 4 |
| Surge protection fault message | Optical, remote indicator contact |
| Data management status | |
| Article revision | 12 |
| Insulation characteristics | |
| Overvoltage category | III |
| Pollution degree | 2 |
| Nominal frequency fN | 50 Hz (60 Hz) |
| Indicator/remote signaling | |
| Connection name | Remote fault indicator contact |
| Switching function | Changeover contact |
| Operating voltage | 250 V AC |
| 250 V DC | |
| Operating current | 1 mA AC ... 2 A AC |
| 1 mA DC ... 50 mA DC | |
| Connection protective circuit | |
| Connection method | Screw connection |
| Tightening torque | 3.5 Nm |
| Stripping length | 14 mm |
| Conductor cross section flexible | 4 mm² ... 25 mm² |
| Conductor cross section rigid | 4 mm² ... 35 mm² |
| Conductor cross section AWG | 18 ... 2 |
| Protective ground connection | |
| Connection method | Screw connection |
| Screw thread | M5 |
| Tightening torque | 4.5 Nm |
| Stripping length | 16 mm |
| Conductor cross section flexible | 2.5 mm² ... 16 mm² |
| Conductor cross section rigid | 2.5 mm² ... 25 mm² |
| Conductor cross section AWG | 12 ... 4 |
| Remote fault indicator contact | |
| Connection method | Pluggable screw connection |
| Screw thread | M2 |
| Tightening torque | 0.25 Nm |
| Stripping length | 7 mm |
| Conductor cross section flexible | 0.14 mm² ... 1.5 mm² |
| Conductor cross section rigid | 0.14 mm² ... 1.5 mm² |
| Conductor cross section AWG | 28 ... 16 |
| Dimensional drawing | |
| Width | 131.5 mm |
| Height | 101 mm |
| Depth | 76 mm |
| Horizontal pitch | 7.5 Div. |
| Color | light gray (RAL 7035) |
| black (RAL 9005) | |
| Flammability rating according to UL 94 | V-0 |
| CTI value of material | 600 |
| Insulating material | PBT-FR |
| Material group | I |
| Housing material | PBT-FR |
| Mode of protection | L-N |
| L-PE | |
| N-PE | |
| Direction of action | 3L-N & N-PE |
| Nominal voltage UN | 240/415 V AC (TN-S) |
| 240/415 V AC (TT) | |
| Nominal frequency fN | 50 Hz (60 Hz) |
| Maximum continuous operating voltage UC(L-N) | 350 V AC |
| Maximum continuous operating voltage UC(L-PE) | 350 V AC |
| Maximum continuous operating voltage UC(N-PE) | 264 V AC |
| Residual current IPE | ≤ 1 µA |
| Nominal discharge current In(8/20) µs (L-N) | 15 kA |
| Nominal discharge current In(8/20) µs (L-PE) | 15 kA |
| Nominal discharge current In(8/20) µs (N-PE) | 20 kA |
| Maximum discharge current Imax(8/20) µs | 30 kA |
| Follow current interrupt rating Ifi(N-PE) | 100 A |
| Short-circuit current rating ISCCR | 25 kA |
| Voltage protection level Up(L-N) | ≤ 2.5 kV |
| Voltage protection level Up(N-PE) | ≤ 1.7 kV |
| Residual voltage Ures(L-N) | ≤ 2.3 kV (at In) |
| ≤ 1.6 kV (at 10 kA) | |
| ≤ 1.3 kV (at 5 kA) | |
| ≤ 1 kV (at 3 kA) | |
| Residual voltage Ures(L-PE) | ≤ 2.5 kV (at In) |
| ≤ 2 kV (at 10 kA) | |
| ≤ 1.5 kV (at 5 kA) | |
| ≤ 1.1 kV (at 3 kA) | |
| Residual voltage Ures(N-PE) | ≤ 1.2 kV (at 10 kA) |
| ≤ 0.8 kV (at 5 kA) | |
| ≤ 0.5 kV (at 4 kA) | |
| ≤ 0.3 kV (at 3 kA) | |
| TOV behavior at UT(L-N) | 415 V AC (5 s / withstand mode) |
| 457 V AC (120 min / safe failure mode) | |
| TOV behavior at UT(N-PE) | 1200 V AC (200 ms / withstand mode) |
| Response time tA(L-N) | ≤ 25 ns |
| Response time tA(L-PE) | ≤ 100 ns |
| Response time tA(N-PE) | ≤ 100 ns |
| Max. backup fuse with V-type through wiring | 40 A (gG) |
| Ambient conditions | |
| Degree of protection | IP20 |
| Ambient temperature (operation) | -25 °C ... 60 °C |
| Ambient temperature (storage/transport) | -40 °C ... 80 °C |
| Altitude | ≤ 2000 m (amsl) |
| Permissible humidity (operation) | 5 % ... 95 % |
| Standards/specifications | IEC 61643-11 |
| Note | 2011 |
| Standards/specifications | EN 61643-11 |
| Note | 2012 |
| Standards/specifications | IEC 60364-4-443 |
| Standards/specifications | IEC 60364-5-534 |
| Mounting type | DIN rail: 35 mm |