PHOENIX CONTACT VAL-CP-MCB-3C-350/40/FM VAL-CP-MCB-3C-350/40/FM 2882776 PHOENIX CONTACT Type 2 surge arrester View larger
Images are for illustrative purposes only. Please refer to data sheet for details

VAL-CP-MCB-3C-350/40/FM 2882776 PHOENIX CONTACT Type 2 surge arrester

VAL-CP-MCB-3C-350/40/FM

2882776

PHOENIX CONTACT

1 Pcs.

Type 2 surge arrester Combination of type 2 surge protection and arrester pre-fuse, with monitoring of the discharger and pre-fuse, in combination with status indication and remote indication contact. Implementation: 4-conductor system (L1, L2, L3, PEN), NS 35 carrier rail mounting Combination of type 2 surge protection and arrester backup fuse, with monitoring of arrester and arrester backup fuse, in combination with a status indicator and remote indication contact. Design: 4-conductor system (L1, L2, L3, PEN), mounting on NS 35 DIN rail

Automation > Surge protection device for power supply systems
Trabtech (TT)

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

The VAL-CP-MCB-3C-350/40/FM 2882776 PHOENIX CONTACT Type 2 surge arrester is a protective electrical component engineered to safeguard sensitive installations from transient overvoltage spikes. Devices of this classification are typically deployed within industrial distribution panels to divert high-energy surges safely to earth, thereby preventing damage to downstream machinery and automation hardware. Pricing, availability and lead time are confirmed per enquiry through an RFQ.

  • Product type: Surge arrester
  • Product family: SEC Family
  • IEC test classification: II
  • EN type: T2
  • IEC power supply system: TN-C
  • Type: DIN rail module, two-section, divisible
  • Number of positions: 3
  • Surge protection fault message: Optical, remote indicator contact
  • Data management status Article revision: 11
  • Insulation characteristics Overvoltage category: III
  • Pollution degree: 2
  • Nominal frequency f N: 50 Hz (60 Hz)
  • Indicator/remote signaling Connection name: Remote fault indicator contact
  • Switching function: Changeover contact
  • Operating voltage: 250 V AC
  • Operating current: 1 mA AC ... 2 A AC

More info

▲
Technical data

Product properties
Product typeSurge arrester
Product familySEC Family
IEC test classificationII
T2
EN typeT2
IEC power supply systemTN-C
TypeDIN rail module, two-section, divisible
Number of positions3
Surge protection fault messageOptical, remote indicator contact
Data management status
Article revision11
Insulation characteristics
Overvoltage categoryIII
Pollution degree2

Electrical properties
Nominal frequency fN50 Hz (60 Hz)
Indicator/remote signaling
Connection nameRemote fault indicator contact
Switching functionChangeover contact
Operating voltage250 V AC
250 V DC
Operating current1 mA AC ... 2 A AC
1 mA DC ... 50 mA DC

Connection data
Connection protective circuit
Connection methodScrew connection
Tightening torque3.5 Nm
Stripping length14 mm
Conductor cross section flexible4 mm² ... 25 mm²
Conductor cross section rigid4 mm² ... 35 mm²
Conductor cross section AWG18 ... 2
Protective ground connection
Connection methodScrew connection
Screw threadM5
Tightening torque4.5 Nm
Stripping length16 mm
Conductor cross section flexible2.5 mm² ... 16 mm²
Conductor cross section rigid2.5 mm² ... 25 mm²
Conductor cross section AWG12 ... 4
Remote fault indicator contact
Connection methodPluggable screw connection
Screw threadM2
Tightening torque0.25 Nm
Stripping length7 mm
Conductor cross section flexible0.14 mm² ... 1.5 mm²
Conductor cross section rigid0.14 mm² ... 1.5 mm²
Conductor cross section AWG28 ... 16

Dimensions
Dimensional drawing
Width114 mm
Height101 mm
Depth76 mm
Horizontal pitch6.5 Div.

Material specifications
Colorlight gray (RAL 7035)
black (RAL 9005)
Flammability rating according to UL 94V-0
CTI value of material600
Insulating materialPBT-FR
Material groupI
Housing materialPBT-FR

Protective circuit
Mode of protectionL-PEN
Direction of action3L-N/PE
Nominal voltage UN240/415 V AC (TN-C)
Nominal frequency fN50 Hz (60 Hz)
Maximum continuous voltage UC350 V AC
Nominal discharge current In(8/20) µs15 kA
Maximum discharge current Imax(8/20) µs30 kA
Short-circuit current rating ISCCR25 kA
Voltage protection level Up≤ 2.5 kV
Residual voltage Ures≤ 2.3 kV (at In)
≤ 1.6 kV (at 10 kA)
≤ 1.3 kV (at 5 kA)
≤ 1 kV (at 3 kA)
TOV behavior at UT415 V AC (5 s / withstand mode)
457 V AC (120 min / safe failure mode)
Response time tA≤ 25 ns
Max. backup fuse with V-type through wiring40 A (gG)

Environmental and real-life conditions
Ambient conditions
Degree of protectionIP20
Ambient temperature (operation)-25 °C ... 60 °C
Ambient temperature (storage/transport)-40 °C ... 80 °C
Altitude≤ 2000 m (amsl)
Permissible humidity (operation)5 % ... 95 %

Standards and regulations
Standards/specificationsIEC 61643-11
Note2011
Standards/specificationsEN 61643-11
Note2012
Standards/specificationsIEC 60364-4-443
Standards/specificationsIEC 60364-5-534

Mounting
Mounting typeDIN rail: 35 mm

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.